Figure 12.16 DIP Switch Opening/DIP Switches Inside of 2T Sensor
Item
Description
1
Hole in sensor housing
2
Cover removed
3.
Referring to Table 12.4 below, and using the non-conductive tool, set the DIP switches for each sensor to its
number in the chain (from sticker applied in step
).
Figure 12.17 on the next page, shows a representation of the DIP switches.
4. Confirm that the DIP switches are set correctly for each sensor, and replace the housing cover if necessary.
Sensor Number/Address
DIP Switch Position
CANbus Node ID
Alternate Use
1
2
3
4
5
6
7
8
A
On
Off
Off
Off
On
Off
Off
Off
17
Temperature/Humidity
B
Off
On
Off
Off
On
Off
Off
Off
18
Temperature/Humidity
C
On
On
Off
Off
On
Off
Off
Off
19
Temperature/Humidity
D
Off
On
On
On
On
Off
Off
Off
30
Fluid inlet/outlet temperature
E
On
On
On
On
On
Off
Off
Off
31
Fluid inlet/outlet temperature
Table 12.4 DIP Switch Settings for Supply Air Aggregation Sensors
13 Hardware Installation
123
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...