The SCSS-700 Fire Alarm Control/Communicator is an analog addressable fire control
system that meets the requirements of UL 864. The SCSS-700ND is used in a networked
system where there is at least one SCSS-700 in the system. The SCSS-700ND is the same as
the SCSS-700 without the display. When using the SCSS-700ND as a stand alone local unit,
one SCSS-700ANN must be connected, and the SCSS-700ANN must be wired in conduit
within 20’ of the SCSS-700ND.
1.1
Overview of Basic System
The SCSS-700 base system is packaged as an assembled stack of 3 circuit boards mounted to
an aluminum housing.
1.1.1
Hardware Features
•
The basic SCSS-700 panel contains one built in signaling line circuit (SLC), which
supports up to 159 LiteSpeed sensors and 159 LiteSpeed modules. Additional SLC loops
can be added using the model 5815XL SLC expander to increase overall point capacity to
a maximum of 636 points.
•
Each SLC supports 159 LiteSpeed sensors and 159 LiteSpeed modules to a maximum of
636 points per SCSS-700 control panel.
•
9.0A of output power is available through 8 sets of terminals for notification and auxiliary
applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total
output power must not exceed 9.0A). The constant auxiliary power load must not exceed
6.0A for normal standby.
•
Built-in dual phone line, digital alarm communicator/transmitter (DACT).
•
Reports events to central station by point or by zone.
•
UL Listed for pre-action and deluge releasing systems.
•
Dedicated Form C trouble relay and two general purpose Form C programmable relays.
•
Can be used with Model SCSS-700ANN remote annunciators (sold separately).
•
Supports the 5865-3, 5865-4, and 5880 LED annunciators. See sections 4.9 and 4.10 for
additional information on these models.
•
Printing of event log available through the Model 5824 serial/parallel printer interface
module (sold separately).
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......