Networking
53722
5-7
5. Based on the type of network repeater board chosen, run the twisted pair wiring /fiber
optic cable to the next network repeater using a BUS or style 7 (class A) wiring method. A
combination of both repeater types can be used. See Figure 5-6, Figure 5-7, Figure 5-8,
and Figure 5-9 for repeater wiring examples.
5.4.2.1 Network Repeater Cable Requirements
Cable requirements for wire runs between repeaters.
1. All fiber cable must be multimode 62.5/125 micron cable with ST type connectors. It is
important that the cable be verified to contain no more than 8dB of loss including the con-
nectors.
2. Twisted pair wiring must be UNSHIELDED twisted pair conductor cable. The wire gauge
must be 18 AWG or larger. The maximum wire length is 3000 ft. between repeaters.
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......