background image

Installation Instructions

Document No. 129-179

October 4, 2017

Retrostat Kits for POWERS™ CONTROLS
TH 180, TH 182 D/N or H/C Thermostats

Item Number 129-179+3, Rev. EA

Page 1 of 4

Product Description

The Retrostat kits replace a discontinued Powers Controls
TH 180 or TH182 day/night or a heating/cooling pneumatic
thermostat with a TH 192 direct or reverse acting, two
pipe, dual temperature pneumatic device.

Contents

Part

Quantity

Retrostat Cover Kit

1

Thermostat *

1

Adapter frame

1

Bag assembly with installation hardware

1

Optional

 1/2-inch Large, Exposed Set

Point Knob

1

*  Includes thermostat installation instructions.

Expected Installation Time

1 hour

Required Tools

 

Calibration and cover screw wrench (192-632) or
1/16” Allen wrench and 1/8” open-end wrench

  Medium flat-blade screwdriver

  Small 

level

  Accurate 

thermometer

  Needle nose pliers

Product Numbers

Thermostat

Replaces

Retrostat Kit

(See Notes

1 and 2)

Type

Action

Scale

Day/
Night

Direct

°

F

180-410
180-413
180-910
180-913
182-500
182-501

192-3044

°

C

182-627
182-630
182-632

192-3144

Reverse

°

F

180-937
182-503

192-3054

Heat/
Cool

Direct/
Reverse

°

F

180-420
180-423
180-920
180-923
182-506
182-507

192-3084

°

C

182-633
182-634

192-3184

NOTE:

For Retrostat Kits with optional 1/2-inch large, exposed
setpoint adjustment knob, order standard kit with “K”
suffix.

Prerequisites

 

Review all of these instructions before you begin
installation.

 

Check job drawings for any site-specific
information.

 

Verify the existing thermostat installation has its
supply and return air lines connected properly.

 

Obtain the installation instructions provided with
the thermostat in this Retrostat Kit. The document
provides instructions for calibrating the thermostat.

 

Ensure that a supply of wall anchors and plastic
ties are available.

Содержание TH 180

Страница 1: ...ewdriver Small level Accurate thermometer Needle nose pliers Product Numbers Thermostat Replaces Retrostat Kit See Notes 1 and 2 Type Action Scale Day Night Direct F 180 410 180 413 180 910 180 913 182 500 182 501 192 3044 C 182 627 182 630 182 632 192 3144 Reverse F 180 937 182 503 192 3054 Heat Cool Direct Reverse F 180 420 180 423 180 920 180 923 182 506 182 507 192 3084 C 182 633 182 634 192 3...

Страница 2: ...ports to lubricate them Carefully insert the thermostat ports into the terminal adapter O rings on the wall plate 7 Configure the cover per installation instructions provided and mount the cover over the thermostat NOTE For applications that use the 1 2 inch large set point adjustment knob align the key hole in the cover over the shaft protruding from the thermostat when mounting the cover see Fig...

Страница 3: ...on Instructions October 4 2017 Siemens Industry Inc Page 3 of 4 Figure 1 Typical Thermostat Installation Figure 2 Terminal Head Removed with 1 8 inch O D Copper Tubing Figure 3 Terminal Head Removed with 3 16 inch O D Copper Tubing ...

Страница 4: ...Buffalo Grove IL 60089 4513 USA Tel 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No 129 179 Printed in the USA Page 4 of 4 NOTE In some terminal heads there is a ball check valve Remove the ball check valve before beginning the installation You will know there is a check valve present i...

Отзывы: