Model SCSS-700 Installation Manual
3-10
53722
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC, or
240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the
9.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. Maximum SBUS address capacity is 63 SBUS modules. The practical limit is determined by the amount of SBUS
5865-3 LED Annunciator
(63 max)
5
Standby: 35 mA
mA
Alarm: 145 mA
mA
5880 I/O Module
(63 max)
5
Standby: 35 mA
mA
Alarm: 200 mA
mA
5883 Relay Interface
Standby: 0 mA
mA
Alarm: (22 mA/relay) 220 mA
mA
VIP-VCM Voice Control Module
(1 max.)
Standby: 50 mA
mA
Alarm: 125 mA
mA
VIP-SW16 Switch Expander
(3 max.)
Standby: 10 mA
mA
Alarm: 75 mA
mA
VIP-50 or VIP-125 Audio
Amplifier with/without VIP-CE4
(8 max.)
Standby: 10 mA
mA
Alarm: 10 mA
mA
SCSS-700RM Remote Microphone
(2 max.)
Standby: 50 mA
mA
Alarm: 125 mA
mA
IFP-RPT-FO Network Repeater
IFP-RPT-UTP Network Repeater
(1 max)
Standby: 24 mA
mA
Alarm: 24 mA
mA
A
Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
B
Auxiliary Devices Current
Notification Appliance Circuits
Refer to device manual for current rating.
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C
Notification Appliances Current
mA
D
Total current ratings of all devices in system (line A + line B + C)
mA
mA
E
Total current ratings converted to amperes (line D x .001):
A
A
F
Number of standby hours
H
G
Multiply lines E and F.
Total standby AH
AH
H
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
H
I
Multiply lines E and H.
Total alarm AH
AH
J
Add lines G and I.
4
Total ampere hours
required
AH
Table 3-1: Current Draw Worksheet for LiteSpeed SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......