System Operation
53722
10-9
10.4.7 Conduct a Dialer Test
1. From the Main Menu, press for System Tests.
2. Select for Dialer Test. The screen will display “Manual dialer test started”. When the
test is completed, you will be returned to the <Test Menu>. A manual dialer test requires
that at least one daily test be enabled in dialer programming in the network.
10.4.8 Silence Alarms or Troubles
Press
to turn off silenceable outputs and annunciator PZTs. If an external silence switch
has been installed, activating the switch will silence alarms or troubles. If you are already
using system menus when you press
, you will not need to enter your code or rotate the
key.
Note: Alarm and trouble signals that have been silenced but the detector remains un-restored will un-silence ev-
ery 24 hours until it is restored.
Note: Multi-Site displays do not allow for silencing multiple sites. Pressing
will only locally silence the
PZT built into the annunciator. To silence a site, enter a multi-site access password, select a site, and then
press .
10.4.9 Reset Alarms
Press
to perform a control panel reset. If an external reset switch has been installed,
activating the switch will reset alarms.
Note: Multi-Site displays do not allow for resetting multiple sites. To reset a site, enter a multi-site access pass-
word, select a site, and then press
.
10.4.10 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in
compliance with NFPA 72. Detectors are sampled every three hours.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL
TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an
out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the central station receives a detector trouble report
(“373” + Zone # for Contact ID format; “FT” + Zone # in SIA format).
To check sensitivity for an individual detector, follow the steps below.
1. From the Main Menu, press
for Point Functions.
2
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......