PROGRAMMABLE OPTIONS
The ORION-EX has a number of programmable options to help the engineer customize the system to meet
the customer's
requirements. To access these options it is necessary to enter Access Level 3.
ONE MAN TEST
After entering Engineering Mode (Access Level 3) press the LAMP TEST button. Release button and the TEST LED will be
on along with the fault LED for all zones that are available for testing indicating that the panel is in TEST mode.
Zones that are in Fault or are Disabled will not have their LED illuminated.
Test the zones accordingly with installation requirements. At each zone activation, the corresponding zone FIRE LED will
light up for 5 seconds.
Zones will automatically reset after 10 seconds. Internal Buzzer and SOUNDERS will operate for 1 second.
To end TEST mode press LAMP TEST button.
To exit Engineering Mode (Access Level 3), press the RESET button.
PRE-RELEASE DELAY
1. After accessing Level 3, press
ACTIVATE EXTINGUISHING
switch. The associated LED will be activated.
2. Select the required time delay by pressing the Red switch (4) consecutively until one of the LEDs that correspond to
required day it’s lit up.
Please refer to below table for additional details
.
3. Confirm the selection by pressing GREEN (1) key. Upon confirmation the Red (FIRE) LED will be activated. Remove
selection by pressing the GREEN key again. The corresponding LED will be switched OFF.
4. To exit the function press
ACTIVATE EXTINGUISHING
switch.
When accessing Pre-Release delay configuration mode, if a delay was already programed, the Red LED associated with the
programmed delay will be shown.
EXTINGUISHING TIMER
1. After accessing Level 3, press
ZONES
switch. The associated LED will be activated.
2. Select the required time delay by pressing the Red switch (4) consecutively until one of the LEDs that correspond to
required time it’s lit up.
Please refer to below table for additional details
.
3. Confirm the selection by pressing GREEN (1) key. Upon confirmation the Red (FIRE) LED will be activated. Remove
selection by pressing the GREEN key again. The corresponding LED will be switched OFF.
4. To exit the function press
ZONES
switch.
When accessing Extinguishing Timer configuration mode, if a delay was already programed, the Red LED associated with
the programmed delay will be shown.
Delay Configuration Table
Active LEDs
during setup
ALL LEDS
OFF
Z1
Z2
Z3
EV
PS
REL
EXT
REM
Corresponding
Delay in seconds
Immediate
(Pre-release)
Active until Reset
(Extinguishing)
15
30
45
60
90
120
150
180
14