background image

 

 

 

 

  Operating Instructions 

MEW01457 

Revision - 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fire Alarm System EBL512 

V2.7.x 

 

Author: 

Jan Pettersson 

Date of issue: 2012-04-05 

Date of rev: 

 

Содержание EBL512

Страница 1: ...Operating Instructions MEW01457 Revision Fire Alarm System EBL512 V2 7 x Author Jan Pettersson Date of issue 2012 04 05 Date of rev ...

Страница 2: ...This page has deliberately been left blank ...

Страница 3: ...y unit DU __________________________________ 9 2 7 COM loop ________________________________________ 9 2 8 BS4 loop ________________________________________ 10 2 9 Control Unit C U C I E __________________________ 10 2 10 Fire Brigade Panel FBP ___________________________ 10 2 11 Control panel CP ________________________________ 10 2 12 System__________________________________________ 10 2 13 Netw...

Страница 4: ...larm devices _____________________ 28 8 1 Silence alarm devices inside switch __________________ 28 8 2 New Zealand FB Silence switch outside switch _________ 29 9 Disable Re enable alarm devices_____________ 30 10 Silence buzzer ___________________________ 31 10 1 Buzzer __________________________________________ 32 11 Disable Re enable all control extinguishing and ventilation outputs___________...

Страница 5: ..._____ 53 16 4 Key cabinet alarm reset_____________________________ 53 16 5 Quiet alarm reset __________________________________ 53 16 6 Alarm Acknowledgement Facility AAF reset __________ 53 16 7 Acknowledged alarm ______________________________ 54 16 8 Isolated alarm ____________________________________ 54 17 Fault _____________________________________ 55 17 1 Fault messages _____________________...

Страница 6: ...s on display and printer H4 110 27 1 Disablement H4 U1 _____________________________ 110 27 2 Disablement by time channel H4 U2 ________________ 111 27 3 Doors open H4 U3 ______________________________ 112 27 4 Activated 2 zone address dependent zone address H4 U4 113 27 5 Sensor values H4 U5 ____________________________ 114 27 5 1 Reset of a week average sensor value _____________ 116 27 5 2 Algo...

Страница 7: ...________ 149 31 10 Activate address in alarm mode H8 S9 ____________ 150 31 11 Synchronize the control units H8 S10 _____________ 152 31 12 Change access code for maintenance H8 S11 _______ 154 32 Interlocking outputs and inputs H9 _________ 155 32 1 Activated interlocking outputs inputs H9 C1 __________ 155 32 2 Activate interlocking output H9 C2 _________________ 156 32 3 Reset interlocking outp...

Страница 8: ...Panasonic Eco Solutions Nordic AB MEW01457 Rev Operating Instructions Fire alarm system EBL512 V2 7 x 6 ...

Страница 9: ...Product Parts List A product has a type number e g 1548 an article number often the type no and sometimes is a country code added e g 1548SE a product name e g EBL512 control unit 128 addresses without printer HW A HW e g a printed circuit board has a type number e g 1556 an article number often the type no and sometimes is a country code added e g 1556SE a product name e g Main Board 128 addr a p...

Страница 10: ...L switch in the ASB see below is used for address setting for detectors 2xxx An analog detector has to be plugged in an analog sensor base ASB 2 2 4 Analog Sensor Base ASB A sensor is plugged in an ASB which is connected to a COM loop see below Old installations Analog sensor base types 2xxx have a DIL switch for the COM loop address setting 2 2 5 Conventional detector Detector with only two statu...

Страница 11: ...End of line resistor in the last alarm point 2 2 11 ADB input Addressable zone interface Old installations Ext line conventional zone line intended for one or more conventional alarm points End of line resistor in the last alarm point 2 3 Output unit Addressable unit with programmable control outputs Connected to a COM loop see below 2 4 Output Control output Defined or programmable function Relay...

Страница 12: ...tc to communicate with the control unit system 2 12 System Several control units connected via a TLON network co operating control units 2 13 Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater Brief explanations to the words expressions to be found in connection with a network See also separate TLON Technical description TLON TeleLarm Local Operating Ne...

Страница 13: ...s and backlight 2 17 Door open Door Key switch In EBL512 there is a door switch which is activated when the control unit door is open In some other units this door switch is replaced with a key switch The LED Door open is indicating door open key switch in position open 2 18 Site Specific Data SSD The SSD is unique for each installation All alarm points presentation numbers user definable text mes...

Страница 14: ... 1582 External FBP interface board4 1583 German FBP interface board5 1584 Autronica interface board four BS4 loops 6 1587 External FBP DU interface board4 Regarding the expansion boards see also the EBL512 Planning Instructions and drawings 3 1 2 Printer Control unit 1549 is equipped with a printer In control unit 1548 it is possible to mount a Printer 1558 In Ext Fire Brigade Panel 1826 it is pos...

Страница 15: ...2 G3 United version 2 7 x 3 3 Documents The following documents are available Operating instructions this document Planning instructions Drawings e g connection diagrams Normally information that is found in one document is not to be found in another document i e the documents complement each other 3 4 Applications The EBL512 system is intended for small medium and large installations The intellig...

Страница 16: ...xed system WinG3 version 1 1 x has to be used to download S W Win512 shall have the same version number as the EBL512 S W version number regarding the two first digits e g 2 7 x and 2 7 x respectively Backup require the same version number in Win512 and EBL512 Old SSD files can be opened and saved in a higher version of Win512 and thereafter downloaded 3 5 2 TLON Manager TLON Manager is used for t...

