PANEL STATUS INDICATORS & CONTROLS 

 

 

 

 
STATUS 

 

FIRE 

– LED used to indicate any FIRE ALARM condition present on panel. 

 

FAULT

 – LED used to indicate any Fault condition present on panel. If there is a communication Fault between ORION-EX 

and an ORION MINI REP or a Sounder / Relay module, this LED will flash at a rate of once per second. 
 

DISABLED

 – Disabled Status LED used to indicate that the panel has features that have been disabled.  

 

TEST

 – This LED is active whenever panel is in TEST MODE, activated in Engineering Mode Access Level 3 only. 

 

SUPPLY

 - Multi function indicator used to indicate the presence of supply. When in Access Level 1 this 

LED is permanently lit. If in Access Level 2 (USER CODE 2244) this LED will flash at a rate of once per second. 
If in Access Level 3 mode (ENGINEERING CODE 4321) this LED will flash faster at a rate of once every 0,5 seconds. 
 

SYSTEM FAULT

 – This LED will be lit whenever there is a processor failure or corruption of the panel firmware. 

 

 

 

Содержание ORION-EX V2

Страница 1: ...ices smoke and or heat detectors and call points per zone Active End of Line for Zone wiring monitoring 10uF 50V bipolar capacitor Programmable Pre Release and Extinguishing times Monitored inputs for...

Страница 2: ...EL Before connecting zones or sounder cables power up the control panel with the Active EOL connected to the zone inputs and the EOL resistors for the sounder output lines connected Then connect mains...

Страница 3: ...ote Input Manual Start extinguishing cycle CAP F ABORT Remote Input Manual Abort extinguishing cycle CAP G S1 Output Circuit S1 Active with Fire 10K RES H S2 EXT Output Circuit S2 Active during exting...

Страница 4: ...s LED used to indicate that the panel has features that have been disabled TEST This LED is active whenever panel is in TEST MODE activated in Engineering Mode Access Level 3 only SUPPLY Multi functio...

Страница 5: ...Z3F for fire detection and Z3X for extinguishing and fire detection Both Z3F and Z3X share the same status indicators in conjunction CONTROL KEYS These four keys can have more than one function They...

Страница 6: ...ones Z1 Z2 and Z3 F X 1 When switch is pressed associated LED will also be lit 2 Select the required ZONE by pressing consecutively the RED BUTTON 4 until the FAULT LED for the required ZONE is lit 3...

Страница 7: ...ilence Buzzer Silence Buzzer Confirm Disablement Disablements Confirm Delay Selection see delay config table RESET 2 insert user code Reset Panel Reset Panel LAMP TEST 3 insert user code Lamp Test Lam...

Страница 8: ...detector zone should be terminated in the relevant terminal blocks at the control panel and the cable screens connected to earth NOTE Zone 3F is independent from extinguishing cycle Upon activation b...

Страница 9: ...Global Fire Equipment globalfire pt ma_oexv2_01_010001_en_180730 POLARIZED DEVICES NON POLARIZED DEVICES RELAYS SOLENOIDS OR BELLS PYROTECHNIC ACTUATORS 9...

Страница 10: ...ne monitoring is achieved with a 4K7 resistor that mimics relay coil resistance therefore resistance should be removed after connecting relay NOTE Relay must have a 24V DC coil rating AUXILIARY INPUTS...

Страница 11: ...m This input has no effect on the panel outputs INS Extinguishing Immediate Activation This input starts the configured automatic extinguishing cycle ABORT Immediate Stopping of Extinguishing Cycle Th...

Страница 12: ...red these must be acknowledged by pressing the Buzzer Silence button to acknowledge each Fault or Fire event before code entry will be accepted LEVEL 3 Engineering Functions 4321 It is accessed from L...

Страница 13: ...ct batteries Observe correct polarity COMMISSIONING 1 If all is normal only the Green supply LED should be illuminated 2 If any Faults are indicated they should be corrected before proceeding 3 Initia...

Страница 14: ...ond to required day it s lit up Please refer to below table for additional details 3 Confirm the selection by pressing GREEN 1 key Upon confirmation the Red FIRE LED will be activated Remove selection...

Страница 15: ...PHICAL OVERVIEW Z1 Z2 ZONES Z1 ON OFF Z2 ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DELAYS TIMERS PRE RELEASE ON OFF RELEASE ON OFF Z3X ZONES Z3F Z3X ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DEL...

Страница 16: ...s timer elapses both S2 and RM outputs will be deactivated if programmed to do so Sounder Circuit 1 is silenced using Sound Resound Alarms button upon entering access level 2 After Sounder Circuit 1 i...

Страница 17: ...This type of fault will indicate that there is either a short or open circuit condition on zone circuit Revise wiring Supply Fault Associated with a low voltage below 20 V present at the input of the...

Страница 18: ...oard and interface are connected using the 5 way flat cable provided The cable is fitted with 2 polarized connectors of the Molex type For details about connection please refer to repeater installatio...

Страница 19: ...side of ORION EX V2 main board to MPX 5 way connection on GFE MPX SNDR V2 or GFE MPX REL V2 board ORION EX V2 GFE MPX SNDR V2 or GFE MPX REL V2 Connection to ORION EX Mini Repeater V2 or ADLI V2 Modul...

Страница 20: ...ING Active EOL 10uF 50V Bipolar Capacitor BS5839 DETECTOR REMOVAL COMPLIANT YES provided diodes are fitted to detector base DEVICES PER ZONE 32 maximum EN54 pt 2 ALARM RESISTANCE VALUE INPUTS 270 1000...

Страница 21: ..._01_010001_en_180730 GLOBAL FIRE EQUIPMENT S A S tio dos Barrab s Armaz m Nave Y Caixa Postal 908 Z 8150 016 S o Br s de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Suppo...

Отзывы:

Похожие инструкции для ORION-EX V2