NOTE: Both probes on the 2T sensor must be installed on the same rack.
2.
Install the 2T sensor probes the front door of the rack:
a. Using a cable tie, secure the sensor wire so that a probe is approximately 12 in. (305 mm) from the top
and in the center of the front door.
This sensor monitors hot air coming over the top of the rack from the hot aisle.
NOTE: Do not wrap cable ties around the actual sensor probe. If the rack has no door, secure the probes to the rack at
the side of the front opening.
b. Use a cable tie to secure the sensor wire of the second probe to the front door so that it is centered in
front of the heat generating equipment drawing air.
If the cabinet is completely filled with equipment, determine the center based on cabinet width and
height.
c. With probes in place, use cable ties to route the wires neatly up the rack door and into the rack leaving
enough slack in the wire so that the rack door opens and closes without binding or pinching the wire.
d. Using the supplied hook and loop fastener, connect the 2T sensor housing to the rack in an easily-
accessible location and with the sensor number visible.
3.
Repeat step
until all sensors are installed.
13.1.4 Connect the CANbus Cable and Ground
WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all local and remote
electric power supply disconnect switches and verify with a voltmeter that power is off before working within
any electric connection enclosures. Service and maintenance work must be performed only by properly
trained and qualified personnel and in accordance with applicable regulations and manufacturers’
specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected from the
electrical source.
Cabling considerations:
•
For cable up to 150 ft (45 m) long, no special considerations are needed.
•
Cable 150 ft (45 m) to 300 ft (91 m) require a CANbus isolator.
•
For cable longer than 300 ft (91 m), contact the factory.
•
The CANbus cable network requires a ground wire.
13 Hardware Installation
117
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...