Страница 17: ...et Depending on country convention configuration etc the look language and functions might vary as well as the max number of loop units addresses The door has a Plexiglas ahead of the FBP part see Figure 1 To open the door access level 1 a key is required supplied When the door is open you fully see the front the Fire Brigade Panel FBP and Control Panel CP see Figure 2 page 16 To open the inner do...

Страница 18: ...ch alarm point zone s having generated fire alarm In the display LCD 2x40 alphanumeric characters the information displayed on the first row is depending on how many alarm points zones having generated fire alarm and also convention On the second row is for an alarm point or a zone a user definable text message alarm text shown if programmed The CP is to communicate with the system i e for commiss...

Страница 19: ...extinguishing 9 L4 Ventilation yellow Output s for fire smoke ventilation equipment activated Activated fire ventilation 9 L5 Fire brigade tx red Output for fire brigade tx routing equipment and or corresponding programmable output s i e type 4 routing equipment activated 9 Test of routing equipment in progress see menu H1 L6 Operation green The c i e is powered via the rectifier or the battery FB...

Страница 20: ...dividually reset Single encapsulated reset Fire alarm reset is like Single reset Encapsulation function is described in EBL512 Planning Instructions chapter System properties settings Encapsulated unit zone disabled unit zone NOTE 1 When Multiple reset or Single reset is used encapsulated reset can be done by pressing Reset P4 and 0 1 sec later also press Alarms queued P1 and hold them pressed for...

Страница 21: ...e generated fault s 16 L14 System fault yellow EBL512 is not running because of S W CPU memory fault L15 Fault Disablements Fire brigade tx yellow Output s for fire brigade tx routing equipment is are disabled via menu H8 S1 or H2 B3 or via an open door 15 Blinking Routing equipment power supply output17 or one or more supervised outputs type 4 routing equipment have generated fault s 18 L16 Fire ...

Страница 22: ...via an access code to carry out disablements etc In conjunction with fire alarm some information is available and some actions are possible to perform via the Fire alarm menu X1 X9 without log on see chapter Fire alarm page 41 P9 Return white Used to stop input of data leave a menu one step up and to log off 1 9 and 0 Numeric keys for the figures 0 9 C Used to clear delete just written data A Used...

Страница 23: ...nt state show the information below The exact look is dependent on the convention language YYYY MM DD EBL512 CU XX hh mm ss User programmable information text Top first row21 YYYY Year 2009 MM Month e g 02 February DD Day e g 28 CU XX Control Unit XX 00 29 hh hours e g 21 mm minutes e g 45 ss seconds e g 45 Bottom second row The information on the bottom row 40 characters can be created via Win512...

Страница 24: ...n only valid in some conventions 25 7 Faults not acknowledged 8 Disablements 9 Zones in Test mode 10 Interlocking in outputs active 22 In the Australian and New Zealand conventions the LCD backlight will not be turned OFF even if the c i e is powered only by the second power source 23 In the New Zealand convention also Acknowledged alarms ACK and Isolated alarms ISO NOTE A Fire alarm has a log off...

Страница 25: ... 3 or 4 Building occupier Installation handling daily duties e g monthly tests dis ablements etc 3 Fire brigade key Access code for level 3 or 4 Service maintenance personnel Service maintenance 4 Fire brigade key Access code for level 4 Service maintenance commissioning engineer Service maintenance commissioning the system 5 PC Win512 connected PC access code for level 5 Service commissioning eng...

Страница 26: ... brigade personnel has access to the push buttons keypad to P2 Silence the buzzer in the c i e EBL512 P3 Silence the alarm devices sounders in the system P4 Reset fire alarm s P5 Evacuate i e turn on the sounders 14 P7 Paper feed when a built in printer is available P8 Get access after logon to level 2 4 i e menus functions in the system NOTE In conjunction with a fire alarm the fire brigade perso...

Страница 27: ...off H3 Set calendar and clock H4 Present system status on display and printer U1 Disablement U2 Disablement by time channel U3 Show open doors 26 U4 Activated 2 zone address dependent zone address U5 Show sensor values U6 Sensors activating service signal U7 Show event log U8 Show configuration H6 Acknowledge faults H7 Perform zone test Test mode H9 Interlocking outputs and inputs C1 Activated int...

Страница 28: ...tenance S1 Disable or re enable outputs for routing equipment Fire brigade tx Fault tx S2 Disconnect loop S3 Re connect loop S4 Acknowledge service signal S5 Clear weekly average S6 De activate alert annunciation function S7 Test alarm devices S8 Safe shut down of control unit S9 Activate address in alarm mode S10 Synchronize the control units S11 Change access code for maintenance access level 3 ...

Страница 29: ...mption in control unit A6 Display current consumption on COM BS4 loop A7 Display statistics for COM loop A8 Select unit on COM loop and BS4 loop to use for trigging A9 Activate address setting mode for DU A10 Change access code for PC communication access level 5 A11 Change access code for service access level 4 7 6 Access level 5 Used by Service Commissioning Engineers when a PC shall be connecte...

Страница 30: ...nce alarm 8 1 Silence alarm devices inside switch NOTE The functions in this chapter are valid for the New Zealand convention only The button Silence alarm devices P3 is called the inside switch and has the following function The inside switch toggles between two states Alarm devices disabled All programmable outputs of type Alarm devices are disabled i e they cannot be activated Alarm devices not...

Страница 31: ...anges from blinking to steady continuous 31 The c i e built in buzzer is silenced A fault is generated32 FAULT FB Silence switch active The outside switch is turned OFF i e from activated to not activated state The fault FAULT FB Silence switch active will be Serviced 33 Any alarm point zone in fire alarm state will automatically be disabled isolated I e it has to be re enabled via menu H2 B5 Any ...

Страница 32: ...can via menu H2 B9 be collectively disabled for one more or all control units This is indicated by LED Disablements L8 and LED Fault Disablements Alarm devices L13 steady ON In case of a fire the sounders will remain disabled i e the alarm devices will not sound They will remain disabled until they are re enabled again via menu H2 B9 See also chapter Disable Re enable alarm devices H2 B9 page 107 ...

Страница 33: ...g box can the function Silence Buzzer by Door Switch be selected The buzzer will then be turned off as long as the control unit door is open This function is a violation to the EN54 2 standard Old front For the function described above the new front with the push button Silence buzzer P2 is required The discontinued front without the push button Silence buzzer results in the following function The...

Страница 34: ...or disablement will be shown in the LCD but more faults and or disablements will be indicated by the word more NOTE In the New Zealand convention if any of the outputs for routing equipment Fire brigade tx and Fault tx is disabled when the door to EBL512 is being closed the EBL512 built in buzzer will give a 2 seconds beep directly after the door is closed Routing equipment left isolated will be s...

Страница 35: ...ontrol general 1 fire ventilation 2 extinguishing system37 can via menu H2 B8 be collective disabled for one more or all control units This is indicated by LED Disablements L8 They will remain disabled until they are re enabled again via menu H2 B8 See also chapter Disable Re enable all control exting and ventilation outputs H2 B8 page 106 37 Also the Extinguish equipment output on the German FBP ...

Страница 36: ... progress The sounders will remain ON until they are turned OFF by pressing the push button Evacuate P5 again NOTE The alarm devices sounders will in this case be activated steady continuous irrespective of the fact that the outputs can be set to something else for fire alarm e g intermittent 12 2 LED Test When the push button LED Test P5 is pressed all LEDs on the front the LCD back light and all...

Страница 37: ... a C U is indicated by LED Door open in that C U and all ext FBPs connected to that C U Door open in an ext FBP is indicated by LED Door open in the C U it is connected to and all ext FBPs connected to that C U Door in control unit Door open in a C U is indicated by LED Door open in that C U and in all ext FBPs connected to that C U Door open in an ext FBP is indicated by LED Door open in that ext...

Страница 38: ...nits The technical number NNNNNN is used when programming all units connected to the COM loops Technical number is also used to identify which unit has generated a fault 001 127 The technical address on the COM loop The addresses don t have to be in sequence The connections on the COM loop don t have to be in sequence The address is for each unit set with the programming tool 3314 ...

Страница 39: ...me old units see dwg 512 71 Regarding the address 000 Address 000 cannot be set with the Address setting tool 3314 i e only addresses 001 127 can be used A brand new detector has the address 000 factory set Connected on the COM loop the LED will start blinking every second as information that an address has to be set before the detector will work ...

Страница 40: ...s also used to identify which unit has generated a fault NOTE In the technical number for unit connected to a BS4 loop the board number 4 Autronica interface board 0 the board number 5 Autronica interface board 1 the board number 6 Autronica interface board 2 and the board number 7 Autronica interface board 3 in the control unit In fault messages for the Autronica interface boards the following in...

Страница 41: ...can be displayed if programmed NOTE 1 Zone numbers 001 999 can be used but more than 512 alarm points or zones per c i e is a violation to the EN54 2 standard NOTE 2 When the function Redundancy in distributed system is used it is presented as 999 xx The zone number 999 is indicating that it is an alarm from a Control Unit and the address xx is indicating from which CU xx xx could be an individual...

Страница 42: ...nd or zones Zone numbers 001 999 can be used and in each zone the alarm point address numbers 01 99 can be used The fire alarms will be shown in the EBL512 display LCD and in Ext FBP 1826 1828 Alert Annunciation unit 1735 1736 and Ext Presentation unit 1728 Regarding the different alarm types etc see the following chapters 15 1 Pre warning Activation of Pre warning is an option that has to be enab...

Страница 43: ...er Alarm reset page 51 15 2 Fire alarm The system can handle up to 15360 fire alarms Up to 512 fire alarms will be shown in the c i e display No more fire alarms will be shown until one or more of the 512 alarms are reset See also chapter Alphanumeric display LCD in EBL512 page 21 Regarding POINT 999 nn nn 00 29 99 see NOTE at the end of this chapter According to the EN54 2 standard45 in case of a...

Страница 44: ...ess that has activated fire alarm No The total number of zones where fire alarm is activated User definable text message alarm text For an alarm point it is the individual free text for the alarm point if programmed or the default control unit text if programmed 47 Plus Alert Annunciation and Ext Presentation units In the old ext FBPs 2425 2426 and 2428 only the ten first fire alarms will be displ...

Страница 45: ...T 999 nn and POINT 999 99 Zone number 999 could indicate that the alarm is activated by one or more control units in the system In this case nn 00 29 is indicating a single slave unit and nn 99 is indicating several slave units connected in parallel Normally the user definable text message alarm text on the second row will indicate if it is a normal alarm point or a slave unit units For more infor...

