STANDBY BATTERY CALCULATION 

 

Battery capacity

 

should be between 2 x 2.4 Ah 12V DC and 2 x 7 Ah 12V DC.

 

 
The battery Ah required for a given installation is calculated from the following formula: 
 

Quiescent current in 
mA of the panel with 

everything 
connected 

Standby time 

required in 

hours 

divided by 

1000 

Alarm 

current in 

Amps 

(sounder 

load) 

Alarm 

time in 

hours 

+  20% 

 
Round the result to the next available battery size. Quiescent current of the panel with everything is found by adding the

 

 

   

 

 

 

 

 

 

   

 

 

 

   

 

 

 

 

standby current of all connected devices to the standby current of the panel (38 mA). Consult the manual for the individual

 

     

 

   

 

 

   

 

 

 

 

 

 

 

 

 

 

devices to confirm the standby current. 
 

Repeater Interface Connection 

 
The interface board used to establish communication between the ORION-EX and its associated repeater(s) should be

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

linked to the connector labelled

DATA

, which is situated on the underside of the panel’s main board. The interface should be

   

 

 

 

 

   

   

 

   

 

 

 

 

 

 

   

fixed to the base of the back box as shown before. The panel’s main board and interface are connected using the 5-way flat

   

 

   

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cable provided. The cable is fitted with 2 polarized connectors of the Molex type. 
 
For details about connection, please refer to repeater installation manual. 
 

Modules Interface Connection 

 
The ORION-EX and its associated modules should be linked to the connector labelled

MPX

, which is situated on the

 

 

 

 

 

 

 

 

   

 

 

 

 

   

 

 

 

underside of the panel’s PCB board. The module should be fixed to the base of the back box as shown before. The panel’s

   

 

 

 

 

 

 

 

 

   

 

   

 

 

   

 

 

 

 

main board and module are connected using direct 5-way flat cable provided. The cable is fitted with 2 polarized connectors

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

   

 

 

of the Molex type. 
 
The following modules can be connected: 
 

GFE-MPX-REL V2

 for Relay activation extension 

GFE-MPX-SNDR V2 

for Sounder activations (Z1, Z2, Z3F, Z3X, etc) 

ADLI V2

 if a connection to a GFE Addressable panel is needed (DATA connector) 

 
GFE-MPX-SNDR V2 and GFE-MPX-REL V2 outputs will activate upon the ORION-EX panel actions shown in the table

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

below. 

 

ORION-EX 

Z1 

ALARM 

Z2 

ALARM 

Z3F 

ALARM 

Z3X 

ALARM 

S1 

Pre 

Release 

RM 

RM 

GFE-MPX-SNDR V2 

/ GFE-MPX-REL V2 

OUTPUTS 

S1 / 

REL1 

S2 / 

REL2 

S3 / REL3 

S4 / REL4 

S5 / REL5 

S6 / REL6 

(latching) 

S7 / REL7 

S8 / REL8 

 
 
For details about connection, please refer to specific module installation manual or contact authorized GFE distributor. 
 

 

18 

Содержание ORION-EX V2

Страница 1: ...ices smoke and or heat detectors and call points per zone Active End of Line for Zone wiring monitoring 10uF 50V bipolar capacitor Programmable Pre Release and Extinguishing times Monitored inputs for...

Страница 2: ...EL Before connecting zones or sounder cables power up the control panel with the Active EOL connected to the zone inputs and the EOL resistors for the sounder output lines connected Then connect mains...

Страница 3: ...ote Input Manual Start extinguishing cycle CAP F ABORT Remote Input Manual Abort extinguishing cycle CAP G S1 Output Circuit S1 Active with Fire 10K RES H S2 EXT Output Circuit S2 Active during exting...

Страница 4: ...s LED used to indicate that the panel has features that have been disabled TEST This LED is active whenever panel is in TEST MODE activated in Engineering Mode Access Level 3 only SUPPLY Multi functio...

