85
RTAA-IOM-3
Figure 45
Fan Configurations – RTAA 130-200 Tons
15 F Minimum Ambient
All fans will be Full Airflow (Full Pitch Blade) Fans:
Circuit #1 is on the right side of the unit from the control panel.
Circuit #2 is on the left side of the unit from the control panel.
# Of Fans
# Of Fans
UCM Outputs
Tons
Circuit #1
Circuit #2
Per Circuit
# Fan Steps/Circuit
130
5
5
4
5 & 5 respectively
140
5
5
4
5 & 5 respectively
155
6
5
4
6 & 5 respectively
170
7
5
4
7 & 5 respectively
185
7
6
4
7 & 6 respectively
200
7
7
4
7 & 7 respectively
For STANDARD air-cooled (RTAA) Chillers, the mapping of UCM outputs to fan staging shall be as follows:
Fan Contactor
5 Fan Circuit
6 Fan Circuit
7 Fan Circuit
Circuit #1
K9
K10
K11
K12
K9
K10
K11
K12
K9
K10
K11
K12
Circuit #2
K13
K14
K15
K16
K13
K14
K15
K16
K13
K14
K15
K16
Number of Fan(s)/
Contactor
1
1
1
2
1
1
2
2
1
1
2
3
Fan Steps
0
–
–
–
–
–
–
–
–
–
–
–
–
1
x
–
–
–
x
–
–
–
x
–
–
–
2
x
x
–
–
x
x
–
–
x
x
–
–
3
x
x
x
–
x
–
x
–
x
–
x
–
4
x
x
–
x
x
x
x
–
x
x
–
x
5
x
x
x
x
x
–
x
x
x
x
–
x
6
–
–
–
–
x
x
x
x
x
–
x
x
7
–
–
–
–
–
–
–
–
x
x
x
x
X = ON
Содержание RTAA-130
Страница 2: ... American Standard Inc 1991 ...
Страница 8: ...8 RTAA IOM 3 ...
Страница 13: ...13 RTAA IOM 3 Figure 3 Typical RTAA Packaged Unit 240 400 Tons Control Panel Evaporator Outlet Inlet ...
Страница 24: ...24 RTAA IOM 3 ...
Страница 26: ...26 RTAA IOM 3 Figure 9 Dimensions and Clearances for RTAA Packaged Unit 130 to 200 Ton RTAA SU 1000E ...
Страница 27: ...27 RTAA IOM 3 Figure 10 Dimensions and Clearances for RTAA Packaged Unit 240 300 Ton RTAA SU 1001C ...
Страница 28: ...28 RTAA IOM 3 Figure 11 Dimensions and Clearances for RTAA Packaged Unit 340 to 400 Ton RTAA SU 1002C ...
Страница 38: ...38 RTAA IOM 3 RTAA SA 2002C Figure 19 Spring Isolator Placement for Typical RTAA Packaged Unit 240 400 Tons ...
Страница 46: ...46 RTAA IOM 3 Figure 24 Typical Domestic Water Heater Piping Figure 25 Typical Domestic Water Heater Piping ...
Страница 50: ...50 RTAA IOM 3 Figure 30 Refrigerant Circuit Identification ...
Страница 52: ...52 RTAA IOM 3 Figure 31 Remote Evaporator Piping Example ...
Страница 58: ...58 RTAA IOM 3 Continued on Next Page Figure 34 Typical Field Wiring for RTAA Packaged Unit 130 to 200 Tons ...
Страница 59: ...59 RTAA IOM 3 Continued from Previous Page See Notes on Next Page ...
Страница 61: ...61 RTAA IOM 3 Figure 35 Typical Field Wiring for RTAA Packaged Unit 240 400 Tons Continued on Next Page ...
Страница 63: ...63 RTAA IOM 3 Continued from Previous Page See Notes on Page 61 ...
Страница 64: ...64 RTAA IOM 3 Figure 36 Typical Field Wiring for RTAA With Remote Evaporator Option Continued on Next Page ...
Страница 65: ...65 RTAA IOM 3 Continued from Previous Page See Notes on Page 61 ...
Страница 76: ...76 RTAA IOM 3 ...
Страница 78: ...78 RTAA IOM 3 Figure 40 Refrigeration System and Control Components Single Circuit Continued on Next Page ...
Страница 80: ...80 RTAA IOM 3 Figure 41 Refrigeration System and Control Components Duplex Circuit Continued on Next Page ...
Страница 92: ...92 RTAA IOM 3 Figure 51 Operator Interface Controls ...
Страница 120: ...120 RTAA IOM 3 ...
Страница 126: ...126 RTAA IOM 3 Figure 56 Unit Sequence of Operation RTAA 240 to 400 Tons Continued on Next Page ...
Страница 127: ...127 RTAA IOM 3 Continued from Previous Page 2307 1566C ...
Страница 128: ...128 RTAA IOM 3 Figure 57 Unit Sequence of Operation RTAA 130 to 200 Tons 2306 9122A ...
Страница 132: ...132 RTAA IOM 3 Figure 58 Operator s Log ...
Страница 138: ...138 RTAA IOM 3 ...