Страница 46: ...vated which could be a nuisance alarm If a fire alarm type A is received it is probably a real fire since fire alarm is then activated from Two or more analog addressable smoke heat or multi detectors Any manual call point Any zone line input Any programmable input with the trigger condition General Fire 15 2 2 Fire alarm menu X1 X7 The special fire alarm menus X1 X7 can only be used if at least o...

Страница 47: ...89 No 003 Display faults ACCEPT X2 Press A E g ZONE 123 LAST 789 No 003 FAULT Battery not connected CU xx Only the fault message for the fault respectively is displayed here not date time and status information 15 2 2 3 Display disablements X3 ZONE 123 LAST 789 No 003 Display disablements ACCEPT X3 Press A E g ZONE 123 LAST 789 No 003 Zone XXX address XX disabled 15 2 2 4 Disable zone X4 ZONE 123 ...

Страница 48: ... For more information see chapter Disable Re enable alarm devices H2 B9 page 107 15 2 3 Alert Annunciation AA alarm When the AA function is enabled indicated by the LED Fire brigade tx delay L16 the indications print outs actions etc are as for a normal fire alarm except the c i e output for routing equipment fire brigade tx will not be activated The AA alarm has to be acknowledged within an ackno...

Страница 49: ...arm point is no longer in alarm status see chapter Alarm reset page 51 The function 2 zone address dependence can be turned on off via a time channel 15 3 Heavy smoke alarm Heavy heat alarm An analog detector generates heavy smoke heat alarm for a higher alarm level55 than the fire alarm level i e fire alarm is already activated by the same detector Heavy smoke heat alarm is a confirmation on that...

Страница 50: ...ee below 15 4 1 Key cabinet opened before a fire alarm If the key cabinet is opened before a fire alarm e g if somebody illegally breaks into the key cabinet a key cabinet alarm i e a fire alarm will be generated Example Key cabinet alarm xx control unit number POINT KEY xx No 001 Alarm from key cabinet It will be printed like a normal fire alarm when printer is available see chapter Fire alarm pa...

Страница 51: ...y cabinet fault can be generated again 15 5 Alarm Acknowledgement Facility AAF One or more Alarm Acknowledgement Facility Controls59 are used in the system During the Acknowledgement Period 10 60 sec there is an indication in the c i e display AAF zone zz activated During the Investigation Period 0 3 min there is an indication in the c i e display AAF zone zz investigation in progress See EBL512 P...

Страница 52: ...he buzzer sounds 0 8 5 sec and there is a Quiet alarm presentation in the display Quiet alarm detector ZZZ AA user definable text message Programmable outputs for quiet alarm e g 3361 outputs controlling supply air fans and standard fans i e any output with a control expression containing the trigger conditions no 42 Quiet Alarm Zone or no 43 Quiet Alarm Zone Address ...

Страница 53: ...0 5 sec When all fire alarms are reset LEDs Fire L1 and Alarms queued L2 are turned OFF and the display is empty 60 All outputs for fire alarm have also been reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet al...

Страница 54: ...t will not activate a new fire alarm within 20 seconds It has to be re enabled via menu H2 B5 before it can activate a new fire alarm This function set in Win512 is a violation to the EN54 2 standard LED Disablements L8 is indicating one or more disablements in the system NOTE When Multi reset or Single reset is used encapsulated reset can be done by pressing Reset P4 and 0 1 sec later also press ...

Страница 55: ...status information Serviced is added This key cabinet fault message is to be acknowledged the same way as a normal fault see chapter Fault acknowledge page 76 When the key cabinet fault is acknowledged the LED General fault L7 will be turned OFF if the key cabinet is closed and if there are no other faults in the system 16 5 Quiet alarm reset Quiet alarms are non latching i e they will be automati...

Страница 56: ...M or an acknowledged alarm ACK presented in the LCD can be isolated as follows When the New Zealand FB Silence switch outside switch is turned OFF from activated to not activated any fire alarm and acknowledged alarm will be isolated disabled 62 Isolated alarms are indicated in the fire alarm list in the LCD by ISO in front of the alarm respectively see page 44 Isolated alarms do not activate any ...

Страница 57: ...ult message FAULT No reply techn no xxxxxx Date MM DD Time HH MM If more than one fault is activated the text More faults is added after the time If a fault has been corrected before it has been acknowledged the status text Serviced is added after the time 65 Fire alarm presentation has higher priority than the fault messages During fire alarm presentation the faults can be shown via the special f...

Страница 58: ...d Check programming Win512 FAULT 1581 Relay board x CU xx 8 relays expansion board Fault on no communication to 1581 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 1582 FBP interface board x CU xx External Fire Brigade Panel interface board Fault on no communication to 1582 board No x in control unit No xx Check address setting an...

Страница 59: ...2 FAULT 24 V for ext equipment CU xx Check the fuses F2 and F4 on the connection board 1555 Supervised output S2 is also supplied via F2 and F4 FAULT 24 V for routing equipment CU xx 512 Check the fuses F1 and F3 on the connection board 1555 Supervised output S3 is in some conventions configurations supplied via F1 and F3 Indicated by LED L15 blinking 512 G3 Check the fuse F8 Output 0 on the 512 G...

Страница 60: ...ine input Input 0 on the 3361 unit with technical number xxxxxx is used for a single slave unit control unit or several slave units connected in parallel i e the unit is used for Redundancy in distributed system The Input 0 is in fire alarm state but there is no activated fire alarm in any control unit and no fault on the TLON Network Check the connections e g of the alarm resistor in the slave un...

