Before You Begin Installing
53722
3-13
3.7
Installation Tasks Overview
This section provides a chart listing tasks that need to be performed when installing the SCSS-
700 system. The chart is intended to be a handy way for you to make sure you have completed
all necessary tasks. Unless noted, these tasks do not have to be performed in the order they are
listed here.
Important: Connect and address SLC devices before running JumpStart AutoProgramming.
Task
See Section
(for more info.)
Main Panel Hardware Installation
U
Mount the control panel cabinet.
U
Connect AC.
U
Connect phone lines.
U
Install 5815XL SLC expander modules (if needed).
U
Install SCSS-700ANN Remote Fire Alarm Annunciator modules if used.
U
Install 5865 or LED Annunciator modules if used.
U
Install 5880 LED I/O module if customized LED annunciation will be used.
U
Install notification appliances.
U
Install auxiliary power devices (if used).
U
If using a printer, install the 5824 Serial/Parallel Printer Interface Module.
U
Connect batteries (typically last step).
SLC Device Hardware Installation
Perform these steps before running JumpStart AutoProgramming.
U
Connect device bases to the loop.
U
Set device addresses.
U
Physically connect detectors to their bases. Connect relay and contact monitor
modules.
7.3 & see device
install instructions
JumpStart AutoProgramming
JumpStart AutoProgramming searches for expanders and SLC devices connected to the
panel but not programmed into the system. JumpStart AutoProgramming automatically
selects some options for SLC devices. See “Input Point Configuration” section of this chart
for other options.
JumpStart AutoProgramming makes selections for the following options. You can
customize options, if necessary.
Device type (detector or switch) configured by JumpStart AutoProgramming.
To change, see 9.6
Program type of detector (heat, photoelectric, or ionization) selected by JumpStart
AutoProgramming.
To change, see 9.5
System Software Configuration
U
Select low AC hours report time (3 hours by default).
U
Enable/disable automatic DST adjustment feature (enabled by default).
U
Change clock display format (12-hour with AM/PM by default).
U
Enable/disable day/night sensitivity (disabled by default).
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...