Figure 12.13 Locating DIP Switches in 2T Sensor
Item
Description
1
Hole in sensor housing
2
Cover removed
NOTE: Up is on, down is off on the DIP switch.
Figure 12.14 DIP Switches in 2T Sensor
2.
Once DIP switches are set, refer to
Terminating the Last Sensor on the CANbus Link
on page 112, then continue
with step
.
3.
On iCOM:
•
In the Service menu, touch
Auxiliary Device Setup
>
Sensors
>
Fluid Sensors
>
Fluid 2T SensorCW T
.
The SENSOR PROPERTIES panel opens.
•
In
Fluid Sensor Type
, select the type of 2T sensor.
4. At the fluid inlet and outlet, use a field-supplied temperature sensor to verify the temperature readings,
compare the iCOM readings to the actual measured temperatures, and calibrate as needed.
•
If inlet and outlet temperature readings in iCOM are reversed based on the field measurements, use Fluid
Sensor 1/2 Placement to swap the readings.
5.
Touch
Save
. The fluid temperature sensor settings are saved.
Vertiv™ | Liebert® iCOM™ Installer/User Guide
120
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...