Страница 61: ...ced FAULT Charging ext power supply CU xx The fault is to be found in the external power supply equipment FAULT Charging output unit xxxxxx The charging function in the external power supply unit is not OK The p c b has to be replaced FAULT Checksum system program CU xx A fault in the control unit xx S W The main board 1556 might have to be replaced This is a very serious fault Call for service pe...

Страница 62: ... program memory fault in the EPU there will be a fault message in the EPU display Memory fault in program area n n 1 or 2 The EPU will not work FAULT Comm EPU xx CU xx EPU 1728 The contact with the EPU is interrupted Check the cable and all connections Is correct complete SSD downloaded via Win512 Check the address setting SW mode setting etc If there is a program memory fault in the EPU there wil...

Страница 63: ...wer supply to the control unit FAULT CU xx has wrong information Can be shown in conjunction with new S W download and or when commissioning a system One or more control units might have data stored that is not the same in all control units If a control unit restarts in conjunction with this fault a synchronization will start automatically otherwise a synchronization has to be started via menu H8 ...

Страница 64: ...ating a break cut off or a missing end of line resistor on input x zone line on the 1580 board placed in control unit xx It can also be a detector that has been removed stolen from its base NOTE The input can as an alternative be used for a single slave unit control unit or several control units connected in parallel i e it is used for Redundancy in distributed system In such a case the output for...

Страница 65: ...ute is an attempt to comm in one direction made again FAULT Display unit xxxxxx Display unit out of work Fault in the display unit EEPROM site specific data Download the data again or change the EEPROM and download the data again FAULT Double addresses techn no xxxxxx Two or more units connected to a BS4 loop 1584 board have been given the same address Check the units FAULT Earth fault plus CU xx ...

Страница 66: ... be replaced FAULT Expansion board x loop x CU xx This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx There is some internal fault on the board FAULT External FBP x board x CU xx The control unit i e the 1582 board cannot communicate with the ext FBP or data converter Check the connections Check the cable break Check the address DIL Switch in the ext ...

Страница 67: ... outside switch is turned ON i e from not activated to activated state FAULT FBP xx 1587 board x CU xx FBP 1826 1828 The unit is programmed as another type of unit than the SSD says or fault in the unit FAULT FBP xx CU xx FBP 1826 1828 The unit is programmed as another type of unit than the SSD says or fault in the unit FAULT Fuse 1580 8 zones board x CU xx DET8 1580 8 zones expansion board Check ...

Страница 68: ...4 x CU xx Autronica interface board BS4 The current consumption is 60 mA on the BS4 loop FAULT High Voltage 1584 board x CU xx Autronica interface board BS4 The BS4 loop voltage is 16V normally it is 14V 0 1V FAULT ID fault display unit xxxxxx The display unit is not the same type as programmed Change the programming or the unit FAULT Interlocking input AAA PP An interlocking input is not activate...

Страница 69: ...unit is out of order faulty FAULT Low battery capacity CU xx Battery internal resistance is too high The check is performed every 12th hour The battery might be too old Cables fuses etc for externally placed batteries might cause a voltage drop Check adjust the rectifier power supply voltage 24 V DC Check the charging voltage over the battery respectively 13 5 13 8 depending on the actual charging...

Страница 70: ...FAULT Mains control unit xx The fault is activated 1 300 minutes66 after Loss of mains i e no 230 V AC Blown fuse 230 V AC Blown fuse F1 on Charger board 1557 1657 Battery charging has been turned off for some security reason e g too high current consumption Valid for Charger board 1657 FAULT Mains ext power supply CU xx The fault is activated after 1 300 minutes 66 because of Loss of mains i e no...

Страница 71: ...server and in other control units in the system Fault in the MMI board 5011 software or the MMI board Check the cable between the boards This is a very serious fault Call for service personnel engineer immediately FAULT No reply expansion board x CU xx Valid for the 8 zones exp board 4580 the 8 relays exp board 4581 and the Inputs and outputs exp board 4583 mounted in the control unit no xx EBL512...

Страница 72: ...b FAULT Printer control unit xx This is valid for an EBL512 G3 type 5000 with printer Control unit no xx Faulty printer Printer not correctly connected No paper FAULT Read write site data SSW CU xx SSW data that is changed during operation i e sensor values access codes etc If the C U was made powerless i e no mains and no the battery without first doing a Safe shut down of control unit via menu H...

Страница 73: ... 2210 2312 Faulty sensor The analog detector 33xx 43xx in NORMAL mode The built in self verification function has reported a fault status Detector removed from its base generates FAULT No reply FAULT Short circ int COM loop x CU xx Short circuit on the connection ribbon cable to or between the expansion boards 458x in the control unit xx EBL512 G3 FAULT Short circuit COM loop x CU xx Short circuit...

Страница 74: ... Sh circ loop x CU xx ASF7 CU FAULT Sh circ loop x CU xx ASF6 CU FAULT Sh circ loop x CU xx ASF5 CU FAULT Sh circ loop x CU xx ASF4 CU FAULT Sh circ loop x CU xx ASF3 CU FAULT Sh circ loop x CU xx ASF2 CU FAULT Sh circ loop x CU xx ASF1 CU FAULT Sh circ loop x CU xx ASF0 CU Short circuit on the COM loop x one or more short circuit isolators are connected on the loop Check the specified and isolate...

