Enable Free Cooling Flush
Number of hours between flushes of the free cooling coil.
Free Cooling Flush Duration
Length of time the for flush of the free cooling coil.
Free Cooling Flush Starts K11
When enabled, the Q15 relay is activated during the free cooling flush.
Ramp Up Fan at 100% FC
Enables/disables and increase in fan speed when free cooling reaches 100% capacity.
7.1.4 Temperature Control with a Fluid Economizer
When an economizer is installed, the cooling requirement (determined by the temperature proportional band) is addressed
first by the economizer’s secondary cooling, if the economizer cooling capacity is insufficient, the compressor(s) begin
cooling to bring the room air temperature down to the temperature setpoint.
The fluid economizer employs a motorized ball valve that controls the flow of chilled water/glycol to provide a cooling
capacity from 0% to 100%.
Simultaneous Operation, Partial Economizer Operation, Staging Cooling Sources
When simultaneous operation of the compressor(s) and secondary cooling is enabled, the portion of the proportional band
assigned to the fluid capacity valve may be reduced by the comparator circuit based on the differential temperature (DT)
settings. When this occurs, the compressor-control proportional band moves closer to the setpoint, and compressorized
cooling begins before secondary cooling reaches 100% (as shown in
Secondary Cooling Temperature Control with 2-Step
on the facing page) or shuts off.
CAUTION: On units with a GLYCOOL fluid economizer and standard-scroll or semi-hermetic compressors
without unloaders, there is a risk of over-cooling and low refrigerant pressure when free cooling/secondary
cooling operates simultaneously with compressor/DX cooling. Make sure adequate flow is provided when
100% free cooling and compressorized cooling occur at the same time. If the fluid temperature is too cold
while the compressors are running, the refrigerant pressure will drop. Contact technical support at 1-800-
543-2778 for more information on setting-up simultaneous operation.
NOTE: The compressor control method is not affected by economizer operation and operates across the assigned
proportional band based on the compressor configuration of your system (1-step, 2-step, 4-step, or digital-scroll). See
Compressor Control by Cooling Requirement
on page 23, for a description compressor-control methods.
Vertiv™ | Liebert® iCOM™ Installer/User Guide
74
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...