Line
ID
Parameter
Name
Range
Default
Setting
Description
S279
Event Delay Time
(sec)
10 - 9999 sec
10 sec
Call Service
Event Enabled
Disabled Enabled
Enabled
Event: CALL
SERVICE
MESSAGE WARNING
ALARM
ALARM
S280
Event Delay Time
(sec)
10 - 9999 sec
10 sec
High Temperature
Event Enabled
Disabled Enabled
Enabled
Event: HIGH
TEMPERATURE
MESSAGE WARNING
ALARM
ALARM
S281
Event Delay Time
(sec)
10 - 9999 sec
10 sec
Loss of Air Blower 1
Event Enabled
Disabled Enabled
Disabled
Event: LOSS OF AIR
BLOWER 1
MESSAGE WARNING
ALARM
ALARM
S282
Event Delay Time
(sec)
10 - 9999 sec
10 sec
Reheat Lockout
Event Enabled
Disabled Enabled
Enabled
Event: REHEAT
LOCKOUT
MESSAGE WARNING
ALARM
WARNING
S283
Event Delay Time
(sec)
10 - 9999 sec
10 sec
Humidifier Lockout
Event Enabled
Disabled Enabled
Enabled
Event: HUMIDIFIER
LOCKOUT
MESSAGE WARNING
ALARM
WARNING
S284
Event Delay Time
(sec)
10 - 9999 sec
10 sec
FC Lockout
Event Enabled
Disabled Enabled
Enabled
Event: FC LOCKOUT
MESSAGE WARNING
ALARM
WARNING
Table B.4 Service Menu Alarm Settings by Line ID (continued)
157
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...