TFHB24F3XYZ1 

Specification & Installation Instructions

2

Mounting Instructions 

A

E

D

C

B

CAUTION: Risk of malfunction. Remove power prior to separate thermostat cover from its base. 
A. 

Remove the screw (captive) holding the base and the front cover of the thermostat. 

B. 

Lift the front cover of the thermostat to separate it from the base. 

C. 

Pull wire through the base hole. 

D. 

Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections. 

E. 

Mount the control module on the base and secure using the screw. 

Terminal Description 

2 Pipe 

Analog 

On/Off 

Floating 

Terminals

Fan option

analog

1 spd 

2 spd 

3 spd 

analog

1 spd 

2 spd 

3 spd 

analog

1 spd 

2spd

3spd

TB1

1

Common 

Common Common Common 

2

24 Vac 

24 Vac 

24 Vac 

24 Vac 

3

Common Triac 

Common Triac 

Common Triac 

Common Triac 

4

Triac output 1 (TO1) 

Floating 
output 1 

2 Pipe on/off 

2 Pipe floating (close) 

5

Triac output 2 (TO2) 

2 Pipe floating (open) 

6

Triac output 3 (TO3) Reheat 

Local reheat (optional) (on/off or pulse)  Local reheat (optional) (on/off or pulse)  Local reheat (optional) (on/off or pulse) 

7

Common Relay 

Common Relay 

Common Relay 

Common Relay 

8

Digital 

output 

(DO1)  - - 

High 

- - 

High 

- - 

High 

9

Digital 

output 

(DO2)  - - 

High 

Med 

- - 

High 

Med 

- - 

High 

Med 

10

Digital output 3 (DO3) / 
Analog Fan Speed (AO4) 

Fan analog  1 spd 

Low 

Low 

Fan analog  1 spd 

Low 

Low 

Fan analog  1 spd 

Low 

Low 

11

Occupancy Sensor (DI1) 

Occupancy Sensor (optional) 

Occupancy Sensor (optional) 

Occupancy Sensor (optional) 

12

External Humidity Sensor (AI1) 

External Humidity Sensor (optional) 

External Humidity Sensor (optional) 

External Humidity Sensor (optional) 

13

External Changeover (AI2) 

External Changeover 

External Changeover 

External Changeover 

14

Analog output 1 (AO1) 

2 Pipe analog 

15

Analog output 2 (AO2) 

16

Analog output 3 (AO3) Reheat 

Local reheat analog (optional) 

Local reheat analog (optional) 

Local reheat analog (optional) 

17

A+

Communication 
port RS-485 

BACnet BACnet BACnet 

18

B- 

4 Pipe 

Cool & Heat Analog 

Cool & Heat On/Off 

Cool Analog-Heat On/Off or pulse 

Cool On/Off - Heat Analog 

Terminals

Fan option 

analog

1 spd  2 spd  3 spd

analog

1 spd 2 spd 3 spd

analog

1 spd 

2 spd  3 spd  analog

1 spd 2 spd 3 spd

TB1

1

Common Common 

Common 

Common 

Common 

2

24 Vac 

24 Vac 

24 Vac 

24 Vac 

24 Vc 

3

Common Triac 

Common Triac 

Common Triac 

Common Triac 

Common Triac 

4

Triac output 1 (TO1)  Floating 

output 1 

4 Pipe on/off cool 

4 Pipe on/off cool 

5

Triac output 2 (TO2) 

4 Pipe (on/off or pulse) heat 

4 Pipe (on/off or pulse) heat 

6

Triac output 3 (TO3) Reheat 

Local reheat 

(optional)(on/off or pulse)

 Local 

reheat 

(optional)(on/off or pulse)

 

Local reheat (optional)(on/off or pulse) 

Local reheat 

(optional)(on/off or pulse)

7

Common Relay 

Common Relay 

Common Relay 

Common Relay 

Common Relay 

8

Digital output 1 (DO1) 

- High 

- - 

- High 

- - 

- High 

- - 

- High 

9

Digital output 2 (DO2) 

High Med 

- - 

High Med 

- - 

High Med 

- - 

High Med 

10

Digital output 3 (DO3) / 
Analog Fan Speed (AO4) 

Fan analog  1 spd 

Low Low 

Fan analog 1 spd 

Low Low 

Fan analog 1 spd 

Low Low 

Fan analog 1 spd 

Low Low 

11

Occupancy Sensor (DI1) 

Occupancy Sensor (optional) 

Occupancy Sensor (optional) 

Occupancy Sensor (optional) 

Occupancy Sensor (optional) 

12

Ext. Humidity Sensor (AI1) 

Ext. Humidity Sensor (optional) 

Ext. Humidity Sensor (optional) 

Ext. Humidity Sensor (optional) 

Ext. Humidity Sensor (optional) 

13

External Changeover (AI2) 

14

Analog output 1 (AO1) 

4 Pipe analog cool 

4 Pipe analog cool 

15

Analog output 2 (AO2) 

4 Pipe analog heat 

4 Pipe analog heat 

16

Analog output 3 (AO3) Reheat  Local reheat analog (optional) 

Local reheat analog (optional) 

Local reheat analog (optional) 

Local reheat analog (optional) 

