Event
Description
GC Low Cond Temp
C1 or C2
Low refrigerant liquid line temperature
GC 1 or 2 Fan 1
through 4 FAIL
The following events may result from a fan failure alarm. Refer to the specific fan manufacturer’s literature for troubleshooting
information.
•
VSD high link current
•
VSD drive error
•
VSD earth to ground fault
•
VSD electronics heat sink thermal overload
•
VSD hall failure
•
VSD IGBT failure
•
VSD line fault
•
VSD motor locked
•
VSD motor thermal overload
•
VSD phase failure
•
VSD-specific uncategorized alarm detected
•
VSD electronics high-temperature condition
•
VSD high link voltage
•
VSD low link voltage
•
RS-485 communications failure
GC 1 or 2 TVSS Failure
TVSS alarm
Table 4.3 Events Specific to Liebert MC Condenser (continued)
Table 4.4 below, describes events available with a Liebert® EconoPhase™.
Event
Description
PB1 BOARD
FAIL
An unrecoverable failure of the pump control board has occurred. Pump shut down.
•
Pump board must be rebooted to reset event.
PB1 CAVITATE
SHUTDOWN
Pump has cavitated and shut down.
•
Event is reset when iCOM requests a new startup.
PB1 IN PRES
SENS FAIL
Inlet refrigerant pressure sensor failure. Pump shut down.
•
Event is reset when condition clears.
PB1 IN TEMP
SENS FAIL
Inlet refrigerant temperature sensor failure. Pump shut down.
•
Event is reset when condition clears.
PB1 INV DATA
SHUTDOWN
Invalid data detected and pump shut down.
•
Event is reset when iCOM requests a new startup.
PB1 LO DIFF
PRESSURE
Pump differential pressure fell below a lower threshold and pump shut down.
Event is reset when iCOM requests a new startup.
PB1 LO OUTLET
TEMP
Pump outlet-refrigerant temperature fell below a lower threshold and pump was shut down.
•
Event is reset when iCOM requests a new startup.
Table 4.4 Events Specific to Liebert EconoPhase
Vertiv™ | Liebert® iCOM™ Installer/User Guide
50
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...