Line
ID
Parameter
Name
Range
Default
Setting
Description
Temperature
XDU.007
Calibration
Leaving Fluid
Temperature
+/-18°F
0°F
Calibrate Leaving Fluid Temperature sensor reading
XDU.009
Fluid Flow
Rateat Full
Scale (20mA)
10 - 1000 l/m
115 l/m
Fluid Flow Rate atFull Scale (20mA)
XDU.010
Fluid Flow Rate
Setpoint
5.0 - 1000.0
l/m
50.0 l/m
display readout showing current Fluid Flow Rate
XDU.011
Fluid Pump
Initial Speed
30 - 100%
50 %
Fluid Pump Initial Speed %
XDU.012
Fluid Flow
Proportional
Band
1.0 - 1000 l/m
20.0 l/m
Fluid Flow Proportional Band
XDU.013
Fluid Flow
Deadband
0.0 - 100.0
l/m
10.0 l/m
Fluid Flow Deadband
XDU.014
Fluid Flow
Integration Time
0 - 300 sec
60 sec
Fluid Flow Integration Time
XDU.018
Pump Transition
Duration
0 - 30 sec
15 sec
overlap timer for when pumps are rotating from one another
XDU.021
Pump Sequence
0 = Auto 1 =
Pump 1 2 =
Pump 2
(0) Auto
Specifies which is the lead pump. If configured for auto, pumps will rotate for equal runtime
purposes based off a set schedule
XDU.027
Pump Rotation
Frequency
0 - 30 days
7 days
Allows end user to define how often pumps should rotate
XDU.035
Flow Switch
Time Delay
1 - 9999 sec
20 sec
XDU.052
Minimum Fluid
Flow Volume
1.0 - 1000.0
l/m
5.0 l/m
Allows end user to specify minimum Fluid Flow
XDU.053
Perform Pump
Rotation
0 = No 1 =
Yes
(0) No
Allows end user to force a pump rotation
Table B.2 Service Menu Setpoints by Line ID (continued)
145
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...