17

A+ 

Communication 
port RS-485 

BACnet BACnet BACnet 

BACnet 

18

B- 

Settings on PC Board

Connecting

strip TB1

Temperature
sensor

TB1

1
 

2
 

3
 

4
 

5
 

6
 

7
 

8
 

9
  

10 
 11
  1
2

   

13
  

14
   

15
  

16  

17
   

18

Mode selector

JP3

PG

M

R

UN

Dip
switch

ON

1  2  3

Triac output

signal selector

JP1

JP4

Fan output signal
selector

JP2

Digital output
signal selector

Triac Output Signal Selection (JP1) 

Mode Selection (JP3) 

Jumper (JP1) on top:

 All triac output 

signal is linked to internal 24Vac.
(Same 24Vac than thermostat)

PGM

RUN

JP3

Jumper (JP3) on RUN: 

Thermostat is in 

operation mode

.

Thermostat must be set in this mode to operate properly.
If not locked, set point, control mode and speed fan 
(Heating & Cooling ON, Cooling only ON or Heating only 
ON) may be modified by end user. 

Jumper (JP1) on bottom:

 All triac output 

signal is linked to external 24Vac.
(Different 24Vac than thermostat)

Digital Output Signal Selection (JP2) 

24VAC

Jumper (JP2) on left:

 All digital output 

signal is linked to internal 24Vac.
(Same 24Vac than thermostat)

PGM

RUN

JP3

Jumper (JP3) on PGM: 

Thermostat is set in 

Programming mode

.

Refer to following section about all settings description

Jumper (JP2) on right:

 All digital output 

signal is linked to external 24Vac.
(Different 24Vac than thermostat)

Fan Output Signal Selection (JP4) 

Bacnet dip switch (DS1) - Optional 

AO4

DO3

JP4

Jumper (JP4) on top: 

Pin 10 of TB1 is set to be digital output 
signal (DO3). 

ON

1     2     3

Pull up

120 ohm termination (Last node)

Pull down

AO4

DO3

JP4

Jumper (JP4) on bottom: 

Pin 10 of TB1 is set to be analog output 
signal (AO4). 

24VAC EXT.

EXT.

24VAC

24VAC

Содержание TFHB24F3XYZ1

Страница 1: ...5 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Interface C F RH MO TU WE TH FR SA SU AM PM Symbols on display Cooling ON A Automatic Communication Status Alarm status Heating ON A Automatic Menu set up Lock Energy saving mode Fan ON A Automatic Programming mode Technician setting RH Percentage of humidity Humidity Dehumidification ON Cor F ºC Celsius scale ºF ...

Страница 2: ...lse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse 7 Common Relay Common Relay Common Relay Common Relay Common Relay 8 Digital output 1 DO1 High High High High 9 Digital output 2 DO2 High Med High Med High Med High Med 10 Digital output 3 DO3 Analog Fan Speed A...

Страница 3: ...y the minimum value step 2 Maximum range 10 to 40ºC 50 to 104ºF Increment 0 5ºC 1ºF Default value 30ºC 86ºF 4 Locking the set point Display shows user setpnt locked and the status of the function You can lock or unlock the set point adjustment by end user If locked yes and lock symbol will appear Default value Unlocked NO 5 C Adjust internal set point Display shows adjust intern setpnt and the set...

Страница 4: ...cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normally heat NoHt is selected if contact is closed cooling mode will be activated if contact is opened heating mode will be activated When change over external sensor SENs is selected heating mode will be ac...

Страница 5: ... minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which signal output you want for reheat You can choose OFF no signal selected ANALOG heating only ANALOG heating fan ON OFF heating only ON OFF heating fan PULSE heating only PULSE heating fan output If yo...

Страница 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0ºC 0 6 to 10 0ºF Increment 0 1ºC 0 2ºF Default value 0 3ºC 0 6ºF 30 Anti cycling delay cooling contact protection for compressor Display shows cooling anti cycle minutes and the value in minutes of the delay to ...

Страница 7: ...ct the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 Occupancy contact Display shows Select occ contact Moon symbol is also displayed You can choose NO normally open or NC normally close contact Default value Normally open NO 39 No occupancy derogation time Display shows no occ delay overide minutes and the derogation time in minute NSB symbo...

Страница 8: ...ze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4ºC 39ºF heat and reheat will start even if thermostat is in OFF mode Heat and reheat will stop when temperature reach 5ºC 41ºF Default value Disable NO 45 Communication bauds rate Display shows adjust comport bauds rate and the value of the baud rate in kBps Select the desired bauds for communication...

Страница 9: ...e the humidity set point is displayed If you press on button or you will leave the humidity set point menu Humidity display In operation mode when humidity reading is displayed for 2 seconds if and alarm symbol are displayed the humidity sensor is not connected or short circuited RH RH D No occupancy mode When thermostat is in no occupancy mode moon symbol is displayed so set point for cooling and...

Страница 10: ...TFHB24F3XYZ1 Specification Installation Instructions 10 Notes ...

Страница 11: ...TFHB24F3XYZ1 Specification Installation Instructions 11 Notes ...

Страница 12: ...n Instructions 12 Notes Recycling at end of life At end of life please return the thermostat to your Neptronic local distributor for recycling If you need to find the nearest Neptronic authorized distributor please consult www neptronic com ...

Отзывы: