INPUTS – Monitored
All below inputs require an active EOL to monitor the status of the lines. Faults are signaled via the associated Yellow LED.
Activation of this inputs is accomplished by using a normally open (NO) voltage free contact in series with a resistor with a
value in the range 470 to 1000 Ohms. This is already included in some devices like GFE’s MCPE-C call points. The Red
LED is activated when the contact is closed.
EV – Electrovalve:
This input is used to monitor and signal status of the
SOLENOID valve associated with the extinguishing system. This input has no
effect on the panel outputs.
PST – Pressure Switch:
This input is used to monitor and signal the status
of the PRESSURE/FLOW SWITCH associated with the extinguishing system.
This input has no effect on the panel outputs.
INS – Extinguishing Immediate Activation:
This input starts the configured automatic extinguishing cycle.
ABORT – Immediate Stopping of Extinguishing Cycle:
This input stops the extinguishing cycle, normally via a coloured
call point connected directly to input.
OUTPUTS – Monitored
AUXILIARY SUPPLY OUTPUT
–
28V DC max 300 mA, short circuit protected, supervised.
The output is protected against short circuit by an electronic fuse which resets when the fault is cleared and
the panel is reset.
RM
– Monitored Remote Extinguishing “Open Collector” Output.
Maximum current is 100 mA.
OUTPUTS – Non Monitored
FIRE Relay –
Provide Fire signal to external devices.
Changeover contact rating: 30V DC / 2 A. Active until Reset.
FLT Relay –
Provide normally closed Fault signal to external devices.
Relay contact rating: 30V DC / 2 A. max resistive. Also Active for microprocessor fault. Active until
reset and all faults are cleared. Relay contact will open when any fault is present on the system.