Networking
53722
5-1
Section 5
Networking
5.1
Network System Hardware Features
SCSS-700 panels can be networked to create a virtual system that is larger than 636
addressable points. Each additional SCSS-700/SCSS-700ND provides another 636
addressable points to the network total. For example, a network of eight panels provides a
maximum addressable point capacity of 5,088 points (636 x 8 = 5,088).
5.1.1
Networked Sites
A networked site is a logical group of SCSS-700 and/or SCSS-700ND panels that behave as
though the logical group is one large control panel. Each building is referred to as a “site”. All
panels in a site operate as a single panel. The control functions like reset, silence or alarm
activation operate across the entire site. There can be one or more logical sites within a
networked system. Taken to the extreme, the maximum number of sites within a network
system is limited to the number of panels in the network with each site comprised of only one
panel.
5.1.2
Wiring Options to Connect Networked Panels
1. Direct Connect - Panels can be connected cost effectively via shielded twisted pair copper
wire within conduit when the panels are located no more than 20 feet apart and in the same
room.
2. Repeater Connection - Panels separated by more than 20 feet or are located in multiple
buildings, must use the IFP-RPT network repeater hardware to provide up to 3000 feet of
separation with twisted pair copper wire or up to 8dB loss of signal separation for fiber
optic cable.
All methods of panel connectivity can be used within the same networked system. The
network architecture provides true peer to peer capability allowing network survivability for
all hardware that remains operational in the event of partial system failure.
5.2
Model SCSS-700ND
The model SCSS-700ND provides the same power and point capacity of an SCSS-700 panel,
but does not include any user interface. It is used in networked systems where added power
and/or point capacity is required but where additional user interface is not needed.
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......