Страница 75: ...ng in the downloaded SSD FAULT SSD FBP xx 1587 board x CU xx FBP 1826 1828 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD FAULT SSD FBP xx CU xx FBP 1826 1828 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD FAULT Supervised output x CU xx If the output is programmed for sounders type 3 alar...

Страница 76: ...15 blinking Check fuses F1 F8 on the output unit p c b Short circuit break on the connected wires Wrong no end of line resistor One or more connected units have been removed stolen FAULT System program MMI board CU xx A fault in the control unit no xx MMI board 5011 software LED System fault is turned on This is a very serious fault Call for service personnel engineer immediately FAULT Temperature...

Страница 77: ...the same type as programmed Change the programming or the unit FAULT Zone line input tech no xxxxxx Detector mounted in an ADB 2330 faulty removed detector or Ext line input to an ADB 2330 break on a wire or wrong no end of line resistor or Zone interface 2335 2226 input break on a wire or wrong no end of line resistor or Zone interface 2226 No ext power supply or Multi purpose I O unit 3361 monit...

Страница 78: ...s and or acknowledged but not corrected faults The first fault in the list is the most recent fault When a fault is acknowledged and corrected it will be removed from the list and a new fault can be shown Corrected faults are shown in the event log menu H4 U7 All faults have to be individually acknowledged one by one push button Fault acknowledge P6 Use or keys to scroll If a fault has been correc...

Страница 79: ...d page 81 The SSD is created via the PC program Win512 8 See also chapter Calibration of supervised outputs H5 A1 page 127 18 2 Control Units in a TLON network In a TLON network there is two or more control units connected A TLON connection board 1590 is required in each control unit connected to the network 69 When the 1590 board is on place and the cables are connected70 for each control unit do...

Страница 80: ...ad the SSD Later when one or more control units shall be stated up Open the project in TLON Manager add the control unit s and install download it according to the separate TLON network documentation Open the SSD in Win512 and add the control unit s and download the SSD to all control units NOTE For highest security the function Redundancy in distributed system can be used in a system with a TLON ...

Страница 81: ...bers Zone Address in the systems are not the same The system properties have to be the same Use one of the systems and add to it the control units etc from the other system 74 If it is known from the beginning that two systems shall be one in the future it is possible to give the control units in the system respectively the final control unit numbers right from the beginning in order to get the co...

Страница 82: ...x 80 Open the current project in TLON Manager delete one control unit according to the separate TLON network documentation Open the SSD for the current system via Win512 Delete one control unit and the units connected to it and download the new SSD according to chapter Programming SSD download page 81 ...

Страница 83: ... 78 For security reasons the SSD i e the installation will be automatically saved after the download 19 1 Check All Loop Units In the Win512 COM loop icon pop up menu select Check All Loop Units This function can be used after or before the download of SSD The function is as follows The control unit will find all units that are connected on the COM loop The addresses 0 127 will be reported to Win5...

Страница 84: ...nit will now restart Now an automatic reset restart will take place see chapter Restart page 88 After the reset restart another text message will be shown in the display FAULT Site specific data SSD CU nn Date MM DD Time HH MM This text message means that the SSD have not been downloaded i e a new download has to be performed 19 3 Control Units in a TLON network The SSD for all control units can b...

Страница 85: ...age The user definable text messages will be printed out when a printer is available See also chapter Fire alarm page 41 Unique user definable text messages for each alarm point and each zone line input can also be shown in Display units 2235 2236 connected on the COM loops All user definable text messages up to 40 alphanumeric characters each are created and downloaded via Win512 See Planning Ins...

Страница 86: ...ialog box and do the required settings e g the path for the S W BIN file and or the language SST file83 Do not forget to mark the checkbox respectively 2 Set the c i e in Bootstrap mode i e set jumper JP1 BOOT in position on the main board 1556 3 Do a reset restart i e set jumper JP4 RESET in position momentarily approx 1 second 4 The buzzer will now sound intermittent and LED LD101 starts blinkin...

Страница 87: ...L512 version 2 7 x In the EBL512 G3 control units the software has to be EBL512 G3 United version 2 7 x which has to be downloaded via Win512 version 2 7 x For download of new S W in each EBL512 control unit follow the procedure described above Since some control units do not have contact with some control units during the downloading the following faults might be generated FAULT CU xx has no cont...

Страница 88: ... specified in the Key field Only authorised personnel have access to Key512 5 When the password is typed click OK NOTE If a running EBL512 system shall be downgraded bear in mind that the Site Specific Data SSD created in a new Win512 version e g 2 7 x cannot be opened in an earlier Win512 version e g 2 2 5 New SSD has in this case to be created in the earlier Win512 version ...

Страница 89: ...trap mode 5 In the Win512 settings dialog box click Read The buzzer will be silenced the actual settings shown and in the Win512 log view will be shown System information has been uploaded 6 Write the new settings in the fields respectively 7 Do like 3 4 above Click Download The buzzer will be silenced and a Win512 box will be displayed Click OK NOTE If Max loop units are changed a Please enter yo...

Страница 90: ...y will after the restart read the SSW data saved in the Flash ROM 89 Action Data etc which will be deleted Data etc which will be not deleted Control unit power OFF 90 and then power ON again SSW90 FFD SSD SSI S W RESET jumper JP4 on the main board 1556 FFD SSW 88 SSD SSI S W SSW Reset command from Win512 or TLON Manager FFD SSD SSI S W SSW Automatically due to external disturbance 91 FFD SSW 88 S...

