Model SCSS-700 Installation Manual
1-4
53722
1.3
Compatible Products
Table 1-2 lists the products available from Stanley for use with the SCSS-700.
Table 1-2: SCSS-700 Compatible Products
Type of
Device
Model
Description
LiteSpeed
Addressable
SLC Devices
See Section 7.1 for a list of compatible devices.
Other
Modules
5815XL SLC Expander
Each 5815XL allows up to 159 LiteSpeed sensors and 159 LiteSpeed modules to be added to
the system. The number of 5815XLs that can be added to the system is limited only by the
maximum number of SBUS devices. However the maximum point count is limited to 636 per
panel. This allows the installer to distribute the 636 points on more than two SLC loops and
also allows all 636 points to be all sensors or all modules or any combination of sensors and
modules.
5824 Serial/Parallel Printer
Interface Module
Allows a printer to be attached for the on-site event logging.
Maximum of two 5824s per control panel
5895XL Intelligent Power
Module
Provides additional power, six Flexputs™ circuits, and two Form C relays.
See Model 5895XL
Installation Instruction PN 151142.
5496 Intelligent Power
Module
Provides four additional Notification Appliance Circuits/Auxiliary power.
SCSS-700ANN Remote Fire
Alarm Annunciator
Same operation, similar appearance as on-board annunciator.
5865-3 and 5865-4 LED
Annunciator
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has key switches
for silence and reset, and a system trouble LED.
5880 LED I/O Module
Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In addition the 5880
has eight generic switch input points.
5883 General Purpose Relay
Module
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be used
with each 5880 module.
VIP-VCM
Voice Control Module used with the SCSS-700VS.
Refer to the
VIP-Series
Installation Manual
P/N
53796 for more information
on these accessories. VIP
series is not FM approved
for use with SCSS-700
.
VIP-SW16
16 switch expander with the SCSS-700VS
VIP-50
50 watt audio amplifier
VIP-125
125 watt audio amplifier
VIP-CE4
Provides four additional audio circuits for the VIP-50/VIP-125
SCS-700RM
Remote Microphone used with the SCSS-700VS.
Misc.
7860 Telephone Cord
RJ31X cord for connecting phone line to the SCSS-700.
SCSS-700PK Software Suite
For communication and panel programming with a Windows-based computer and *modem
(see Table 1-3 for compatible modems). Enables remote viewing of detector status and event
history.
RBB
Remote Battery Box for mounting backup batteries up to 35AH that are too large to fit into the
main control panel cabinet.
Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
AB-55
Remote Battery Box for mounting backup batteries up to 55AH that are too large to fit into the
main control panel cabinet.
Dimensions: 20" W x 12" H x 7.5" D (50.8 cm W x 30.48 cm H x 19.05 cm D)
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......