System Operation
53722
10-17
10.7 Releasing Operations
This control panel supports two types of releasing, Double Interlock Zone, and Single
Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the
system, and the Single Interlock does not. An interlock switch is typically a dry-contact
pressure switch.
When a Single or Double Interlock Zone releasing is selected the system is will automatically
default the following system parameters:
Note: The defaults created can be modified through programming if desired.
•
Output Group 2 is created. Output Group 2 will be defaulted as an “Alarm” output group
for all releasing zones. NAC [98:001] is assigned to Output Group 2.
•
Output Group 3 is created. Output Group 3 will be defaulted as an “Pre-Alert” output
group for all releasing zones. NAC [98:002] is assigned to Output Group 3.
•
Output Group 4 is created. Output Group 4 will be defaulted as a “Release” output group
for all releasing zones. NAC circuit [98:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches, or inter-
lock/pressure switches.
Note: For manual release operation, Installer must use an FM approved/ UL listed releasing manual station.
Table 10-2: Approved Releasing Solenoids
Manufacturer
Part Number
Rating
Current
Freq
Asco
T8210A107
24 VDC
3A max
0 Hz
8210G207
24 VDC
3A max
0 Hz
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......