Neptronic TFHB24F3XYZ1 Скачать руководство пользователя страница 9

TFHB24F3XYZ1 

Specification & Installation Instructions

9

Operation Mode

Step Description 

Display 

A

At powering up, thermostat will light display and activate all LCD segments during 2 seconds. 

Illuminating the LCD. 

To illuminate the LCD, you just have to push onto any of the 4 buttons. LCD will light for 4 seconds. 

Temperature display 

In operation mode, thermostat will automatically display the temperature reading for 8 seconds. 
Humidity reading will be displayed for 2 seconds. 
If “

OFF

”, “

- - -

” and alarm symbol are displayed, the temperature sensor is not connected or short 

circuited. 

To change the scale between ºC and ºF, press on both 

'

 and 

’

 for 3 seconds.

C

B

Temperature set point display and adjustment

To display the set point, press two times on 

'

 or 

’

. Set point will be displayed during 3 seconds. 

To adjust set point, press on 

'

 or 

’

 while the temperature set point is displayed. 

Note: If set point adjustment has been locked, 

 symbol will be displayed.

C

C

C

Humidity set point display and adjustment

Humidity set point menu will be access by pushing 

 button for 5 seconds. When in this mode 

“ADJUST HUMIDTY SETPNT”

 is displayed. Set point will be displayed during 5 seconds. 

To adjust set point, press on 

'

 or 

’

 while the humidity set point is displayed. If you press on button 

 or 

, you will leave the humidity set point menu. 

Humidity display 

In operation mode, when humidity reading is displayed for 2 seconds, if “

- - -

” and alarm symbol are 

displayed, the humidity sensor is not connected or short circuited. 

%RH

%RH

D

No occupancy mode :

When thermostat is in no occupancy mode, moon symbol   is displayed, so set point for cooling 
and/or heating are increased as per the setting made in programming mode.  
If not locked, no occupancy mode can be derogated for a predetermined period by pressing onto 
any of the 3 buttons. During period of derogation the  symbol will flash. If   does not flash, the 
derogation period is finished or the no occupancy mode derogation has been locked in 
programming mode.

C

E

Control mode selection :

To change the control mode, press on 

. Control mode will be displayed during 5 seconds. You 

can choose one of the following: 

9

  Automatic Cooling or Heating 

9

  Cooling and Heating OFF 

9

 Cooling 

only 

9

 Heating 

only 

Note: These selections can vary according to the choice made on steps #6 & #7. 

F

Fan speed mode selection:

To change the fan speed mode, press on 

. Fan speed mode will be displayed during 5 seconds. 

You can choose one of the following: 

9

  Automatic speed (if not disable in programming mode) 

9

 Low 

speed 

9

 Medium 

speed 

9

 High 

speed 

Note: These selections can vary according to the choice made on step 

#33 & 

#36.

Содержание TFHB24F3XYZ1

Страница 1: ...5 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Interface C F RH MO TU WE TH FR SA SU AM PM Symbols on display Cooling ON A Automatic Communication Status Alarm status Heating ON A Automatic Menu set up Lock Energy saving mode Fan ON A Automatic Programming mode Technician setting RH Percentage of humidity Humidity Dehumidification ON Cor F ºC Celsius scale ºF ...

Страница 2: ...lse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse 7 Common Relay Common Relay Common Relay Common Relay Common Relay 8 Digital output 1 DO1 High High High High 9 Digital output 2 DO2 High Med High Med High Med High Med 10 Digital output 3 DO3 Analog Fan Speed A...

Страница 3: ...y the minimum value step 2 Maximum range 10 to 40ºC 50 to 104ºF Increment 0 5ºC 1ºF Default value 30ºC 86ºF 4 Locking the set point Display shows user setpnt locked and the status of the function You can lock or unlock the set point adjustment by end user If locked yes and lock symbol will appear Default value Unlocked NO 5 C Adjust internal set point Display shows adjust intern setpnt and the set...

Страница 4: ...cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normally heat NoHt is selected if contact is closed cooling mode will be activated if contact is opened heating mode will be activated When change over external sensor SENs is selected heating mode will be ac...

Страница 5: ... minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which signal output you want for reheat You can choose OFF no signal selected ANALOG heating only ANALOG heating fan ON OFF heating only ON OFF heating fan PULSE heating only PULSE heating fan output If yo...

Страница 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0ºC 0 6 to 10 0ºF Increment 0 1ºC 0 2ºF Default value 0 3ºC 0 6ºF 30 Anti cycling delay cooling contact protection for compressor Display shows cooling anti cycle minutes and the value in minutes of the delay to ...

Страница 7: ...ct the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 Occupancy contact Display shows Select occ contact Moon symbol is also displayed You can choose NO normally open or NC normally close contact Default value Normally open NO 39 No occupancy derogation time Display shows no occ delay overide minutes and the derogation time in minute NSB symbo...

Страница 8: ...ze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4ºC 39ºF heat and reheat will start even if thermostat is in OFF mode Heat and reheat will stop when temperature reach 5ºC 41ºF Default value Disable NO 45 Communication bauds rate Display shows adjust comport bauds rate and the value of the baud rate in kBps Select the desired bauds for communication...

Страница 9: ...e the humidity set point is displayed If you press on button or you will leave the humidity set point menu Humidity display In operation mode when humidity reading is displayed for 2 seconds if and alarm symbol are displayed the humidity sensor is not connected or short circuited RH RH D No occupancy mode When thermostat is in no occupancy mode moon symbol is displayed so set point for cooling and...

Страница 10: ...TFHB24F3XYZ1 Specification Installation Instructions 10 Notes ...

Страница 11: ...TFHB24F3XYZ1 Specification Installation Instructions 11 Notes ...

Страница 12: ...n Instructions 12 Notes Recycling at end of life At end of life please return the thermostat to your Neptronic local distributor for recycling If you need to find the nearest Neptronic authorized distributor please consult www neptronic com ...

Отзывы: