To install the sensors on the racks:
NOTE: Do not leave sensor probes coiled on top or coiled inside of a rack. Do not install a sensor in the hot aisle, or if a
sensor is installed in the hot aisle, make sure that it is set to "reference" to ensure that its readings are not used for
fan or cooling control.
1.
Install the inlet-rack temperature sensors on a rack in the area cooled by its connected unit as shown in Figure
12.10 below.
Figure 12.10 Rack Sensor Placement
Item
Description
1
To cable entry in cooling unit
2
First probe, 12 in. (305 mm) from top
3
Second probe, in approximate center of rack and in front of the equipment
4
2T sensor with label visible
5
Hot aisle
6
Cold aisle
Vertiv™ | Liebert® iCOM™ Installer/User Guide
116