FUNCTIONAL DESCRIPTION
Based on presented in graphical timeline, when both zones 1 and 2 are in Fire condition, the pre-extinguishing delay is
initiated, if previously programmed. Also if zone 3X is activated the pre-extinguishing delay is also initiated, if previously
programmed.
●
S1
output is activated immediately with each zone activation (including Z3F an Z3X).
●
S2
and
RM
outputs will be active for the duration of the programmed time but only after the pre-extinguishing delay
has elapsed (after Z1 & Z2 or Z3X).
●
S1
output can be silenced using Sound/ Resound Alarms button.
NOTE:
If no extinguishing delay has been programmed (default), S2 output and output RM will
activate immediately for the duration of the programmed extinguishing cycle (default condition is
activation until panel reset).
When this timer elapses, both
S2
and
RM
outputs will be deactivated (if programmed to do so).
Sounder Circuit 1 is silenced using Sound / Resound Alarms button upon entering access level 2. After Sounder Circuit 1 is
silenced, the LED associated with the Sound / Resound Alarms button will be OFF.
FIRE LEDs for zone 1 and 2 will be active. With each fire activation the Sounders Red LED is activated.
When the extinguishing discharge is active, both EXTINGUISHING and REMOTE O/P Red LEDs will be lit.
EXTINGUISHING CYCLE - MANUAL
MANUAL – INS Input
Upon activation of this input, normally via a dedicated coloured call point, extinguishing cycle process starts in the same way
as if both zones Z1 & Z2 or Z3X have been activated.
●
S1
output is activated immediately.
S1
output can be silenced using SOUNDERS ACTIVATE/SILENCE button.
●
S2
and
RM
outputs will be active for the duration of the programmed time but only after the pre-extinguishing delay
has elapsed.
MANUAL – Panel
The extinguishing process can be controlled manually using the buttons available on the panel’s front display.