Line
ID
Parameter
Name
Range
Default
Setting
Description
calculate the corresponding RH% based on that sensors actual temperature.
S125
Dew Point
Setpoint
41 - 65
◦
F
5.0 - 18.3
◦
C
48 °F
8.9 °C
Selects a humidity level that the cooling unit will maintain by removing or adding moisture to
the air. The humidity setpoint will either be set in percent RH or as a Dew Point value
depending on what the humidity control type is set for.
Humidity
Setpoint
20 - 80 %
0.5
S126
Humidity
Control Type
Relative
Compensated
Predictive
Dew Point
Predictive
Selects the humidity control calculation. Setting this parameter to Relative (%RH) will control
the humidity without considering any temperature deviations. Predictive and Absolute
control consider the temperature deviation from temperature setpoint so that a constant
level of moisture is kept in the area based on the humidity sensor reading and the
temperature deviation from setpoint. Compensated is recalculated with the actual deviation
from temperature setpoint. 1 degree Celsius is equal to 3 %RH, indirect proportional. If
temperature increases, the humidity setpoint is decreased and vice versa.
Humidity
Control Mode
Supply Return
Return
S127
Dew Point
Proportional
Band
2 - 18
◦
F
1.1 - 10.0 K
8
◦
F
4.4 K
Adjusts the activation points of the humidifier and compressors based on the actual sensor
values deviation from setpoint. The smaller this number, the faster the compressors and
humidifier will increase capacity. Too small of a number may cause the unit to short cycle or
overshoot setpoint.
Humidity
Proportional
Band
1 - 20%
0.2
S128
Humidity
Integration Time
0.0 - 25.0 min
0.0 min
Adjusts the capacity of the unit based on a time away from setpoint so that accurate
humidity control can be maintained. If the integration time is set to 0, the humidity control
operates as a "proportional only" control. When integration time is set, the control mode
changes to "PI" control
S129
Humidity
Deadband
0 - 18
◦
F
0.0 - 10.0 K
4
◦
F
2.2 K
Prevents overshooting of the setpoint and cycling between humidification and
dehumidification. The value entered in this field will be split in half by the temperature
setpoint.
S130
Dehum Supply
Temperature
Setpoint
41 - 104
◦
F
5.0 - 40.0
◦
C
54 °F
12.2 °C
Allows for a target temperature setpoint to be activated when a call for dehumidification is
enabled instead of the traditional method of over cooling the space by increasing cooling to
100% and lowering fan speed if equipped. Must be in supply air control mode. When a call for
dehumidification is active, the supply or remote sensor setpoint will be lowered to this
parameter. This parameter should be set below the accepted dew point threshold of your
space. Used only when supply dehumidification is enabled.
Actual Dehum
Temperature
Setpoint
41 - 104
◦
F
5.0 - 40.0
◦
C
50
◦
F
10.0
◦
C
S131
Dehum Setpoint
Adjustment
0 - 18 °F
0.0 - 10.0 K
9 °F
5.0 K
Sets the amount of that the Dehum Temp Setpoint is adjusted once the reheats activate. EX:
If the unit is equipped with a reheat device, this parameter will increase the dehumidification
temperature as the call for reheats are increased until the reheat call is at 100%. When the
reheats are at 100%, the full Dehum Setpoint Adjustment will be applied.
Dehum Setpoint
Filter
0.01 - 0.10
K/s
0.02 K/s
S132
Dehum
Reheat/LL
Sensor
Supply Sensor
Remote
Sensor Return
Sensor
Return
Sensor
Sets the sensor and temperature start point that the reheat will be deactivated and
dehumidification will be stopped due to over cooling the space in a call for dehumidification.
Dehum
Reheat/LL
Setpoint
41 - 104°F
5.0 - 40.0 °C
71 °F
21.7 °C
Table B.2 Service Menu Setpoints by Line ID (continued)
137
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...