OPERATING AND PROGRAMMING THE PANEL
There are three access levels on the ORION-EX:
LEVEL 1 – General User Controls
● Perform LEDs and Buzzer test
● Silence Internal buzzer
● Put the panel into Access Level 2 or 3 using required access codes.
LEVEL 2 – Authorized user controls (2244) or Access Key
This level allows the user to:
● Silence and re/activate S1 sounder output
● Reset after an Alarm or Fault
● Manually activate the sounders (Evacuate function)
● Silence Internal Buzzer
● Disable/Enable: Outputs; Zones & Monitored Inputs; Activate & Abort Extinguishing Cycle.
NOTE:
When any zone or function is disabled, the Disabled LED on the STATUS area of the Control
Panel display will be lit together with the corresponding function or zone disablement LED. Disabled
zones will have their corresponding FAULT/DISABLED LED illuminated.
Level 2 Access is gained by entering the code
2244
using the numbered buttons. When in panel is in Level 2 the Green LED
will flash with a frequency of 1 Hz.
Each successful button press is indicated by the illumination in sequence of the top screen Fault LEDs. If the code is not
completed within 20 seconds of the last key press, the system reverts to Level 1.
NOTE:
If any Fire or Fault events have occurred these must be acknowledged
by pressing the Buzzer
Silence
button to acknowledge each Fault or Fire event
before code entry will be accepted.
LEVEL 3 – Engineering Functions (4321)
It is accessed from Level 1 and allows:
● One Man Test
● Panel Reset
● Set Extinguishing Pre-Release Delay and Extinguishing Timer.
NOTES:
1)
Changes made at this level affect the factory default settings and the operation of the system. They
should only be made by qualified personnel who are fully aware of their effects.
2)
If any Fire or Fault events have occurred, these must be acknowledged by pressing the Buzzer
Silence button to acknowledge each fault and Fire event before code entry will be accepted.
3)
When in Access Level 3, the occurrence of any Fire or Fault condition the system will automatically
exit from Level 3 and revert to Level 2.
To enter Engineering Mode (Access Level 3) enter the code 4321, using the numbered keys (from 1 to 4), which are
available on the top right-hand side of the control panel display. Each successful button press is indicated by the illumination
in sequence of the Fault LEDs for zones 3, 4, 5 and 6. If the code is not completed within 20 seconds of the last key press,
the system reverts to Level 1.
Once this mode is entered the Green LED (SUPPLY) will flash once every 0,5 seconds.
To exit this mode at any time, press the RESET button. The panel will revert to Access Level 1.
Total removal of power during the programming phase could cause changes not to be saved.