1.
At the cooling unit, verify that it is the lead unit of the group:
•
Touch
, then
>
BMS & Teamwork Setup
>
U2U Setup
.
•
In the CONTROL BOARD column, verify that the
U2U Address
is 1.
If it is the lead unit, continue with step
.
If it is not the lead unit, find the lead unit and start at step
.
2.
Touch
, then
>
BMS & Teamwork Setup
>
Teamwork / Standby
. The TEAMWORK/STANDBY panel
opens.
3.
Touch
Unit Rotation
. The UNIT ROTATION CONTROL panel displays.
4. Touch
Rotate Now
, then touch
Save
. The operating and standby units are rotated.
Vertiv™ | Liebert® iCOM™ Installer/User Guide
70