Event
Description
CAN GC 1 or 2
•
The Liebert® iCOM board cannot establish communication with the Liebert® MC condenser board for 10 seconds
consecutively.
•
Alarm notification displayed for the corresponding circuit.
•
EconoPhase pump operation disabled for the circuit affected.
•
When iCOM re-establishes communication with the Liebert® MC board, the event is reset.
GC 1 or 2 Rem
Shutdown
•
Remote shutdown requested.
•
Compressor(s) and EconoPhase pump(s) in the corresponding circuit are powered-off.
•
If event occurs on the lead circuit, then the lead-lag order of the compressors/tandem banks changes.
•
When the Liebert® MC condenser remote-shutdown circuit returns to inactive state (closed), the event is reset
and the compressors in that circuit may be powered-on.
•
Normal compressor lead-lag sequence resumes when both compressors are Off.
GC 1 or 2 Board Fail
An unrecoverable failure of the Liebert® MC condenser control board has occurred causing a condenser shutdown.
GC Pres Sens Fail C1
or C2
Condenser pressure sensor failure
GC High Cond Press
C1 or C2
High condensing pressure
GC Low Cond Press C1
or C2
Low condensing pressure
GC 1 or 2 Amb Sens
Fail
Ambient-temperature sensor failure
GC 1 or 2 Amb Temp
Limit
High/low ambient temperature
GC Temp Sens Fail C1
or C2
Refrigerant-liquid-line temperature-sensor failure
GC High Cond Temp
C1 or C2
High refrigerant liquid line temperature
Table 4.3 Events Specific to Liebert MC Condenser
4 Managing Events: Alarms, Warnings and Messages
49
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...