Installation Manual: PAD100-PSSA/PSDA Pull Station (Single & Dual Action)

NOTICE TO THE INSTALLER

This manual provides an overview and the installation instructions for the PAD100-PSSA / PSDA (Single Action / Dual Action)

module. This module is only compatible with addressable fire systems that utilize the PAD Addressable Protocol.

All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National 

Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For 

further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system 

operation.

1.  Description

The PAD100-PSSA (Single Action) is activated by pulling the white "T" bar handle down. The PAD100-PSDA (Dual Action) is 

activated by lifting the front cover and then pulling the white "T" bar handle down. Once activated, the "T" bar cannot be reset 

without opening the front cover. Opening the front cover will also activate the pull station. To reset the PAD100-PS series, use the 

Potter WS-93 key to unlock and open the front cover. Once the cover is open, push the "T" bar back into the normal position and 

re-secure the front cover. It is a non-coded addressable pull station and installs on a single gang box or surface mounts using the 

P32-BB or P32-DBB (deep) back box.

2.  Setting the Address

All PAD protocol detectors and modules require an address prior to connection to the panel's SLC loop. Each PAD device's 

address 

(i.e., detector and/or module)

 is set by changing the dip switches located on the device. PAD device addresses are 

comprised of a 

seven (7) position dip switch

 used to program each device with an address ranging from 1–127.

Figure 1. PAD Device Dip Switch Addresses Table (Addresses 1

127)

Note:

 Each

 "gray" box 

indicates that the dip switch is 

"On,"

 and each

 

"white" box 

indicates

 "Off."

The examples shown below illustrate a PAD device's dip switch settings: the 1st example shows a device 

not addressed 

where all 

dip switch settings are in the 

default

 

"Off" position

, the 2nd illustrates an 

addressed PAD device

 via the dip switch settings.

Figure 2. Examples of PAD Device Showing Default Dip Switch Setting (Unaddressed) & Addressed PAD Device

Document 5406320-A  02/16

Potter Electric Signal Co., LLC              •              St. Louis, MO              •            Phone: (866) 956-0988              •             www.pottersignal.com

 

PAGE 1 OF 3

1 2 4 8 16 32 64

1 2 4 8 16 32 64

1 2 4 8 16 32 64

1 2 4 8 16 32 64

1 2 4 8 16 32 64

1

27

53

78

103

2

28

54

79

104

3

29

55

80

105

4

30

56

81

106

5

31

57

82

107

6

32

58

83

108

7

33

59

84

109

8

34

60

85

110

9

35

61

86

111

10

36

62

87

112

11

37

63

88

113

12

38

64

89

114

13

39

65

90

115

14

40

66

91

116

15

41

67

92

117

16

42

68

93

118

17

43

69

94

119

18

44

70

95

120

19

45

71

96

121

20

46

72

97

122

21

47

73

98

123

22

48

74

99

124

23

49

75

100

125

24

50

76

101

126

25

51

77

102

127

26

52

1 2 4 8 16 32 64

1 2 4 8 16 32 64

1 2 4 8 16 32 64

1 2 4 8 16 32 64

1 2 4 8 16 32 64

Off

On

1 2 4

16

8

32 64

All dip switches are 

shown in the "Off" 

position.

Off

On

1 2 4

16

8

32 64

Example shows this PAD device's 

address = 42. Dip switches #2, 8 & 

32 are in the "On" position.

Отзывы: