13 HARDWARE INSTALLATION
Your unit includes the Liebert® iCOM controller. This section describes the installation of connections and cabling to fully
utilize the iCOM features.
NOTE: Your Liebert® DSE™ Packaged Solution does not offer humidification or dehumidification functions. Please
disregard those settings/fields when mentioned in this guide or displayed on the iCOM controller.
13.1 Installing Wired Remote Sensors
Up to 10 remote sensor modules, installed in the monitored racks and connected to the cooling unit, provide control and
reference input to iCOM and building-management systems. Using remote, rack sensors combats cooling problems related
to recirculation air, uneven rack loading, and air distribution.
The sensor array consists of 2T sensors that each have two temperature probes on a 6 ft (1.8 m) probe-connection cable,
Figure 12.4 below, and requires several steps to prepare, connect, and begin monitoring the racks:
•
Set DIP switches in each sensor.
•
Terminate final sensor on CANbus link.
•
Install sensors on racks.
•
Install CANbus cabling between sensors.
•
Connect CANbus cable to the cooling unit.
•
Configure the sensors in iCOM.
NOTE: The 2T sensor shown in Figure 12.4 below, may differ slightly for your system, depending on equipment
installed.
Figure 12.4 2T Sensor for Rack Monitoring
13.1.1 Setting DIP Switches and Labeling 2T Sensors
Tools required:
•
Small non-conductive tool to set switches
•
Small Phillips head screw driver to open 2T housing.
Each sensor requires a unique address in the CANbus loop connected to the cooling unit. We recommend that you set the
DIP-switch sensor-number setting to correspond to the sensor’s location on the CANbus run. If settings are incorrect, the
control will not operate properly.
Vertiv™ | Liebert® iCOM™ Installer/User Guide
110
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...