Agency Listings, Approvals, and Requirements
53722
2-3
Restricted Options:
•
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 -
30 hours. For UL certified installations this number must be set from 1 to 3 hours.
•
The system allows the use of non-latching spot type smoke detectors. This feature may not
be used in commercial applications whereby a general alarm is sounded. It is intended for
elevator recall, door holding applications, and hotel/motel room applications.
•
The system allows the Alarm Verification confirmation time to be set from 1 to 255
seconds. For UL certified installations the setting must be a minimum of 60 seconds.
•
Call forwarding shall not be used.
•
When two count is used detector spacing shall be cut in half, you shall not use the alarm
verification feature, and no delay shall be used.
•
P.A.S feature shall be used only with automatic detectors.
2.2.2
Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the SCSS-700 sends an auto-
matic daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
2.2.3
Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4
Requirements for Remote Station Protected Fire
Alarm Systems - Digital Alarm Communicator
Transmitter (DACT)
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 1-3 hours for UL installations.
Содержание SCSS-700
Страница 2: ......
Страница 12: ...SCSS 700 Installation Manual 8...
Страница 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Страница 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Страница 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Страница 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Страница 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Страница 130: ...Model SCSS 700 Installation Manual 8 8 53722 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 131: ...Programming Overview 53722 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 134: ...Model SCSS 700 Installation Manual 8 12 53722 Figure 8 9 Example of SCSS 700PK Software mapping Site Events...
Страница 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Страница 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Страница 250: ...SCSS 700 Installation Manual A 14 53722...
Страница 254: ...Cut Along the Dotted Line...
Страница 256: ......
Страница 257: ......