Страница 5: ...Z3F for fire detection and Z3X for extinguishing and fire detection Both Z3F and Z3X share the same status indicators in conjunction CONTROL KEYS These four keys can have more than one function They...

Страница 6: ...ones Z1 Z2 and Z3 F X 1 When switch is pressed associated LED will also be lit 2 Select the required ZONE by pressing consecutively the RED BUTTON 4 until the FAULT LED for the required ZONE is lit 3...

Страница 7: ...ilence Buzzer Silence Buzzer Confirm Disablement Disablements Confirm Delay Selection see delay config table RESET 2 insert user code Reset Panel Reset Panel LAMP TEST 3 insert user code Lamp Test Lam...

Страница 8: ...detector zone should be terminated in the relevant terminal blocks at the control panel and the cable screens connected to earth NOTE Zone 3F is independent from extinguishing cycle Upon activation b...

Страница 9: ...Global Fire Equipment globalfire pt ma_oexv2_01_010001_en_180730 POLARIZED DEVICES NON POLARIZED DEVICES RELAYS SOLENOIDS OR BELLS PYROTECHNIC ACTUATORS 9...

Страница 10: ...ne monitoring is achieved with a 4K7 resistor that mimics relay coil resistance therefore resistance should be removed after connecting relay NOTE Relay must have a 24V DC coil rating AUXILIARY INPUTS...

Страница 11: ...m This input has no effect on the panel outputs INS Extinguishing Immediate Activation This input starts the configured automatic extinguishing cycle ABORT Immediate Stopping of Extinguishing Cycle Th...

Страница 12: ...red these must be acknowledged by pressing the Buzzer Silence button to acknowledge each Fault or Fire event before code entry will be accepted LEVEL 3 Engineering Functions 4321 It is accessed from L...

Страница 13: ...ct batteries Observe correct polarity COMMISSIONING 1 If all is normal only the Green supply LED should be illuminated 2 If any Faults are indicated they should be corrected before proceeding 3 Initia...

Страница 14: ...ond to required day it s lit up Please refer to below table for additional details 3 Confirm the selection by pressing GREEN 1 key Upon confirmation the Red FIRE LED will be activated Remove selection...

Страница 15: ...PHICAL OVERVIEW Z1 Z2 ZONES Z1 ON OFF Z2 ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DELAYS TIMERS PRE RELEASE ON OFF RELEASE ON OFF Z3X ZONES Z3F Z3X ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DEL...

Страница 16: ...s timer elapses both S2 and RM outputs will be deactivated if programmed to do so Sounder Circuit 1 is silenced using Sound Resound Alarms button upon entering access level 2 After Sounder Circuit 1 i...

Страница 17: ...This type of fault will indicate that there is either a short or open circuit condition on zone circuit Revise wiring Supply Fault Associated with a low voltage below 20 V present at the input of the...

Страница 18: ...oard and interface are connected using the 5 way flat cable provided The cable is fitted with 2 polarized connectors of the Molex type For details about connection please refer to repeater installatio...

Страница 19: ...side of ORION EX V2 main board to MPX 5 way connection on GFE MPX SNDR V2 or GFE MPX REL V2 board ORION EX V2 GFE MPX SNDR V2 or GFE MPX REL V2 Connection to ORION EX Mini Repeater V2 or ADLI V2 Modul...

Страница 20: ...ING Active EOL 10uF 50V Bipolar Capacitor BS5839 DETECTOR REMOVAL COMPLIANT YES provided diodes are fitted to detector base DEVICES PER ZONE 32 maximum EN54 pt 2 ALARM RESISTANCE VALUE INPUTS 270 1000...

Страница 21: ..._01_010001_en_180730 GLOBAL FIRE EQUIPMENT S A S tio dos Barrab s Armaz m Nave Y Caixa Postal 908 Z 8150 016 S o Br s de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Suppo...

Отзывы: