Line
ID
Parameter
Name
Range
Default
Setting
Description
0 - 20.0 K
0.0 K
S113
Enable
Temperature
Compensation
No Return
Supply
Ret+Sup
No
Temperature compensation allows for a second or even a third sensor to be used that that will
influence the units cooling or heating. Return compensation can be used when the supply or
remote sensors are being used for control. Then the return sensor is then monitored to
maintain a minimum return temperature. Supply compensation can be used only when
Optimized Aisle (TW3) is enabled. The supply sensor will not only be used for controlling
cooling capacity but will also monitor the cold aisle temperature to ensure that the cold aisle
temperature setpoint is met.
S114
Return
Compensation
Setpoint
41 - 104
◦
F
5.0 - 40.0
◦
C
73
◦
F
23.0
◦
C
The temperature setpoint where compensation begins to operate by increasing the supply air
setpoint.
S115
Return
Compensation
Band
0 - 18
◦
F
0.0 - 10.0 K
0
◦
F
0.0 K
The return compensation band/value will determine how quickly the cooling capacity is
adjusted as the return temperature drops below the return compensation setpoint.
Return
Compensation
Value
0 - 18
◦
F
0.0 - 10.0 K
0
◦
F
0.0 K
S116
Supply
Compensation
Value
0 - 18
◦
F
0.0 - 10.0 K
0
◦
F
0.0 K
The Supply Compensation value determines how much the supply temperature setpoint will
be reduced when the units fan speed is at 100% and the cold aisle is not able to maintain
temperature setpoint. Any modifications to the supply temperature setpoint will be shown at
the temperature setpoint on parameter S103 as the actual active control point.
S118
Compressor
Capacity Filter
at 0 %
0.01 - 99.99
%/s
0.60 %/s
Controls the rate of change during compressor load changes to avoid overshoots. The filter
value depends on the current control deviation from setpoint. On the setpoints (@ 0% call for
cooling), it's typically set lower (slow).
Compressor
Capacity Filter
at 100%
0.01 - 99.99
%/s
4.00 %/s
At the end of the proportional band (@ 100% call for cooling) it's typically set higher (faster).
S119
Capacity
Transition Filter
0.01 - 99.99
%/s
4.00 %/s
This parameter should only be adjusted by a factory-service trained technician. The
transition capacity filter controls how quickly the capacity changes between different modes
of operation. This filter helps with the transition to avoid overshoot.
S120
CW Capacity
Filter @ 0%
0.01 - 99.99
%/s
0.10 %/s
The CW capacity filter controls the rate of change during a valve position adjustment to
avoid overshoots. The filter value depends on the current control deviation from setpoint. On
the setpoint (@ 0% call for cooling), its typically set lower (slower)
S121
CW Capacity
Filter @ 100%
0.01 - 99.99
%/s
0.60 %/s
At the end of the p-band (@ 100% call for cooling) its typically set higher (faster)
BMS Backup
Temp Setpoint
41 - 104
◦
F
5.0 - 40.0
◦
C
73
◦
F
23.0
◦
C
Selects a temperature setpoint that will be activated in the event of a BMS timeout. The BMS
timer must be configured for this parameter to be active.
S122
2nd
Temperature
Setpoint
41 - 104
◦
F
5.0 - 40.0
◦
C
73
◦
F
23.0
◦
C
Selects a temperature setpoint that will be activated in the event of a customer input signal
configured as the second setpoint. The customer input must be configured for the parameter
to activate.
S124
Humidity
Control Sensor
Remote
Sensor Return
Sensor
Return
Sensor
Defines which humidity sensor the humidity setpoint is compared with. The return sensor is
equipped with a Temp/Hum sensor and can calculate the dew point based on iCOM's internal
lookup table. If a sensor other than the return sensor is selected, the Liebert iCOM will
Table B.2 Service Menu Setpoints by Line ID (continued)
Vertiv™ | Liebert® iCOM™ Installer/User Guide
136
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...