Model SCSS-700 Installation Manual
4-26
53722
4.9.4
Dry Contact Wiring
The 8 input circuits on the 5880 board are for monitoring switch inputs. Any type of switch
supported by the control panel can be used with the 5880. For example, you can use a 5880 to
monitor pull stations, water flow, tamper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-25. Notice grouping of terminals; power terminals are
shared by two inputs.
Figure 4-25 Dry Contact Wiring
Model 7628
EOL Resistor