Global Fire Equipment // 

globalfire.pt 

ma_oexv2_01_010001_en_180730

 

 
 

ORION-EX V2 

Conventional Fire Detection & Extinguishing Panel 

 

INSTALLATION, OPERATION & MAINTENANCE MANUAL

 

 

 

GENERAL DESCRIPTION 

 

The ORION-EX Conventional Fire Detection and Extinguishing Panel is designed and manufactured to comply with 
EN54-2, EN54-4 and EN12094-1 standards. 

 
Advanced configuration solutions include the following: programmable pre-release and extinguishing times, electro valve and 
flow pressure switch status indications; start and abort remote activation; four fire detection zones causing different effects. 
Finally all inputs are fully monitored for both Fire, Activation and Fault Conditions.  
 

MAIN FEATURES 

Fire Detection Zones: 2 crossed Zones and 1 individual Zone linked with automatic extinguishing cycle. One 

dedicated Zone only for fire detection which doesn’t start automatic extinguishing cycle 

Up to 32 conventional devices (smoke and/or heat detectors and call-points) per zone 

Active End of Line for Zone wiring monitoring (10uF/50V bipolar capacitor) 

Programmable Pre-Release and Extinguishing times 

Monitored inputs for Manual Extinguishing Cycle Activation and Remote Abort 

Electrovalve solenoid and Weight/Flow/Pressure Switch Status monitoring 

One man test capability 

Supervised auxiliary 24-volt supply output 

3 Supervised/monitored output circuits 

1 Remote reset input 

2 Relay outputs for fire and fault status indication 

Dedicated repeater panel and analogue loop interface 

Additional output via MPX-REL & MPX-SNDR modules 

Fully EN54-2, EN54-4 and EN12094-1 compliant. 

 

IMPORTANT SAFETY NOTES 

 
● This equipment must only be installed and maintained by a suitably qualified and technically competent person. 
● This equipment must have an Earth Connection. 
● A basic knowledge and training in the installation of Fire and Extinguish Detection systems is assumed. 
● The Fire Detection system should be designed by a suitably qualified person with reference to the Local 

Regulations and Guidance from the fire Officer where applicable. 

 

Содержание ORION-EX V2

Страница 1: ...ices smoke and or heat detectors and call points per zone Active End of Line for Zone wiring monitoring 10uF 50V bipolar capacitor Programmable Pre Release and Extinguishing times Monitored inputs for...

Страница 2: ...EL Before connecting zones or sounder cables power up the control panel with the Active EOL connected to the zone inputs and the EOL resistors for the sounder output lines connected Then connect mains...

Страница 3: ...ote Input Manual Start extinguishing cycle CAP F ABORT Remote Input Manual Abort extinguishing cycle CAP G S1 Output Circuit S1 Active with Fire 10K RES H S2 EXT Output Circuit S2 Active during exting...

Страница 4: ...s LED used to indicate that the panel has features that have been disabled TEST This LED is active whenever panel is in TEST MODE activated in Engineering Mode Access Level 3 only SUPPLY Multi functio...

Страница 5: ...Z3F for fire detection and Z3X for extinguishing and fire detection Both Z3F and Z3X share the same status indicators in conjunction CONTROL KEYS These four keys can have more than one function They...

Страница 6: ...ones Z1 Z2 and Z3 F X 1 When switch is pressed associated LED will also be lit 2 Select the required ZONE by pressing consecutively the RED BUTTON 4 until the FAULT LED for the required ZONE is lit 3...

Страница 7: ...ilence Buzzer Silence Buzzer Confirm Disablement Disablements Confirm Delay Selection see delay config table RESET 2 insert user code Reset Panel Reset Panel LAMP TEST 3 insert user code Lamp Test Lam...

Страница 8: ...detector zone should be terminated in the relevant terminal blocks at the control panel and the cable screens connected to earth NOTE Zone 3F is independent from extinguishing cycle Upon activation b...

Страница 9: ...Global Fire Equipment globalfire pt ma_oexv2_01_010001_en_180730 POLARIZED DEVICES NON POLARIZED DEVICES RELAYS SOLENOIDS OR BELLS PYROTECHNIC ACTUATORS 9...

Страница 10: ...ne monitoring is achieved with a 4K7 resistor that mimics relay coil resistance therefore resistance should be removed after connecting relay NOTE Relay must have a 24V DC coil rating AUXILIARY INPUTS...

Страница 11: ...m This input has no effect on the panel outputs INS Extinguishing Immediate Activation This input starts the configured automatic extinguishing cycle ABORT Immediate Stopping of Extinguishing Cycle Th...

Страница 12: ...red these must be acknowledged by pressing the Buzzer Silence button to acknowledge each Fault or Fire event before code entry will be accepted LEVEL 3 Engineering Functions 4321 It is accessed from L...

Страница 13: ...ct batteries Observe correct polarity COMMISSIONING 1 If all is normal only the Green supply LED should be illuminated 2 If any Faults are indicated they should be corrected before proceeding 3 Initia...

Страница 14: ...ond to required day it s lit up Please refer to below table for additional details 3 Confirm the selection by pressing GREEN 1 key Upon confirmation the Red FIRE LED will be activated Remove selection...

Страница 15: ...PHICAL OVERVIEW Z1 Z2 ZONES Z1 ON OFF Z2 ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DELAYS TIMERS PRE RELEASE ON OFF RELEASE ON OFF Z3X ZONES Z3F Z3X ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DEL...

Страница 16: ...s timer elapses both S2 and RM outputs will be deactivated if programmed to do so Sounder Circuit 1 is silenced using Sound Resound Alarms button upon entering access level 2 After Sounder Circuit 1 i...

Страница 17: ...This type of fault will indicate that there is either a short or open circuit condition on zone circuit Revise wiring Supply Fault Associated with a low voltage below 20 V present at the input of the...

Страница 18: ...oard and interface are connected using the 5 way flat cable provided The cable is fitted with 2 polarized connectors of the Molex type For details about connection please refer to repeater installatio...

Страница 19: ...side of ORION EX V2 main board to MPX 5 way connection on GFE MPX SNDR V2 or GFE MPX REL V2 board ORION EX V2 GFE MPX SNDR V2 or GFE MPX REL V2 Connection to ORION EX Mini Repeater V2 or ADLI V2 Modul...

Страница 20: ...ING Active EOL 10uF 50V Bipolar Capacitor BS5839 DETECTOR REMOVAL COMPLIANT YES provided diodes are fitted to detector base DEVICES PER ZONE 32 maximum EN54 pt 2 ALARM RESISTANCE VALUE INPUTS 270 1000...

Страница 21: ..._01_010001_en_180730 GLOBAL FIRE EQUIPMENT S A S tio dos Barrab s Armaz m Nave Y Caixa Postal 908 Z 8150 016 S o Br s de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Suppo...

Отзывы: