Model SCSS-700 Installation Manual
8-2
53722
manually change the switch type if manual pull is not correct.
The first JumpStart AutoProgramming creates one zone (Zone 1) and assigns all input points
to Zone 1. Zone 1 is mapped to Output Group 1.
8.1.2
Output Points
The first JumpStart AutoProgramming on a panel in default configuration creates three output
groups and assigns output circuits as follows:
Internal Power Supply Circuits 1-8:
Configured as Notification and assigned to Group 1.
Internal Power Supply Circuit 9 (Relay 1):
Assigned to Group 998.
Internal Power Supply Circuit 10 (Relay 2):
Assigned to Group 999.
Addressable output points (Relay modules):
All addressable relay devices will be configured as “Output Pt” (general purpose output point)
and assigned to Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
8.1.3
Running JumpStart AutoProgramming
Run JumpStart AutoProgramming immediately after you have addressed and connected all
input devices (detectors, pull stations, and so on) and output devices (notification appliances,
relays, and so on).
Note: If you need to install a few devices after you have run JumpStart AutoProgramming, you can install them
manually or run JumpStart again at a later time. JumpStart will keep user options, such as names, for de-
vices already installed. Follow instructions in Section 8 for configuration.
To run JumpStart AutoProgramming, follow these steps.
1. Press
to view Main Menu.
2. Select for Panel Programming. Enter Access code.
3. Select for JumpStart AutoProgramming.
4. The message “System will be shutdown during JumpStart Continue?” displays on the
LCD. Select Yes to continue. A series of messages displays for the next several seconds.
JumpStart scans the SLC loops for devices. This can take several minutes, depending on
the number of devices attached.
5. When the message “Configuring System Done” displays, press any key to continue.
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......