Model SCSS-700 Installation Manual
4-32
53722
4.13.1.1 Regulated Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the
back of this manual.
To install a circuit:
1. Wire Class B Notification appliances as shown in Figure 4-31.
2. Configure the circuit through programming (see Section 9.5)
Figure 4-31 Class B Notification Appliance Circuit Wiring
Maximum voltage drop per Class B notification circuit is 3V. See Table 4-3
Table 4-3: Maximum Impedance Class B
Current
Maximum Impedance
1.0A
3
Ω
1.5A
2
Ω
2.0A
1.5
Ω
2.5A
1.2
Ω
3.0A
1.0
Ω
Supervised
Power Limited
Notification Wiring
Regulated 24 VDC
3A per Circuit, 9A max Combined
UL Listed EOL
Model 7628
4.7 k
Ω
Alarm Polarity Shown.
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......