background image

Fan Coil Thermostat

Specification & Installation Instructions

TFHB24F3XYZ1/100910

 

1

Fan Coil Thermostat with BACnet

®

 Communication Port

Technical Data

TFHB24F3XYZ1

Inputs 

1 Digital input (24Vac or dry contact) 

1 Analog input (humidification 0-10Vdc) 

1 Analog input (change over 10Kohms or dry contact) 

Outputs

1 Fan analog or 3 Fan speed dry contracts 24Vac, 1A max 3A in-rush 

2 Analog outputs (cooling and/or heating 0-10Vdc) 

1 Analog output (local reheat 0-10Vdc) 

2 Triacs output (cooling and/or heating) 24Vac, 0.3A max fused / triac 

1 Triacs output (local reheat) 24Vac, 0.3A max fused / triac 

Power supply 

22 to 26Vac 50/60Hz 

Power consumption 

1 VA max 

Set point range 

Temperature: 10ºC to 40ºC [50ºF to 104ºF], Humidity: 10 to 65%RH 

Control accuracy 

Temperature: ±0.4ºC [0.8ºF], Humidity: ±3.5% 

Proportional band 

0.5ºC to 5ºC [1ºF to 10ºF] adjustable (heat/cool/reheat independent) 

Dead band 

0.3ºC to 5ºC [0.6ºF to 10ºF] adjustable (heat/cool/reheat independent) 

Electrical connection 

0.8 mm

2

 [18 AWG] minimum 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative Humidity 

5 to 95 % non condensing 

Degree of protection of housing 

IP 30 (EN 60529) 

Weight 

160 g. [0.36 lb] 

Interface

C

F

%RH

MO TU WE TH FR SA SU

AM PM

..

..

Symbols on display 

Cooling ON 
A: Automatic 

Communication 
Status

Alarm status 

Heating ON 
A: Automatic 

Menu set-up Lock 

Energy saving mode 

Fan ON 
A: Automatic 

Programming mode
(Technician setting) 

%RH

Percentage of 
humidity 

Humidity

Dehumidification ON 

C

or

F

ºC: Celsius scale 
ºF: Fahrenheit scale 

Dimensions

A

B

C

D

E

-

Dimension 

Imperial (in) 

Metric (mm) 

A

2.85 73 

B

4.85 123 

C

1.00 24 

D

2.36 60 

E

3.27 83 

Features:

x

 

Attractive modern look with large LCD and backlight 

x

 

Icons driven information and 1 line of text information 

x

 

2 Pipes Analog, ON/OFF or Floating or  
4 Pipes Analog, ON/OFF with local re-heat function 

x

 

Auto fan and ON/OFF function enable or disable 

x

 

External humidity sensor input and dehumidification sequence  
(compensated by auto-activation of the reheat output) 

x

 

Precise achieve temperature control with programmable PI function 

x

 

Independent cooling & heating no occupancy set point 

x

 

Lockable Set point / Control mode 

x

 

Change over by contact or external temperature sensor 

x

 

Celsius or Fahrenheit scale selectable 

x

 Anti-freeze 

protection 

x

 BACnet

®

 MS/TP @ 9600, 19200, 38400, 76800bps 

x

 

Selectable device Instance and MAC Address via technician menu 

TFHB24F3XYZ1 

Содержание TFHB24F3XYZ1

Страница 1: ...5 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Interface C F RH MO TU WE TH FR SA SU AM PM Symbols on display Cooling ON A Automatic Communication Status Alarm status Heating ON A Automatic Menu set up Lock Energy saving mode Fan ON A Automatic Programming mode Technician setting RH Percentage of humidity Humidity Dehumidification ON Cor F ºC Celsius scale ºF ...

Страница 2: ...lse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse 7 Common Relay Common Relay Common Relay Common Relay Common Relay 8 Digital output 1 DO1 High High High High 9 Digital output 2 DO2 High Med High Med High Med High Med 10 Digital output 3 DO3 Analog Fan Speed A...

Страница 3: ...y the minimum value step 2 Maximum range 10 to 40ºC 50 to 104ºF Increment 0 5ºC 1ºF Default value 30ºC 86ºF 4 Locking the set point Display shows user setpnt locked and the status of the function You can lock or unlock the set point adjustment by end user If locked yes and lock symbol will appear Default value Unlocked NO 5 C Adjust internal set point Display shows adjust intern setpnt and the set...

Страница 4: ...cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normally heat NoHt is selected if contact is closed cooling mode will be activated if contact is opened heating mode will be activated When change over external sensor SENs is selected heating mode will be ac...

Страница 5: ... minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which signal output you want for reheat You can choose OFF no signal selected ANALOG heating only ANALOG heating fan ON OFF heating only ON OFF heating fan PULSE heating only PULSE heating fan output If yo...

Страница 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0ºC 0 6 to 10 0ºF Increment 0 1ºC 0 2ºF Default value 0 3ºC 0 6ºF 30 Anti cycling delay cooling contact protection for compressor Display shows cooling anti cycle minutes and the value in minutes of the delay to ...

Страница 7: ...ct the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 Occupancy contact Display shows Select occ contact Moon symbol is also displayed You can choose NO normally open or NC normally close contact Default value Normally open NO 39 No occupancy derogation time Display shows no occ delay overide minutes and the derogation time in minute NSB symbo...

Страница 8: ...ze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4ºC 39ºF heat and reheat will start even if thermostat is in OFF mode Heat and reheat will stop when temperature reach 5ºC 41ºF Default value Disable NO 45 Communication bauds rate Display shows adjust comport bauds rate and the value of the baud rate in kBps Select the desired bauds for communication...

Страница 9: ...e the humidity set point is displayed If you press on button or you will leave the humidity set point menu Humidity display In operation mode when humidity reading is displayed for 2 seconds if and alarm symbol are displayed the humidity sensor is not connected or short circuited RH RH D No occupancy mode When thermostat is in no occupancy mode moon symbol is displayed so set point for cooling and...

Страница 10: ...TFHB24F3XYZ1 Specification Installation Instructions 10 Notes ...

Страница 11: ...TFHB24F3XYZ1 Specification Installation Instructions 11 Notes ...

Страница 12: ...n Instructions 12 Notes Recycling at end of life At end of life please return the thermostat to your Neptronic local distributor for recycling If you need to find the nearest Neptronic authorized distributor please consult www neptronic com ...

Отзывы: