1

User manual
ALFANET 95

with door contact

VDH doc. 080643

Version: v1.1

Date: 12-04-2011

Softw.: 011506_ALFANET 95 RTDF-DK

File: Do080643.wpd

Range: -50,0/+50,0

C

* Description.

The 

ALFANET 95

 is a cooling/heating thermostat with various automatic defrost and fan drive facilities.

It can be programmed through the 

ALFANET PC-INTERFACE

 on the PC.

* Installation.

On the connection diagram of  the  

ALFANET 95

 is shown how the sensor, power supply and relays

should be connected. After the 

ALFANET 95

 has been connected to the power supply a self-test

function will take place, after which the measured temperature will appear in the display. 

* Operation.

The 

ALFANET  95

 thermostat can be operated by means of four pushbuttons on the front. These

pushbuttons are:

SET

- view / change the set point.

UP

- raise the set point.

DOWN

- lower the set point.

C

- hidden key under the 

C text.

* Normal operation status.

During normal operation the temperature of the control sensor is shown in the  display.

* Viewing the set point.

By pressing the 

SET

 key the set point becomes visible. At the same time the decimal point of the right-

hand display will blink, as an indication that the set point is being read. A few seconds after the  

SET

key has been released, the set point will disappear and the measured value will be visible again.

Содержание Alfanet 95

Страница 1: ...n will take place after which the measured temperature will appear in the display Operation The ALFANET 95 thermostat can be operated by means of four pushbuttons on the front These pushbuttons are SE...

Страница 2: ...isplay the upper and lower segment will blink With the UP and DOWN keys the required parameter can be selected see the parameter table When the required parameter has been selected the value of the pa...

Страница 3: ...the following two conditions can be set i e a The fan is blocked until the defrost sensor measures a temperature that is lower than the set switching on temperature of the fan P25 b The fan is blocked...

Страница 4: ...50 50 C 0 No 1 Yes 15 2 0 0 35 36 37 Day night contact as door contact Cooling and fan off if door is open Max time cooling and fan off when door is open 0 No 1 Yes 0 No 1 Yes 0 99 Minutes 0 0 30 40...

Страница 5: ...ir shielded Dimensions 35 x 77 x 71 5mm hwd Panel cutout 29 x 70mm hw I O UNIT Supply 230 Vac 50 60Hz 5 10 Max 3VA Relays These two relays have one common Ry 1 Alarm SPDT NO NC 250V 8A cos 1 Ry 2 Cool...

Страница 6: ...6 Dimensions of ALFANET 95 Control unit I O unit...

Страница 7: ...7 Connection data Diagram 042527w2...

Страница 8: ...8 Function diagram Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl Netherlands Internet www vdhproducts nl...