Страница 91: ...ault acknowledge menu H6 the LEDs will be turned OFF if there are no other faults After reset a synchronization of the control units starts automatically See also chapter Synchronize the control units H8 S10 page 152 After reset required disablements have to be done Memory fault In case of a fault in the S W system program the following text message will be shown in the display Memory fault in pro...

Страница 92: ...ng When the text Booting appears press Access and 0 1 sec later also press 1 and the Boot menu will be shown 1 Reset 2 Clear mem 4 Read AD 5 MSClo ck 6 Checksum 7 Cursor 8 Texts Press 1 to perform a reset restart you will also leave the Boot menu Press 2 to open the Clear memory menu see below The alternatives 3 8 are for R D use only The Clear memory menu 1 SSD 2 SSW 3 SysInfo 4 Echel oninfo 5 Te...

Страница 93: ...Panasonic Eco Solutions Nordic AB MEW01457 Rev Operating Instructions Fire alarm system EBL512 V2 7 x 91 NOTE After clearing the SSW perform a Power off power on reset restart directly ...

Страница 94: ... are circular i e if you scroll with and the last menu is reached the first menu comes up next Quick jump can be used within each menu e g in menu H1 press 6 for a quick jump to menu H6 1 and 0 within 1 sec 10 Instead of a menu identification e g B1 the letter L can be shown which means that it is a List Use and to scroll in the list Use and to move the cursor in a menu Use Return to return from a...

Страница 95: ...vated etc See also chapter Alphanumeric display LCD in EBL512 page 21 NOTE If the control unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in Win512 There will be an automatic ending of the test mode one hour after the latest tested alarm point zone See also chapter Perform ZONE TEST test mode H7 page 139 Action Text in display Comments Access A...

Страница 96: ...t be able to activate fault After 60 minutes or Return Return Zones in test mode 001 002 003 004 NOTE See chapter Alphanumeric display LCD in EBL512 page 21 regarding priority order You are no longer in menu H1 but still in test mode When required Access code A Zone in TEST MODE 001 002 003 004 End test ACCEPT Press A to end the test mode A Test of routing equipment 0 1 Yes 0 No ACCEPT The LED Tes...

Страница 97: ...ones in test mode 001 002 003 004 NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will not be a fire alarm activated Instead the alarm point will be disabled and has to be re enabled again via menu H2 B5 When the Fire door closing function is used the fire door will be closed when the detectors controlling the door are tested via the test mode ...

Страница 98: ...OM BS4 loops zone interface inputs and or MIO inputs can be disabled via menu H8 S2 Alarm points disabled via time channels are not limited and must not be counted Up to 200 outputs can be individually disabled via menu H2 B3 Disabled output will stay in or return to the normal condition for the output respectively Disabled outputs via menu H2 B8 and menu H2 B9 are not limited and must not be coun...

Страница 99: ...to chapter Access see page 92 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 A Disable zone 000 ACCEPT Write zone number e g 001 Disable zone 001 ACCEPT Press A to accept A Automatic re enabling 0 0 No 1 Yes Time HH MM ACCEPT Default is current time 3 hours Press 1 for aut re enabling and accept or change the time max 24 hours Press A to accept LED Disablements L8 will l...

Страница 100: ...zone addresses have to be re enabled via menu H4 B2 Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B2 Disable zone address ACCEPT B2 A Disable zone 000 Address 00 ACCEPT Write zone number and address e g 001 01 Disable zone 001 Address 01 ACCEPT Press A to accept A Automatic re ...

Страница 101: ...ol unit 00 Type 0 0 Loopunit 1 S 2 R 3 RE 4 ES ACCEPT 4 ES not valid in Swedish SBF convention Write C U No and press 0 RU4 2265 or SU4 2262 2263 or MIO 3361 or AOU 3364 or ASI 3377 or ASB 3378 1 S0 S3 2 R0 R1 3 Relay board 1581 4 1583 board output Extinguishing system Press A to accept A Depending on the chosen type 0 1 2 3 resp 4 the following will be shown Disable 00 0000 control output 0 ACCEP...

Страница 102: ...ns Fire alarm system EBL512 V2 7 x 100 A Disable output control unit 00 Type 0 0 Loopunit 1 S 2 R 3 RE 4 ES ACCEPT If more disablements shall be done continue like above If not press Return to menu B3 Scroll or press Return to menu H2 Scroll or press Return to log off ...

Страница 103: ...e address that are individually disabled via menu H2 B2 Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B4 Re enable zone ACCEPT B4 A Re enable zone 000 ACCEPT L If there are no zones to re enable menu B4 will be shown again L a list in which you can scroll If it s the correct zo...

Страница 104: ...than automatic re enabling When all alarm points zones have been re enabled The LED Disablements L8 will be turned OFF if there are no other disablements in the system Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B5 Re enable zone address ACCEPT B5 A Re enable zone 000 Address...

Страница 105: ...S ACCEPT 4 ES not valid in Swedish SBF convention Press 0 RU4 2265 or SU4 2262 2263 or MIO 3361 or ASI 3377 or ASB 3378 1 S0 S3 2 R0 R1 3 Relay board 1581 4 1583 board output Extinguishing system Press A to accept A Depending on the chosen type 0 1 2 3 resp 4 the following will be shown Re enable 00 0000 output 0 ACCEPT L Re enable control unit 00 S0 ACCEPT L Re enable control unit 00 R0 ACCEPT L ...

