TFHB24F3XYZ1 

Specification & Installation Instructions

7

Step Display 

Description 

Values 

34 

Minimum voltage of the fan output:

Display shows 

“min vdc analog output fan”

 and the value of the 

minimum voltage of the fan ramp. 
Please select the desired value of the minimum voltage of the fan ramp. 
(This is the “zero” value) 

The minimum value is restricted by the maximum value. (step #35) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 0.0 Volt

35 

Maximum voltage of the fan output:

Display shows 

“max vdc analog output fan”

 and the value of the 

minimum voltage of the fan ramp. 
Please select the desired value of the maximum voltage of the fan ramp. 
(This is the “span” value) 

The maximum value is restricted by the minimum value. (step #34) 

Range: 0.0 to 10.0 Volt 
Increment: 0.1 Volt 

Default value: 10.0 Volt

36 

Set fan speed automatic mode enable or disable:

Display shows 

“enable fan auto mode”

. Fan 

 symbol is also displayed. 

You can enable or disable the Automatic mode adjustment by end user.  

If you selected to disable the automatic mode, go directly to step 
#38.

Default value: 
Enable (YES)

37 

Time out fan contact:

Display shows 

“fan auto timeout minutes”

 and the automatic shutoff delay 

value (in minutes) when there is no demand.
Please select the desired value of the automatic shutoff delay. 

Range: 0 to 15 min. 
Increment: 1 min. 

Default value: 2 min.

38 

Occupancy contact:

Display shows 

“Select occ contact”

. Moon   symbol is also displayed. 

You can choose NO (normally open) or NC (normally close) contact. 

Default value: 
Normally open (NO)

39 

No occupancy derogation time :

Display shows 

“no occ delay overide minutes”

 and the derogation time in 

minute. NSB   symbol is also displayed. 
Please select the desired derogation time. 
If no derogation time is desired select “0”. 

Range: 0 to 180 min. 
Increment: 15 min. 

Default value: 120 min.

40 

C

Heating Set point during no occupancy:

Display shows 

“no occ heating setpnt”

 and the value of the heating set 

point temperature during no occupancy period. Moon   and heating 
symbols are also displayed. 
Please select the heating set point temperature during no occupancy. 
The maximum value is restricted by the no occupancy cooling set point. 
(step # 41) 

Range: 10.0 to 40.0ºC [50 to 104ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 16.0ºC [61ºF]

41 

C

Cooling set point during no occupancy:

Display shows 

“no occ cooling setpnt”

 and the value of the cooling set 

point temperature during no occupancy period. Moon   and cooling 
symbols are also displayed. 
Please select the cooling set point temperature during no occupancy. 
The minimum value is restricted by the no occupancy heating set point. 
(step # 40) 

Range: 10.0 to 40.0ºC [50 to 104ºF] 
Increment: 0.5ºC [1ºF] 

Default value: 28.0ºC [82ºF]

Содержание TFHB24F3XYZ1

Страница 1: ...5 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Interface C F RH MO TU WE TH FR SA SU AM PM Symbols on display Cooling ON A Automatic Communication Status Alarm status Heating ON A Automatic Menu set up Lock Energy saving mode Fan ON A Automatic Programming mode Technician setting RH Percentage of humidity Humidity Dehumidification ON Cor F ºC Celsius scale ºF ...

Страница 2: ...lse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse 7 Common Relay Common Relay Common Relay Common Relay Common Relay 8 Digital output 1 DO1 High High High High 9 Digital output 2 DO2 High Med High Med High Med High Med 10 Digital output 3 DO3 Analog Fan Speed A...

Страница 3: ...y the minimum value step 2 Maximum range 10 to 40ºC 50 to 104ºF Increment 0 5ºC 1ºF Default value 30ºC 86ºF 4 Locking the set point Display shows user setpnt locked and the status of the function You can lock or unlock the set point adjustment by end user If locked yes and lock symbol will appear Default value Unlocked NO 5 C Adjust internal set point Display shows adjust intern setpnt and the set...

Страница 4: ...cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normally heat NoHt is selected if contact is closed cooling mode will be activated if contact is opened heating mode will be activated When change over external sensor SENs is selected heating mode will be ac...

Страница 5: ... minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which signal output you want for reheat You can choose OFF no signal selected ANALOG heating only ANALOG heating fan ON OFF heating only ON OFF heating fan PULSE heating only PULSE heating fan output If yo...

Страница 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0ºC 0 6 to 10 0ºF Increment 0 1ºC 0 2ºF Default value 0 3ºC 0 6ºF 30 Anti cycling delay cooling contact protection for compressor Display shows cooling anti cycle minutes and the value in minutes of the delay to ...

Страница 7: ...ct the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 Occupancy contact Display shows Select occ contact Moon symbol is also displayed You can choose NO normally open or NC normally close contact Default value Normally open NO 39 No occupancy derogation time Display shows no occ delay overide minutes and the derogation time in minute NSB symbo...

Страница 8: ...ze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4ºC 39ºF heat and reheat will start even if thermostat is in OFF mode Heat and reheat will stop when temperature reach 5ºC 41ºF Default value Disable NO 45 Communication bauds rate Display shows adjust comport bauds rate and the value of the baud rate in kBps Select the desired bauds for communication...

Страница 9: ...e the humidity set point is displayed If you press on button or you will leave the humidity set point menu Humidity display In operation mode when humidity reading is displayed for 2 seconds if and alarm symbol are displayed the humidity sensor is not connected or short circuited RH RH D No occupancy mode When thermostat is in no occupancy mode moon symbol is displayed so set point for cooling and...

Страница 10: ...TFHB24F3XYZ1 Specification Installation Instructions 10 Notes ...

Страница 11: ...TFHB24F3XYZ1 Specification Installation Instructions 11 Notes ...

Страница 12: ...n Instructions 12 Notes Recycling at end of life At end of life please return the thermostat to your Neptronic local distributor for recycling If you need to find the nearest Neptronic authorized distributor please consult www neptronic com ...

Отзывы: