Model SCSS-700 Installation Manual

9-14

53722

Define Output Group Type

Each output group is defined as either a voice output group or a non-voice output group. 
Output points that are audio circuits (all circuits on a VIP-Amplifier and VIP-CE4) can only 
be assigned to voice output groups. Output points that are non-voice circuits (all other points 
and circuits that are on all modules except a VIP-Amplifier and VIP-CE4) are assigned to 
non-voice output groups.

Each of the output groups defined as voice can be mapped to a particular Switch and LED on 
the VIP-VCM and VIP-SW16. Figure 9-6 illustrates how the numbers selected correspond to 
the VIP-VCM and -SW16.

Figure 9-6  Corresponding Switch and LED for Mapping Output Groups

7. To get to this menu item repeat steps 1 through 5 of Section 9.4.1.

8. To edit group properties, press 

.

9. Press the 

 or 

 arrows to select the desired VIP switch number, or enter the number.

10. Press .

11. Press the 

 or 

 arrows to select Y (yes) to make this a voice output group or N (no) to 

make this a non-voice output group.

9.4.2

Add Group

To add a group:

1. Enter the installer code. The panel will automatically go to the main menu.

2. Select 

 for Panel Programming.

Display reads:

Initializing

Please wait . . .

VIP-VCM

VIP-SW16

Corresponding

Switch and LED Numbers 

Corresponding

Switch and LED Numbers 

2

7

Содержание SCSS-700

Страница 1: ...Copyright 2010 All Rights Reserved Published in U S A SCSS 700 Analog Addressable Fire System Installation Operation Manual D P N 53722 D ECN 10 235 Document 53722 03 18 10 Rev...

Страница 2: ......

Страница 3: ...ranges and humidity Therefore it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 27 C 60 80 F Verify that wire sizes are adequat...

Страница 4: ...oom as the control panel and in rooms used by the system for the connection of alarm transmission wiring communications signaling and or power If detectors are not so located a developing fire may dam...

Страница 5: ...3 2 2 4 Requirements for Remote Station Protected Fire Alarm Systems Digital Alarm Communicator Transmitter DACT 2 3 Section 3 Before You Begin Installing 3 1 3 1 What s in the Box 3 1 3 2 Environmen...

Страница 6: ...65 Mounting 4 29 4 11 Vip Module Installation 4 30 4 12 Telephone Connection 4 30 4 13 Flexputs I O Circuits 4 30 4 13 1 Conventional Notification Appliance 4 31 4 13 1 1 Regulated Class B Notificatio...

Страница 7: ...ater Wiring 5 9 5 4 2 4 Fiber Optic and Twisted Pair Repeater Wiring between Multiple Panels 5 10 5 5 Using Both Repeaters and Direct Connect Wiring on a Networked System 5 11 5 5 1 Setting the Networ...

Страница 8: ...2 3 Event Mapping 8 7 8 2 4 Mapping LED Points 8 13 8 2 5 Mapping LED Points for a Networked System 8 14 8 3 Programming Using the SCSS 700PK PC Configuration Software 8 15 8 4 Programming Using an A...

Страница 9: ...tary Format 9 28 9 6 2 5 Line Monitor 9 28 9 6 2 6 Answering Machine Bypass 9 29 9 6 2 7 Phone Line Unused 9 29 9 6 3 Daytime Nighttime Sensitivity 9 29 9 6 4 Holiday Days 9 31 9 6 5 Miscellaneous Opt...

Страница 10: ...Silence Alarms or Troubles 10 9 10 4 9 Reset Alarms 10 9 10 4 10 Check Detector Sensitivity Through Point Status 10 9 10 4 11 View Status of a Point 10 10 10 4 12 View Alarms or Troubles 10 11 10 4 13...

Страница 11: ...nd Testing Tools 12 4 12 3 1 SLC Device Locator 12 4 12 3 2 SLC Multi Device Locator 12 5 12 3 3 I O Point Control 12 6 12 3 4 Earth Fault Resistance 12 7 Section 13 Installation Records 13 1 13 1 Det...

Страница 12: ...SCSS 700 Installation Manual 8...

Страница 13: ...815XL SLC expander to increase overall point capacity to a maximum of 636 points Each SLC supports 159 LiteSpeed sensors and 159 LiteSpeed modules to a maximum of 636 points per SCSS 700 control panel...

Страница 14: ...within conduit when the panels are located no more than 20 feet apart and within the same room Panels separated by more than 20 feet or located in multiple buildings use IFP RPT network repeater hardw...

Страница 15: ...SCSS 700ND panels itself and the built in power supply It also refers to any optional 5815XL SLC expansion modules Input Point An addressable sensing device such as a smoke or heat detector or a cont...

Страница 16: ...D annunciator can display up to 30 LEDs 15 red and 15 yellow 5865 4 has key switches for silence and reset and a system trouble LED 5880 LED I O Module Driver for up to 40 LEDs Interfaces with customi...

Страница 17: ...ing modems have been tested by Stanley for compatibility with the Software Suite software packages Table 1 3 Compatible Modems Manufacturer Model US Robotics 28 8 Motorola LifeStyle 28 8 3400 series P...

Страница 18: ...e level of a structure cannot be expected to sense fires developing on another level The amount of smoke present may be insufficient to alarm smoke detectors Smoke detectors are designed to alarm at v...

Страница 19: ...ility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals iii In rare instances the sounding of a warnin...

Страница 20: ...mmended that smoke detectors be located in any room where an alarm control is located or in any room where alarm control connections to an AC source or phone lines are made If detectors are not so loc...

Страница 21: ...tification appliances shall be protected until they enter the evacuation signaling zone that they serve Any of the following methods shall be considered acceptable as meeting these requirements 1 A 2...

Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...

Страница 23: ...r of devices is limited The REN number is imbedded in the FCC registration number as 10BIf the SCSS 700 causes harm to the telephone network the telephone company will notify you in advance that the t...

Страница 24: ...g subsections list specific requirements for each type of installation for example Central Station Fire Alarm systems Local Protected Fire Alarm systems and so on See Section 10 7 for information on r...

Страница 25: ...be used When two count is used detector spacing shall be cut in half you shall not use the alarm verification feature and no delay shall be used P A S feature shall be used only with automatic detect...

Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...

Страница 27: ...tions It is important to protect the SCSS 700 control panel from water To prevent water damage the following conditions should be AVOIDED when installing the units Intended for indoor use in dry locat...

Страница 28: ...ower Circuits 0 O 100 mA for initiation circuits X I O 4 Flexput Circuits 24 VDC 3 0 Amp Notification and Aux power Circuits 0 O 100 mA for initiation circuits X I O 5 Flexput Circuits 24 VDC 3 0 Amp...

Страница 29: ...Relay 1 24 VDC 2 5 A resistive N A C N O N C TROUBLE Trouble Relay 24 VDC 2 5 A resistive N A C N O S SLC OUT SLC terminals 32 VDC 150 mA 0 S SC SLC IN Used for Class A installations 0 SC Ring Phone L...

Страница 30: ...th ground at the panel You must route high and low voltages separately Route the wiring around the inside perimeter of the cabinet It should not cross the circuit board where it could induce noise int...

Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...

Страница 32: ...If you should need to remove the board assembly for repair remove the four mounting nuts which hold the assembly in the cabinet Then lift the entire assembly out of the cabinet Do not attempt to remo...

Страница 33: ...s and record in the table at Line B 3 Add up all notification appliance loads and record in the table at Line C 4 For notification appliances and auxiliary devices not mentioned in the manual refer to...

Страница 34: ...t per Device Standby Current Alarm Current For each device use this formula This column X This column Current per number of devices Fire Panel Battery current draw 1 Standby 290 mA 290 mA Alarm 530 mA...

Страница 35: ...rm 2 mA mA mA B200SR Sounder Base 159 max loop 636 max panel Aux Pwr Standby 1 mA mA Alarm 15 mA mA SLC Alarm 0 7 mA mA B224RB Relay Base Standby Alarm 0 5 mA mA mA RT151 151 KEY Alarm 7 5 mA mA RA100...

Страница 36: ...h Expander 3 max Standby 10 mA mA Alarm 75 mA mA VIP 50 or VIP 125 Audio Amplifier with without VIP CE4 8 max Standby 10 mA mA Alarm 10 mA mA SCSS 700RM Remote Microphone 2 max Standby 50 mA mA Alarm...

Страница 37: ...ach SBUS module See section 4 5 2 6 The BEAM355S draws a maximum of 500mA from auxiliary power when the test feature is used This should be considered when determining auxiliary power capacity but not...

Страница 38: ...473mA 442mA 18AH 569mA 506mA 475mA 24AH 769 mA 706mA 675mA 33AH 1 07A 1 01A 975mA 35AH 1 14A 1 07A 1 04A 40AH 1 30A 1 24A 1 21A 55AH 1 80A 1 74A 1 71A Table 3 3 Maximum Battery Standby Loads for 90 Ho...

Страница 39: ...batteries typically last step 4 3 SLC Device Hardware Installation Perform these steps before running JumpStart AutoProgramming U Connect device bases to the loop 7 5 U Set device addresses 7 5 U Phys...

Страница 40: ...lay options detection characteristics for zone 9 3 1 2 U Select heat detector trip temperature and or smoke sensitivity level for photoelectric smoke detectors 9 3 1 2 Output Point Configuration Conve...

Страница 41: ...3 15 U Assign output points to the group 9 5 U Program a name or description for the group if desired 9 4 1 1 Select group properties see below U Select options for activation with system switches 9 4...

Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...

Страница 43: ...hole for the enclosure should be 14 75 W x 25 H x 4 D Do NOT flush mount in a wall designated as a fire break 4 1 1 Preventing Water Damage Water damage to the fire system can be caused by moisture en...

Страница 44: ...lation connect the AC terminals to the power source as shown in Figure 4 1 It may be necessary for a professional electrician to make this connection The AC terminals are rated at 120 VAC 50 or 60 Hz...

Страница 45: ...ating as per your standby load calculation see Section 3 6 Wire batteries in series to produce a 24 volt equivalent Do not parallel batteries to increase the AH rating It is recommended that you repla...

Страница 46: ...inet and backup batteries follow these steps 1 Mount the accessory cabinet See figure Figure 4 3 for the four cabinet mounting holes If mounting onto drywall the accessory cabinet must be mounted onto...

Страница 47: ...e of how the wire connections can be routed However any other cabinet knock outs on either the main control panel or the RBB AB 55 cabinet that are not previously being used may be utilized to connect...

Страница 48: ...er plate mounting keyhole over the cover mounting screws See Figure 4 6 Figure 4 6 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment 7 Slide the cover into place and tighten the cover...

Страница 49: ...worst case current draw will exceed the 2 amps total then the current draw must be distributed using 5895XL Power Expanders Each 5895XL Power Expander provides an additional SBUS with an additional 1...

Страница 50: ...0 617 ft 1563 ft 2488 ft 3937 ft 0 400 463 ft 1172 ft 1866 ft 2953 ft 0 500 370 ft 938 ft 1493 ft 2362 ft 0 600 309 ft 781 ft 1244 ft 1969 ft 0 700 265 ft 670 ft 1066 ft 1687 ft 0 800 231 ft 586 ft 93...

Страница 51: ...current is calculated as follows Using this value and referring to the Wiring Distance table it can be found that the available options are 370 feet maximum using 22 Gauge wire 938 feet maximum using...

Страница 52: ...igure 4 8 illustrates SBUS1 Class B configuration SBUS 2 wiring configurations are the same as SBUS1 Figure 4 7 SBUS Class A Wiring Figure 4 8 SBUS Class B Wiring Caution For proper system supervision...

Страница 53: ...he actual number is limited by current draw and SBUS bandwidth usage as discussed below When installing a hardware module such as 5815XL 5824 SCSS 700ANN 5496 5895XL 5865 3 or 5865 4 you must use the...

Страница 54: ...e this tool if you plan to have more than eight SBUS devices per SBUS Remember to include devices that are on 5895XL SBUS repeaters in your list of devices for SBUS bandwidth calculators 4 6 SCSS 700A...

Страница 55: ...sign an SBUS ID to the SCSS 700ANN see Section 4 5 1 5 The SCSS 700ANN module must be added to the system through programming Jump Start AutoProgramming will add the module automatically see Section 8...

Страница 56: ...4 6 1 1 Flush Mounting This section of the manual describes flush mounting Follow these steps to flush mount the SCSS 700ANN 1 The back box dimensions are 9 9 32 w x 8 3 8 h The minimum depth 2 The ba...

Страница 57: ...tions Figure 4 12 Back Box Knockout Locations 3 Wire the annunciator board to the main control panel See Figure 4 8 4 Attach the annunciator and door assembly to back box as shown in Figure 4 13 using...

Страница 58: ...w into the key shaped mounting hole Do not tighten all the way See Figure 4 14 Place a level on top of the back box with the back box level insert the rest of the mounting screws Figure 4 14 Back Box...

Страница 59: ...bed in Section 4 6 2 replace the electronic assembly in the back box Place the bezel over the back box and tighten the set screws on the bezel 4 6 2 SCSS 700ANN Connection to the Panel Connect the SCS...

Страница 60: ...L See also Model 5895XL Installation Manual PN 151142 or 5815RMK Remote Mounting Kit Installation Instructions P N 151391 3 Connect the 5815XL to the control panel See Section 4 7 1 4 Use on board DIP...

Страница 61: ...nel Connect the 5815XL to the control panel as shown in Figure 4 18 After the 5815XL is connected to the panel it must be added to the system This programming step is described in Section 9 2 2 Figure...

Страница 62: ...5824 installation involves the following steps 1 Make sure power is off at the panel 2 Connect the 5824 to the panel as shown in Figure 4 19 Note Two 5824s per panel maximum 3 Use the DIP switches on...

Страница 63: ...ns Configuring the 5824 includes the following steps Add the module to the system JumpStart will add the module automatically see Section 8 1 You can also add it manually see Section 9 2 2 Select a na...

Страница 64: ...wo screens A screen similar to the one shown in Figure 4 21 will display Figure 4 21 Selecting Printer and Output Port Options 6 Select options for the printer as needed for your installation Most pri...

Страница 65: ...0 also has eight inputs for dry contact monitoring The following sub sections describe hardware installation Refer to Section 6 for programming information 4 9 1 5880 Board Layout Figure 4 22 is a pic...

Страница 66: ...The 5880 connects to the panel via the SBUS Make connections as shown in Figure 4 23 After the 5880 is connected to the panel it must be added to the system This programming step is described in Secti...

Страница 67: ...ts can be mapped to output circuits See Section 9 5 3 for programming details Wire the LEDs as shown in Figure 4 24 On connector P1 Pin 12 is an open collector output for controlling a PZT If used the...

Страница 68: ...Any type of switch supported by the control panel can be used with the 5880 For example you can use a 5880 to monitor pull stations water flow tamper reset or silence switches Wire dry contacts as sho...

Страница 69: ...for alarm and yellow typically used for trouble LEDs Installation of the 5865 3 and 5865 4 is identical The key switches and the trouble LED follow the behavior of other system annunciators and do no...

Страница 70: ...onnection The 5865 connects to the panel via the SBUS Make connections as shown in Figure 4 27 After the 5865 is connected to the panel it must be added to the system This programming step is describe...

Страница 71: ...a 4 gang box is used as an example Figure 4 28 5865 Mounting Example The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly These labels can be used in...

Страница 72: ...Connect the telephone lines as shown in Figure 4 30 The Model 7860 phone cord is available from the factory for this purpose If you do not use the model 7860 to connect to the phone lines the wire use...

Страница 73: ...contact the X terminal is negative and O terminal is positive If the circuit is programmed as an output circuit Aux power or NAC then the X terminal is positive and the O terminal is negative This sec...

Страница 74: ...as shown in Figure 4 31 2 Configure the circuit through programming see Section 9 5 Figure 4 31 Class B Notification Appliance Circuit Wiring Maximum voltage drop per Class B notification circuit is 3...

Страница 75: ...tion 9 5 Figure 4 32 Class A Notification Appliance Circuit Configuration Note In programming any point that uses multiple Flexput circuits the lowest Flexput circuit number is used to refer to the ci...

Страница 76: ...4 13 2 1 Class B Inputs You can connect conventional Class B switches such as waterflow switches and pull stations directly to the Flexput circuits of the control panel To install a Class B switch 1...

Страница 77: ...igure the circuit through programming see Section 9 5 Figure 4 34 Class A initiating Switches Note In programming any point that uses multiple Flexput circuits the lowest Flexput circuit number is use...

Страница 78: ...ustrate how to connect a UL listed 2 wire detector to the control panel 4 13 3 1 Installing 2 Wire Class B Smoke Detectors To install a Class B two wire smoke detector wire as shown in Figure 4 35 Fig...

Страница 79: ...amming any point that uses multiple Flexput circuits the lowest Flexput circuit number is used to refer to the circuit pair For example Figure 4 36 uses both Flexput circuit 5 and 6 so in programming...

Страница 80: ...panel at once 2 Each Class B loop input is paired with a unique power source as shown in Figure 4 37 3 Each loop gets smoke power from the even numbered Flexput circuit and the contact input is connec...

Страница 81: ...in Figure 4 38 Figure 4 38 Class A 4 Wire Smoke Detector Connections Note In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput circuit number used...

Страница 82: ...Flexput circuits 2 Configure the auxiliary power output through programming see Section 9 5 Figure 4 39 Flexput Circuit Location 4 13 5 1 Door Holder Power Door holder power is intended for fire door...

Страница 83: ...ntrol panel has two built in programmable relays and a built in trouble relay All relays are Form C rated at 2 5 A 24VDC Figure 4 40 Location of Conventional Relay Circuits 4 14 1 Trouble Relay The co...

Страница 84: ...ontrol panel Wiring must be enclosed in conduit 3 Program control panel Relay 1 for alarm 4 Program Flexput circuit 5 for alarm 5 Program Flexput circuit 6 for supervisory non latching Table 4 5 Keltr...

Страница 85: ...l Not suitable for remote station where separate transmission supervisory if applicable and protected premise service circuits are required for fire trouble signals Intended for connection to a polari...

Страница 86: ...et in length 2 Wire the 5220 to the control panel as shown in Figure 4 42 This drawing also shows how to connect the city box coil to terminals 3 and 4 on the 5220 Do not install an EOL resis tor in t...

Страница 87: ...4 45 4 15 3 Using the CRF 300 Addressable Relay Module for City box Connection Wire the CFR 300 as shown in Figure 4 43 Figure 4 43 CRF 300 Module for City box Connection UL listed Model 7642 Must be...

Страница 88: ...100 mA 24 VDC Alarm 100 mA 24 VDC To install the 5220 for polarity reversal follow the steps below 1 Locate the knockout on the right side of the control panel cabinet to connect the 5220 using a shor...

Страница 89: ...ontrol panel is reset To install the 7644 for polarity reversal 1 Wire the 7644 to the control panel as shown in Figure 4 45 Do not install an EOL resistor on the terminals of the flexput circuit used...

Страница 90: ...S 700 Installation Manual 4 48 53722 4 Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible rating Figure 4 45 Polarity Reversal Connection Using...

Страница 91: ...itter to the SCSS 700 dry relay contacts The SCSS 700 FACP contacts must be supervised by the remote station transmitter module using end of line resistors ELRs with a value determined by the transmit...

Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...

Страница 93: ...in the network with each site comprised of only one panel 5 1 2 Wiring Options to Connect Networked Panels 1 Direct Connect Panels can be connected cost effectively via shielded twisted pair copper w...

Страница 94: ...D panels within 20 feet of conduit run distance from each other Place the conduit for routing the direct connect networking cable between panels in a bus configuration as shown above in Figure 5 1 2 M...

Страница 95: ...be run in a BUS configuration Figure 5 2 DIP Switch terminations settings for Direct Connect Wiring option 5 4 Repeater Wiring Options Networking a group of SCSS 700 and or SCSS 700NDs at a distance...

Страница 96: ...d lines Figure 5 3 Repeater Networking Connections 5 4 1 Network Repeater Types Network repeaters are available in two configurations See Figure 5 4 1 P N IFP RPT UTP is used for twisted pair copper w...

Страница 97: ...ry Mounting Kits Repeaters can be mounted within the SCSS 700 cabinet or in an accessory cabinet Accessory kits are available that included a small cabinet with door key mounting hardware 5 foot ribbo...

Страница 98: ...inal block TB1 Each repeater has the ability to monitor for earth ground faults on the twisted pairs connected to port 1of its terminal block TB1 Earth fault detection for any wiring at Port 2 of TB1...

Страница 99: ...Figure 5 9 for repeater wiring examples 5 4 2 1 Network Repeater Cable Requirements Cable requirements for wire runs between repeaters 1 All fiber cable must be multimode 62 5 125 micron cable with ST...

Страница 100: ...5 4 2 2 Unshielded Twisted Pair Wiring between Multiple Panels Unshielded twisted pair wiring between multiple panels is shown in Figure 5 6 Class A wiring is shown with a dotted line Figure 5 6 Twis...

Страница 101: ...rking 53722 5 9 5 4 2 3 Fiber Optic Repeater Wiring Fiber optic cable between multiple panels is shown in Figure 5 7 Class A is shown with a dotted line Figure 5 7 Fiber Optic Wiring Example Class A W...

Страница 102: ...Panels A mixture of fiber optic cable and twisted pair wiring between multiple panels is shown in Figure 5 8 Class A cabling is shown with dotted line Figure 5 8 Twisted Pair and Fiber Optic Combinat...

Страница 103: ...rk wiring example using both repeaters and direct connect wiring All repeaters in the system must be placed only on panels that are at the ends of a direct connect BUS or connected to panels with no d...

Страница 104: ...is at the end of a direct connect BUS and it does not have a repeater so its DIP switches 8 9 and 10 must be ON to provide direct connect BUS termination Panel 2 is NOT at the end of a direct connect...

Страница 105: ...is at the end of a direct connect BUS but because it is also using a repeater its DIP switches 8 9 and 10 must be OFF In this example panel 6 is actually in the middle of a direct connect BUS between...

Страница 106: ...ant that much thought is given when choosing the network IDs for each panel It is difficult to change the IDs once panel programming has begun The network ID for each panel is set using DIP switch pos...

Страница 107: ...s Menu 6 2 Network Programming This section of the manual describes how to program network options using the built in annunciator All options described in this section can be programmed using the SCSS...

Страница 108: ...dit Network information 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Network Programming 3 Press to enter the Edit Network Menu 6 2 2 1 Edit Panel 4 Press t...

Страница 109: ...low you to change the currently assigned Network Panel ID to the current Network ID dip switch setting The system will be down as the panel needs to reboot in order to complete the transition When usi...

Страница 110: ...rk Programming 3 Press to enter the Computer Account Menu 4 Enter the computer code up to 6 digits then press 5 Enter the computer access code then press 6 Enter the phone number the panel will dial t...

Страница 111: ...of Function Selectable Functions Panel Operations System Reset System Silence System Ack Fire Drill Key Panel Menus System Test Fire Drill Menu Indicator Test Walk Test no Report Walk Test with Repor...

Страница 112: ...list of available characters and their numeric designators 7 Then press to finish 6 2 5 2 Edit Access Code 8 Enter new access code minimum of 4 digits maximum of 7 digit 9 Press 10 Enter code again 1...

Страница 113: ...information according to the SIA Modifier option The selections for this option are enable PI SIA Modifier Yes or No The default selection is Yes If set to No the panel ID will be included as part of...

Страница 114: ...dd or remove panels into the network See Section 6 2 1 Edit Network Edit Panel Network Panel ID See Section 6 2 2 Edit Panel Name Edit Site Assignment Edit Site Name Edit Site Member Edit Panel ID Cha...

Страница 115: ...be edited See Section 6 2 5 Edit Access Code Edit Panel Function System Reset System Silence System Ack Fire Drill Key System Tests Fire Drill Menu Indicator Test Walk Test no Report Walk Test w Repo...

Страница 116: ...ceiver Configuration Can report up to four receivers Receiver Number See Section 6 2 6 3 Receiver Format Contact ID SIA500 SIA8 SIA20 Dialer Report Table Panel See Section 6 2 6 4 Report Alarms Report...

Страница 117: ...ation smoke detector F300 23 00 D350PL Photoelectric duct smoke detector with extended air speed range F300 27 00 H355 Fixed temperature thermal detector 135 F F300 25 00 H355R Rate of rise thermal de...

Страница 118: ...device you are installing for details 7 3 1 Wiring 5815XL in Style 4 Class B Configuration No special wire is required for addressable loops The wire can be untwisted unshielded solid or stranded as...

Страница 119: ...e wiring Figure 7 1 Calculating wire run length for a simple out and back tap When using T taps the total length of all taps and the main bus must not exceed 40 000 feet This requirement must be met i...

Страница 120: ...does not use short circuit isolator devices Note Style 7 wiring you have to have an isolator module as the first device on the in and the out loops Figure 7 3 Class A SLC Configuration Note No t taps...

Страница 121: ...SD355T Photoelectric Smoke Detector with Thermal AD355 Multicriteria Photoelectric Smoke Detector with Thermal H355 Thermal Detector 135 F H355HT High Temperature Thermal Detector 190 F H355R Rate of...

Страница 122: ...be assigned any unique address from 1 to 159 There can be a sensor using address 1 and a module using address 1 0 is an invalid address In order to set the sensor above address 99 carefully remove th...

Страница 123: ...ps This includes selecting characteristics for output groups and mapping output circuits to output groups see Section 9 5 for details 8 1 JumpStart AutoProgramming The JumpStart AutoProgramming featur...

Страница 124: ...utput pattern 8 1 3 Running JumpStart AutoProgramming Run JumpStart AutoProgramming immediately after you have addressed and connected all input devices detectors pull stations and so on and output de...

Страница 125: ...tors 4 The first photoelectric or ionization detector on the system will display Select for DUCT and for NonDUCT 5 Press to select the next detector Select for DUCT and for Non DUCT Continue until all...

Страница 126: ...an important concept with the control panel In general terms mapping is assigning or linking events to outputs that should activate when events occur You do this by assigning input points to input zon...

Страница 127: ...oints are assigned to input zones Any input point can be assigned to any input zone Input points can be assigned to one zone only An input point can be designated as Unused which means it has not been...

Страница 128: ...stallation Manual 8 6 53722 8 2 2 Output Circuit Mapping Figure 8 3 is a simple example showing how to assign notification and relay output circuits to groups Figure 8 3 Example of Assigning Output Ci...

Страница 129: ...Table 8 1 Event Types Zone Panel Site Manual Pull Alarm Aux 1 Fire Drill Water FLow Alarm Aux 2 General Alarm Detector Alarm heat or smoke detectors SBus Exp Trouble General Supervisory Aux 1 and Aux...

Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...

Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...

Страница 132: ...Model SCSS 700 Installation Manual 8 10 53722 Figure 8 6 Example of Events Mapped to Output Groups and Patterns within a Networked Site...

Страница 133: ...Programming Overview 53722 8 11 Figure 8 7 Example of SCSS 700PK Software mapping Zone Events Figure 8 8 Example of SCSS 700PK Software mapping Panel events...

Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...

Страница 135: ...are mapped to zones and output groups Typically you would create two output groups for each zone one for alarms and one for troubles LED points are available when models 5865 3 4 and or 5880 are used...

Страница 136: ...Model SCSS 700 Installation Manual 8 14 53722 8 2 5 Mapping LED Points for a Networked System Figure 8 11 Example of Expanding Mapping of LED Points Across Panels...

Страница 137: ...iator or a SCSS 700ANN remote annunciator The following subsections describe programming basics including a description of editing keys available for programming and how to move through programming me...

Страница 138: ...ending on which screen you are currently using The chart below is a generic explanation To Press Select from a menu Enter the number of the option Enter numeric data Press the appropriate number on th...

Страница 139: ...ming Overview 53722 8 17 8 4 1 3 Editing Keys The keys shown in Figure 8 13 are available for use when you are in the Panel Programming Menu Figure 8 13 Editing Keys Available from the Panel Programmi...

Страница 140: ...lass Section 9 2 1 Add Module 5815XL SLC Section 10 SCSS 700ANN Key stat 5824 Ser Par IO 5895XL Pwr Sup 5496 NAC Expand 5880 LED IO Dev 5865 LED Annunc VIP Amplifier See section 9 9 VIP Series Install...

Страница 141: ...elected zone Section 9 3 4 Group1 Edit Group Select Group Group Name Enter Name1 Section 9 4 1 1 Enter Number1 Enter Name2 Enter Number2 Group Properties VIP Switch Number 1 through 32 Section 9 4 1 2...

Страница 142: ...FIREDRILL SILENCE RESET PAS_ACK ZN_AUX1 LATCH NLATCH ZN_AUX2 LATCH NLATCH SYS_AUX1 LATCH NLATCH SYS_AUX2 LATCH NLATCH DETECT SW TAMPER LATCH NLATCH MAN REL ILOCK NOTIF OUTPUT PT Select Group Section 9...

Страница 143: ...elect Sensor LiteSpeed ONLY DETECTOR PHOTO SDR BAS RLY BAS Section 9 5 BEAM PHOT HEAT SDR BAS RLY BAS HEAT HT SDR BAS RLY BAS ACCLIMATE SDR BAS RLY BAS PHOT DUCT DCT RLY ION DUCT DCT RLY HEAT SDR BAS...

Страница 144: ...one TAMPER Select zone FIREDRILL SILENCE RESET PAS_ACK Select zone ZN_AUX1 Select zone ZN_AUX2 Select zone SYS_AUX1 SYS_AUX2 MAN REL ILOCK A SWITCH Same as B SWITCH B DETECTOR 2 WIRE SMK 4 WIRE SMK A...

Страница 145: ...Option TT TouchTone Touch Tone TT PL TouchTone alternating with pulse see Section 9 6 2 3 PULSE Pulse dialing Rotary Pulse Format U 60 40 U Section 9 6 2 4 E 66 34 Line Monitor Yes Y Section 9 6 2 5...

Страница 146: ...ystem Clock Format AM PM or military Section 9 6 5 4 MIL AC Freq 50 Hz Section 9 6 5 5 60 Hz Neither Misc Options 2 SYNC Strbs w Sil Y Enabled Disabled Section 9 6 6 1 N Disabled Auto Display Oldest Y...

Страница 147: ...4 32 4 sec increments 8 Allow Message Restart with new alarm Yes Y NO N No Edit Ethernet IP Address Section 4 1 3 Subnet Mask Default Gateway DCHP Enable Y Yes N No JumpStart AutoPrg Y Yes N No See Se...

Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...

Страница 149: ...s JumpStart allows you to confirm the integrity of the installation prior to performing any custom programming After determining that the hardware is properly installed custom programming can be perfo...

Страница 150: ...n is selected are module ID module name class of wiring Class A or Class B or features that are specific to the module to be edited To edit an existing module 1 Enter the installer code The panel will...

Страница 151: ...is option applies only to the 5815XL Each module has a unique set of options that spe cifically applies to the functionality of the module being edited Choose the class of wiring you wish to use for t...

Страница 152: ...ct a name for the module if desired You must save changes when you exit the Panel Programming or the new module will not be added Note If you Add a Module that has not been physically connected the pa...

Страница 153: ...ption in Panel Programming you can edit add delete and view zone points Selections made here affect all detectors and switches in the zone Up to 999 zones can be used in each panel 9 3 1 Edit Zone Fea...

Страница 154: ...9 3 1 1 Edit Zone Name 6 Press to edit the selected zone name Refer to Appendix B for a list of available characters and their numeric designators A screen similar to the one shown in Figure 9 2 disp...

Страница 155: ...detector sensitivity and smoke detector sensitivity 1 Do steps 1 through 5 of Section 9 3 1 2 Press to edit the properties of the selected zone Detection type also selected from this screen see Table...

Страница 156: ...o an output group for the prealarm event the output group will activate The prealarm will not be reported to the central station When two count is used detector spacing shall be cut in half you shall...

Страница 157: ...to the main menu 2 Select for Panel Programming IMPORTANT Drift compensation is automatic for all smoke detectors photoelectric and ionization The feature is always in effect no programming is require...

Страница 158: ...e programmed through the Zone Edit sub menu Up to 999 zones can be used per panel 9 3 3 Delete Zone To delete a zone follow these steps 1 Enter the installer code The panel will automatically go to th...

Страница 159: ...installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Press to enter zone menu 4 Press to view zone points 5 Enter th...

Страница 160: ...up is defined as either a voice output group or a non voice output group Output points that are audio circuits all circuits on the VIP Amplifier and VIP CE4 can only be assigned to voice output groups...

Страница 161: ...ilable characters and their numeric designators Group Name Example Figure 9 4 Editing Group Name Example 9 4 1 2 Edit Group Properties The Edit Group Menu allows you to select options for each group f...

Страница 162: ...IP VCM and VIP SW16 Figure 9 6 illustrates how the numbers selected correspond to the VIP VCM and SW16 Figure 9 6 Corresponding Switch and LED for Mapping Output Groups 7 To get to this menu item repe...

Страница 163: ...Section 9 4 1 2 A total of 999 output groups can be defined 9 4 3 Delete Group 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads...

Страница 164: ...izing Please wait 3 Press to enter group menu 4 Press to view group points 5 Enter the group number then press 9 4 5 Edit OPG Template 1 Enter the installer code The panel will automatically go to the...

Страница 165: ...5XL Module points follow these steps 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Press to enter...

Страница 166: ...onization detector HEAT spot heat detector PHOT DUCT duct photoelectric detector ION DUCT duct Ion detector ACCLIMATE acclimate photoelectric detector HEAT HT high temperature heat detector PHOTO HEAT...

Страница 167: ...l option available from the annunciator When the switch is activated a fire drill begins when the switch is de activated the fire drill ends SILENCE This system level switch is an alternative way to s...

Страница 168: ...iary power source Power is always present at Constant circuits AUX RESET Use for auxiliary power resettable applications See Section 4 13 5 3 for a description of how this option operates AUX DOOR Use...

Страница 169: ...Select the function by pressing the or arrows 11 Press 12 Select the zone by pressing the or arrows 13 Press 14 Edit point name See Section 9 5 3 1 Or Press to skip point name edit 15 Repeat Steps 1 t...

Страница 170: ...fer to comments column of Table 9 3 for description of these options Latch or Non latching feature only appears for waterflow supervisory tamper zone aux1 zone aux2 system aux1 and system aux2 WATERFL...

Страница 171: ...it 3 Press to enter point menu 4 Press the or arrows to select the desired module Refer to Section 8 5 for available choices 5 Press Figure 9 7 Programming Points Screen for 5880 and 5865 Modules 6 En...

Страница 172: ...available characters and their numeric designator 18 Press to accept If you wish to bypass the Edit Name field press 9 5 4 Point Programming For VIP Amplifier VIP CE4 To program VIP Amplifier or VIP...

Страница 173: ...ing 53722 9 25 9 Press 10 Press the or arrows to select the desired Group 11 Press 12 Edit module name See Section 9 5 3 1 Or Press to skip module name edit 13 Repeat Steps 1 through 13 for all voice...

Страница 174: ...l automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Select for System Options 4 From the next menu select for Auto Test Time 5 Enter the hour yo...

Страница 175: ...codes a pause and so on The following special characters are available Use the number buttons on the annunciator or the up and down arrow keys to select special characters Characters begin displaying...

Страница 176: ...select the pulse ratio for rotary dialing option then press Options are 9 6 2 5 Line Monitor Enable the line monitor for each phone line that will be used See Figure 9 8 for location of this field on...

Страница 177: ...PK See the SCSS 700PK manual for more information 11 Select Y answering machine bypass enabled or N answering machine bypass disabled by pressing the or arrow then press 9 6 2 7 Phone Line Unused This...

Страница 178: ...Model SCSS 700 Installation Manual 9 30 53722 A screen similar to the one shown in Figure 9 9 will display Figure 9 9 Changing Day Night Sensitivity Time...

Страница 179: ...e wait 3 Select for System Options 4 Select for Holiday Days A screen similar to that shown in Figure 9 10 will display 5 Edit the holiday schedules you wish to change or add holidays as needed in the...

Страница 180: ...ogramming water flow delay follow these steps 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Select...

Страница 181: ...this feature is enabled set to Yes the system clock will switch to DST on the first Sunday in April at 2 00 a m and revert to standard time on the last Sunday in October at 2 00 a m After January 200...

Страница 182: ...stallation site The Neither option can be used in areas where the AC line frequency is not dependable and you want the panel to calculate time from the internal crystal The internal crystal is not as...

Страница 183: ...e only functions with outputs that use a synchronized output pattern 5 Press the or arrow to toggle this selection between Y Yes or N No 6 Press or to make your selection and move to the next programm...

Страница 184: ...me and set the start and end week and month of Daylight Saving Time To edit Miscellaneous Options 3 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Progr...

Страница 185: ...The second Sunday in March DST End The first Sunday in November To set the start and end for Daylight Saving Time 8 Press the or arrow to select the week 1st 2nd etc Daylight Saving Time starts then...

Страница 186: ...You cannot change the internal banner To customizing the banner display message 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display read...

Страница 187: ...o to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Select for System Options 4 Select for Edit Voice Commands 5 Select the command you wish to edit Fire Cmd Aux...

Страница 188: ...0 Edit Ethernet 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Select for System Options 4 Select f...

Страница 189: ...arning screen 5 Press IMPORTANT JumpStart Auto Programming is used to auto learn the system hardware after devices have been added or removed from the system Hardware devices which remain the same bet...

Страница 190: ...faults All programming will be lost 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Select for Resto...

Страница 191: ...ng or editing user message through the 7780 SKE Voice Evacuation Software 4 Connect the computer to the VIP VCM via the serial ports 5 Run the 7780 software 6 Select 7 Through the 7780 software add or...

Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...

Страница 193: ...s Please read this entire section carefully before operating the panel Press to view Main Menu Select the desired menu option Enter your access code if prompted Note See Section 6 2 5 or information o...

Страница 194: ...Model SCSS 700 Installation Manual 10 2 53722 10 2 Annunciator Description Figure 10 1 shows the annunciator that is part of the control panel board assembly Figure 10 1 Control Panel Annunciator...

Страница 195: ...ng over four lines of 40 characters each Annunciator keys beep when they are pressed 10 2 2 Banner The banner is the message that displays on the control panel when the system is in normal mode no ala...

Страница 196: ...u Options Description System Tests From here both menus can access Fire Drill and Indicator Test Point Functions From here both menus can enable disable points Event History Display event history on t...

Страница 197: ...le Enable NACs by Template 1 From the Main Menu select for Point Functions 2 Press for Disable NACs by Template press to Enable NACs by Template 3 Use and to move through the list of templates Press t...

Страница 198: ...isable Enable Zone Points 1 From the Main Menu select for Point Functions 2 Press to Disable Zone Points press to Enable Zone Points 3 Use and to move through the list of zones Press to select the zon...

Страница 199: ...ct for System Tests From the test menu select Clear History Buffer In network setups this clears the History Buffer of all panels in the site 10 4 4 Conduct a Fire Drill 1 From the Main Menu press for...

Страница 200: ...on reporting will occur as normal during the walk test The panel generates a TEST report to the central station when the walk test begins During a walk test the panel s normal fire alarm function is c...

Страница 201: ...the annunciator To silence a site enter a multi site access password select a site and then press 10 4 9 Reset Alarms Press to perform a control panel reset If an external reset switch has been instal...

Страница 202: ...tor Sensitivity Compliance You can print detector status by uploading the detector status to and printing from SCSS 700PK 10 4 11 View Status of a Point 1 From the Main Menu select for Point Status 2...

Страница 203: ...the Web Site Once a panel has been updated with using the Firmware Update Utility you can use Send Receive Update to propagate the firmware to the other panels in the network 1 Press for Send Update o...

Страница 204: ...be calling is already displayed press Continue with Step four If the phone number you will be calling is not already displayed enter the number and press A phone number can be up to 40 digits long an...

Страница 205: ...ll Systems Normal display indicates that the system is in normal mode The current date and time display on the last line of the LCD Enter the appropriate code to activate the User or Installer Menu Al...

Страница 206: ...he supervisory condition has been corrected the system will restore itself automatically Trouble A system trouble condition occurs The dialer seizes control of the phone line and calls the central sta...

Страница 207: ...ate and time normal mode screen displays Menus are not available during the reset process Silenced An alarm or trouble condition has been silenced but still exists To silence alarms and troubles press...

Страница 208: ...ly Silenced is enabled on a multi site annunciator it will be indicated by a blinking Silenced LED If any new troubles supervisory pre alarms or alarms are triggered in any assigned sites Locally Sile...

Страница 209: ...efaulted as an Alarm output group for all releasing zones NAC 98 001 is assigned to Output Group 2 Output Group 3 is created Output Group 3 will be defaulted as an Pre Alert output group for all relea...

Страница 210: ...S 700 Installation Manual 10 18 53722 Figure 10 4 Wiring Configuration for Solenoid Model 7641 Must be Mounted at the Solenoid Releasing solenoid Use 24 VDC UL listed model in table 10 2 1 solenoid pe...

Страница 211: ...r an General Alarm and Release Output Activation If two or more addressable detectors or a manual release switch activate the Alarm and the Release outputs will activate Also refer to Table 10 3 Impor...

Страница 212: ...Any release requires the activation of an interlock switch and either a manual release switch or 2 activated addressable detectors When these conditions are met the Release and General Alarm outputs w...

Страница 213: ...ou would like to utilize 2 Enter a PIN with F Key macro recording privileges 10 9 1 Recording an F Key macro 1 Access the F Key Recording Menu and select the Start FKEY Recording option 2 This will ex...

Страница 214: ...cting Abort FKEY Recording option 2 This will exit you from the menu 10 9 3 Erasing an F Key macro 1 If an F Key macro has already been recorded you can erase it by accessing the F Key Recording Menu...

Страница 215: ...ther Report by Point or Report by Zone is se lected AC power low trouble AT 0 ATNN000000 1 301 00 000 AC power low trouble restore AR 0 ARNN000000 3 301 00 000 Auto dialer test communications trouble...

Страница 216: ...D 000 SBUS expander trouble ET Exp ID ETNNXX0000 1 333 Exp ID 000 SBUS expander trouble restore ER Exp ID ERNNXX0000 3 333 Exp ID 000 SLC class A supervision trouble ET Exp ID ETNNXX0000 1 331 Exp ID...

Страница 217: ...Zone FTNN000ZZZ 1 373 02 Zone Zone based acknowledge switch trouble restore FJ Zone FJNN000ZZZ 3 373 02 Zone Zone based AUX1 switch alarm UA Zone UANN000ZZZ 1 140 01 Zone Zone based AUX1 switch alarm...

Страница 218: ...3 320 Exp ID Point Positive Alarm Sequence acknowledge switch disabled pi Exp ID FB Point FBNNXXPPPP 1 571 Exp ID Point Positive Alarm Sequence acknowledge switch enabled pi Exp ID FU Point FUNNXXPPP...

Страница 219: ...Exp ID Point Zone based AUX1 switch trouble restore pi Exp ID UJ Point UJNNXXPPPP 3 373 Exp ID Point Zone based AUX2 switch alarm pi Exp ID UA Point UANNXXPPPP 1 140 Exp ID Point Zone based AUX2 switc...

Страница 220: ...t sent in the SIA event parameters For Example see Table 11 2 SIA SCSS 700 Panels PI Modifier Reporting Examples Event Report Zone Point Panel ID Module Zone ZZZZ Point ZZZZ Fields Sent SIA Event Data...

Страница 221: ...er ZZZZ 2 Based on the actual Event Code the Module Number or Event Parameter fields might not contain pertinent information In that case the field will contain zeros 3 The account number is sent usin...

Страница 222: ...Test n a 32 n a n a n a EE PP MM ZZZZ RP32000000 Battery Trouble Panel 32 n a 32 98 n a n a EE PP MM ZZZZ YT3298000 0 Battery Trouble Expander 18 n a 32 18 n a n a EE PP MM ZZZZ YT3218000 0 SLC Loop...

Страница 223: ...wiring is correct section 7 5 if using LiteSpeed devices For 5815XL devices make sure the device connects to the 5815XL via the SLC OUT terminals There can be only one SLC loop on the main panel and o...

Страница 224: ...he panel indicates a ground fault trouble condition trouble message GROUND FAULT displays An earth ground fault occurs when the panel senses an unexpected flow of current from one or more of its termi...

Страница 225: ...n Appliances sound Measure battery voltage while the Notification Appliances are sounding Replace any battery with terminal voltage less than 85 of rating Reapply AC power and RESET system 12 2 2 Even...

Страница 226: ...lect Point Functions from the Main Menu 2 Select SLC Single Device Locator A message similar to the one shown in Figure 12 1 will display Figure 12 1 Shut Down Warning 3 Press the or arrow to toggle N...

Страница 227: ...r to the one shown in Figure 12 2 will display Figure 12 2 Shut Down Warning 3 Press the or arrow to toggle NO to YES then press If NO is chosen you will exit back to the Point Function menu If Yes is...

Страница 228: ...l to test a point s output mapping Follow these steps to control a I O point 1 Select Point Functions from the Main Menu 2 Select I O Point Control 3 Select the Module the point is on 4 Enter the zone...

Страница 229: ...Terminal Function Terminal Label Low Biased High Biased Values in Ohms High Trip High Restore Low Trip Low Restore Flexput Notification Circuits X I O 8 0 0 O 0 0 X I O 7 0 0 O 0 0 X I O 6 0 0 O 0 0 X...

Страница 230: ...0 SBUS Power 0 0 0 0 SBUS Communication B SBUS 2 IN 0 0 A 0 0 SBUS Power 0 0 0 0 SLC Terminals SLC OUT 0 0 0 0 SLC IN 0 0 0 0 Table 12 1 Earth Fault Resistance Values by Terminal Function Terminal Lab...

Страница 231: ...scription Module Addr Zone Group Description On board 1 On board 30 On board 2 On board 31 On board 3 On board 32 On board 4 On board 33 On board 5 On board 34 On board 6 On board 35 On board 7 On boa...

Страница 232: ...On board 77 On board 121 On board 78 On board 122 On board 79 On board 123 On board 80 On board 124 On board 81 On board 125 On board 82 On board 126 On board 83 On board 127 On board 84 On board 128...

Страница 233: ...board 147 On board 154 On board 148 On board 155 On board 149 On board 156 On board 150 On board 157 On board 151 On board 158 On board 152 On board 159 On board 153 Table 13 1 Installation Record of...

Страница 234: ...ices Use the table below to record devices installed on additional 5815XL s Make a copy of this page if additional pages are needed Table 13 2 Installation Record of Devices Installed on 5815XL Module...

Страница 235: ...Installation Records 53722 13 5 Table 13 2 Installation Record of Devices Installed on 5815XL Module Addr Zone Group Description Module Addr Zone Group Description...

Страница 236: ...nstallation Manual 13 6 53722 13 2 Conventional Output Point Record This chart can be used to keep track of how conventional output points circuits have been configured Point Circuit Group Description...

Страница 237: ...pliances compatible with the fire alarm control panel Appliances which can be synchronized indicate the type of SYNC available in the columns marked Audio and or Visual Table A 1 Compatible Notificati...

Страница 238: ...FC Horn Strobe P241575W FC Horn Strobe P241575F FC Horn Strobe P241575K FC Horn Strobe P2430 FC Horn Strobe P2430W FC Horn Strobe P2430K FC Horn Strobe P2475 FC Horn Strobe P2475W FC Horn Strobe P2475...

Страница 239: ...Horn Strobe GCC24 Multi Candella Horn Strobe Ceiling Mount GCCR24 Multi Candella Horn Strobe Ceiling Mount GCS24 Multi Candella Strobe Ceiling Mount GCSR24 Multi Candella Strobe Ceiling Mount GECR 24...

Страница 240: ...Strobe P2RH 2 Wire Horn Strobe High Candela P2RH P 2 Wire Horn Strobe High Candela PC2RH 2 Wire Horn Strobe High Candela PC2RH P 2 Wire Horn Strobe High Candela P2W 2 Wire Horn Strobe P2W P 2 Wire Ho...

Страница 241: ...RHK 4 Wire Horn Strobe High Candela PC4RH 4 Wire Horn Strobe High Candela SR Strobe SR P Strobe SCR Strobe SCR P Strobe SRH Strobe High Candela SRH P Strobe High Candela SCRH Strobe High Candela SCRH...

Страница 242: ...e AS 24MCW Horn Strobe AS 24MCWH Horn Strobe ASWP 2475W Horn Strobe Weatherproof ASWP 2475C Horn Strobe Weatherproof ASWP 24MCWH Horn Strobe ASWP 24MCCH Horn Strobe CH 70 Chime CH 90 Chime CH70 241575...

Страница 243: ...NH Horn NS 121575W Horn Strobe NS 241575W Horn Strobe NS 24MCW Horn Strobe NS 24MCC Horn Strobe NS 24MCCH Horn Strobe ZNS MCW Horn Strobe ZNS MCWH Horn Strobe ZNS 24MCC Horn Strobe ZNS 24MCCH Horn Str...

Страница 244: ...24MCCH Strobe Weatherproof RSSWP 2475W Strobe Weatherproof RSSWP 2475C Strobe Weatherproof RSSWP 24MCWH Strobe Weatherproof ZRS MCWH Strobe ZRS 24MCC Strobe ZRS 24MCCH Strobe MB G6 24 Motor Bell MB G1...

Страница 245: ...umber greater than or equal to the maximum reset time of the smoke detector SCSS 700 Identifier 24H Operating voltage Range 17 1 27 3 VDC Table A 2 Compatible Two Wire Smoke Detectors Style B Manufact...

Страница 246: ...A N A 16 loop 2451TH B401B A N A 16 loop Table A 3 Compatible Two Wire Smoke Detectors Style B or Style D Manufacturer Model Name or Number Compatibility ID per Loop Head Base System Sensor 2W B A N...

Страница 247: ...ation 0 05 50 System Sensor 1424 Ionization 0 10 41 System Sensor 1451 w B402B Base Ionization 0 10 39 System Sensor 2112 24ATR Photoelectric 0 50 60 70 System Sensor 2112 24AITR Photoelectric 0 50 60...

Страница 248: ...WITAR B 12 24 Volt I3 Photo w Isolated Therm Sounder Relay 05 50 System Sensor 2W MOD2 I3 Loop Test Maintenance Mod 05 System Sensor RRS MOD I3 Reversing Relay Sync Module 05 System Sensor 64241 Proje...

Страница 249: ...L TYPE Current mA Edwards DH150A Floor Mount 96 Edwards DH154A Flush Mount 96 Edwards DH158A Surface Mount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon...

Страница 250: ...SCSS 700 Installation Manual A 14 53722...

Страница 251: ...ssociated numeric designator When programming 1 Use the up or down arrow key to scroll to the mode wanted 2 Press the number shown in Table B 1 until the character wanted is shown 3 Arrow left and rig...

Страница 252: ...ears 2 Press or to change mode to lower case letters Press until i appears 3 Press until r appears 4 Press until e appears 5 Press to accept 6 Press to space then continue to next word using the same...

Страница 253: ...ress to access Main Menu then rotate the key or enter a code if prompted 2 Then press to select Point Functions 3 Enter code if prompted then press to select Point Status 4 Select the module the devic...

Страница 254: ...Cut Along the Dotted Line...

Страница 255: ...TIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR A...

Страница 256: ......

Страница 257: ......

Страница 258: ...Stanley Convergent Security Solutions Inc 877 476 4968 www stanleycss com To view license information please visit www stanleycss com licenses html...

Отзывы: