Line
ID
Parameter
Name
Range
Default
Setting
Description
S1A7
Override
Integration Time
0.0 - 15.0 min
0.0 min
S1A8
Control Slew
Rate Filter
0.50 - 99.99
%/s
1.00 %/s
S1A9
Current
Override
Temperature
°F
°C
invalid
S1B1
Current
Override Value
0 - 100 %
0%
S1B9
Create
SuperSaver
Signal
0 = No
1 = Local
2 = U2U
Group AVG 3
= U2U
Group MAX 4
= U2U
Group MIN
0 (No)
S1C1
Deadband Low
Value
5 - 95 %
20%
S1C2
Deadband High
Value
10 - 100 %
90%
S1C3
Update
SuperSaver
Signal every
30 - 300 sec
120 sec
S1C4
Update
SuperSaver
Signal by
1 - 10 %
1%
S1C5
SuperSaver Max
Limit
0 - 100 %
100%
S1C6
Current
SuperSaver
Request
0 - 100 %
0%
Current
SuperSaver
Signal
0 - 100 %
0%
S1C7
U2U Aggregated
Signal
0 - 100 %
0%
XDU.006
Calibration
Leaving Air
Temperature
+/-18°F
0°F
Calibrate Supply Air Leaving Temperature sensor reading
XDU.008
Calibration
Entering Fluid
+/-18°F
0°F
Calibrate Entering Fluid Temperature sensor reading
Table B.2 Service Menu Setpoints by Line ID (continued)
Vertiv™ | Liebert® iCOM™ Installer/User Guide
144
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...