Figure 7.1 Temperature Control—Fluid Economizer and Example 2-Step Compressor Capacity
No.
Description
No.
Description
1
Deadband.
5
½ of proportional band assigned to compressor(s) operation.
2
½ of proportional band assigned
to valve operation.
6
Scroll compressor step 1.
(Compressor 1 in dual-compressor configuration, Unloaded in single-compressor
configuration.)
3
Fluid control valve closed.
7
Scroll compressor step 2.
(Compressor 2 in dual-compressor configuration, Loaded in single-compressor
configuration.)
7
Fluid control valve fully-open.
Vertiv™ | Liebert® iCOM™ Installer/User Guide
76