Chapter 2 - Installation
_______________________________________________________________________________________________________________
MNL000530
Revision 1
03/15/2018
BSGS eV / BULKGUARD eV
© Versum Materials, Inc. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page
2
-
19
Power Requirements: Single Power Feed – JT heater with heat trace
208-240 VAC, 32A, 50/60Hz, 3 wire
Power Requirements: Single Power Feed – Heat trace with no JT heater
208-240 VAC, 7A, 50/60Hz, 3 wire
Power Requirements: Controller Powered Separate – JT heater with heat trace
Heaters: 208-240 VAC, 32A, 50/60Hz, 3 wire
Controller: 100-240 VAC @ 150 VA maximum, 50/60Hz, 3 wire
Power Requirements: Controller Powered Separate – Heat trace with no JT heater
Heaters: 208-240 VAC, 7A, 50/60Hz, 3 wire
Controller: 100-240 VAC @ 150 VA maximum, 50/60Hz, 3 wire
Acceptable wire gauge:
Single power feed: 14-4 AWG
OR
Heater Power: 14-4 AWG
Controller Power: 14-10 AWG
Use at least 75C rated wiring for the mains supply.
Replaceable fuses:
F1, F2, F3, and F4, located on the power board in the top of the AP11 controller, are 4A super
quick acting fuses.
FS-405, located in the eV ECC adjacent the DC power supply, is a 2A medium time delay fuse.
FS-406, FS-407, and FS-408 are 500 mA medium time delay fuses.
See the Spare Parts List in Appendix B for Manufacturer and part numbers and specifications.
Figure 2-6: Power Connections