13.5.3 U2U Wiring connection
NOTICE
Cooling units are factory wired for stand-alone operation. Do not connect the U2U network cabling before
setting the U2U network configuration/groups. Network communication conflicts and un-reliable display
readings will result.
Before you begin, refer to
Preparing for U2U Group Set Up
on page 57, and
Configuring U2U Network Settings
– or –
Contact Vertiv™ Technical Support at 1-800-543-2778 or https://www.vertiv.com/en-us/support/.
U2U Network Requirements
The network must be private:
•
Isolated from other network traffic.
•
Switches connecting the units must be dedicated to iCOM communication only.
•
Do not connect the U2U network to the building or IT network. If the U2U network experiences a failure, the
cooling units continue to operate independently.
iCOM supports up to 64 nodes on the U2U network. The following are considered nodes:
•
Input/output board (one in each cooling unit)
•
Large wall mount display
Small touchscreen displays on the cooling unit are not considered nodes because they are directly connected to the
input/output board in the unit, not the network.
Of the 64 nodes, up to 32 may be cooling unit input/output boards connected as a group. Table 12.6 below, provides U2U
network configuration examples.
Configuration Example
No. of Input/Output Boards (CoolingUnits)
No. of Wall Mount Displays
Private Switch Required?
A
2
0
No
B
2
1
Yes
C
3
0
Yes
D
8
1
Yes
E
32
5
Yes
F
32
32
Yes
Table 12.6 Example iCOM U2U Network Configurations
13 Hardware Installation
127
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...