2
* Changing the set point.
Press the
SET
key. The set point appears on the display. Release the
SET
key. Press the
SET
key
again. Now the set point can be adjusted with the
UP
or
DOWN
keys, the set point can be adjusted.
A few seconds after the keys have been released, the measured value will again appear in the display.
* Status of the Relays.
Press the
C
key. The three lower segments light up and the
upper vertical segments show the status of the five relays
(see diagram). Relay is active when the segment lights up.
* Start/stop defrost cycle.
The defrost cycle will stop and start automatically by internal parameters. Defrosting can also be done
manually;
Stop:
If defrosting is taking place, defrosting can be stopped manually by pressing the
DOWN
and
UP
keys simultaneously.
Start:
If defrosting is not taking place, then defrosting can be started manually by pressing
the
DOWN
and
UP
keys simultaneously.
* Setting internal parameters.
In addition to adjusting the set point a number of internal adjustments can be made, including the
differentials, sensor-offsets, set point range, compressor settings, fan settings and the defrosting
settings.
By pressing the
DOWN
key for more than 10 seconds the 'internal programming menu' will be
entered. On the left-hand display the upper and lower segment will blink.
With the
UP
and
DOWN
keys the required parameter can be selected (see the parameter table).
When the required parameter has been selected, the value of the parameter can be read out by
pressing the
SET
key. The parameter value can be changed by pressing the
UP
and
DOWN
keys. If
no key has been pressed for 20 seconds, the
ALFANET 95
will return to it’s normal operation mode.
* Adjusting the sensor.
The
control sensor
can be adjusted by means of the Offset control sensor (parameter 05).
The
defrost sensors
can be adjusted by means of the Offsets defrost sensors (parameters 08 and
11). For reading the temperatures of the defrost sensor choose parameters 07 and 10.
Should a sensor of the
ALFANET 95
indicates 2
C too much, for example. Then the according Sensor
Offset must be lowered by 2
C.
* Error messages.
The following error messages may appear in the display of the
ALFANET 95
:
LO
- Minimum alarm.
Solution E1/E2/E3:
HI
- Maximum alarm.
- Check if sensor is properly connected.
E1
- Control sensor defect.
- Check sensor (1000
/25
C).
E2
- Defrost sensor-1 defect.
- Replace sensor.
E3
- Defrost sensor-2 defect.
Solution EEE:
EEE
- Settings have been lost.
- Program the settings again.
-L-
- In case of a short-circuited sensor the error codes
E..
and
-L-
will alternate in the display, indicating a short-circuited sensor.
-H-
- In case of a disconnected sensor the error codes
E..
and
-H-
will alternate in the display, indicating a disconnected sensor.