Страница 106: ...ions Fire alarm system EBL512 V2 7 x 104 A Re enable control output type 0 0 Loopunit 1 S 2 R 3 RE 4 ES ACCEPT If more re enablements shall be done continue like above If not press Return to menu B6 Scroll or press Return to menu H2 Scroll or press Return to log off ...

Страница 107: ...t page 52 Menu H2 B5 shall be used instead Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B7 Re enable non reset zone address ACCEPT B7 A This menu is no longer valid Use menu H2 B5 ACCEPT A Re enable non reset zone address ACCEPT B7 Scroll or press Return to menu H2 Scroll or p...

Страница 108: ...led until re enabled again via this menu Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B8 Disable Re enable all control exting and ventilation outputs ACCEPT B8 A Disable 0 or Re enable 1 outputs 1 CU 99 99 All ACCEPT Press 1 or 0 write the CU number or 99 for all CUs 97 and pr...

Страница 109: ...units can be disabled or the outputs in all control units The outputs will be disabled until re enabled again via this menu NOTE This function is not the same as push button Silence alarm devices P3 see chapter Silence Alarm devices page 28 This function has higher priority than Silence alarm devices Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H2 D...

Страница 110: ...ress A If you don t want to change anything e g if you only want to see the S W version press Return instead of A to return to menu H3 Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H3 Set calendar and clock ACCEPT H3 A Date YY MM DD Time hh mm ss Weekday W 1 M 7 S VER vvvvvvvvvvvv NOTE The date is in some conventions languages shown as DD MM YY Here ...

Страница 111: ... x 109 26 1 Daylight saving time Use daylight saving time is selected via Win512 If selected the time is automatically changed when the Daylight saving time period starts and stops respectively Forward 1 hour the last Sunday in March 02 00 03 00 Backward 1 hour the last Sunday in October 03 00 02 00 ...

Страница 112: ...chapter Access see page 92 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1 yes U1 Press 1 for an automatic print out of all disablements in the system Press A for presentation in the display A or 1 When A is pressed the disablements will be shown in the display Some examples Zone XXX address XX disabled L or Zone XXX is disabled L or Alarm points a...

Страница 113: ...ime channel Printout 1 yes U2 Press 1 for an automatic print out of all disablements in the system Press A for presentation in the display A or 1 When A is pressed the disablements will be shown in the display e g Zone XXX address XX disabled by time channel L L a list in which you can scroll If there are no disablements and if Return is pressed menu U2 will be shown again Printing started To stop...

Страница 114: ...printer ACCEPT H4 A Disablement Printout 1 yes U1 Scroll to menu U3 Doors open Printout 1 yes U3 Press 1 for an automatic print out of all open doors Press A for presentation in the display A or 1 When A is pressed open doors will be shown in the display Two examples Door open CU 00 L or Door open FBP x board x CU xx L L a list in which you can scroll If there are no open doors and if Return is pr...

Страница 115: ...o chapter Access see page 92 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1 yes U1 Scroll to menu U4 Activated 2 zone address dependent zone address Printout 1 yes U4 Press 1 for an automatic print out Press A for presentation in the display A or When A is pressed the active zone address or zone will be shown in the display e g Co incidence alarm ...

Страница 116: ...to accept Here follows the alternative A no printout The alternative 1 printout follows below A Start Sensor 000000 Write the sensor s techn number and or press A to accept E g 000001 Depending on the type the following will be shown A Type 3304 Sensor 000001 Momentary XX X m Weekly XX X m This is a list in which you can scroll or use to see the next information window for the selected sensor Pres...

Страница 117: ...cal number in the system Here follows the alternative 1 printout Scroll to menu U5 Sensor values Printout 1 yes U5 Press 1 to accept 1 Start Sensor 000000 End Sensor Write the techn numbers and or press A to accept A Printing started To stop printing press C and 0 simultaneously ACCEPT Press A and menu U5 will be shown again A Start Sensor 000000 Write the sensor s techn number and or press A to a...

Страница 118: ... sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be set to the default value otherwise the new clean sensor will inherit the old sensor s value It is possible to clear the week average sensor value for each sensor individually see chapter Clear weekly average H8 S5 page 146 See also chapter Acknowledge SERVICE signal H8 S4 page ...

Страница 119: ...thm can be used No values offset level etc can be set via menu H4 U5 i e these values have to be set via Win512 The Short name set in Win512 can be 5 characters When scrolling the message Please Wait might be shown for a second and No more sensors found in the system before the lowest and after the highest possible technical number in the system NOTE If an algorithm is set changed via menu H4 U5 t...

Страница 120: ...nsor 000001 Momentary XX X m Weekly XX X m This is a list in which you can scroll or use to see the next information window for the selected sensor Press Return to Enter technical number Sensor 000001 Min XX X m Perf Factor X XX m Max XX X m NOTE XX X m XX X obscuration per meter Perf Factor see below this table Sensor 000001 Current algorithm N 15 N 15 short name see separate table page 115 Press...

Страница 121: ...CU s will now restart ACCEPT A Sensor values Printout 1 yes U5 Menu U5 will be shown for a few seconds and then the affected control unit s will restart See chapter Restart page 88 NOTE The new algorithm will not be in use until after the restart In case of an automatic log off and one or more algorithms are changed the affected control unit s will restart Perf Factor Performance factor Low min 0 ...

Страница 122: ... the sensor s techn number and or press A to accept A Sensor 000003 Min XX C Momentary XX C Max XX C This is a list in which you can scroll or use to see the next information window for the selected sensor Press Return to Enter technical number Sensor 000003 Current algorithm A1 A1 short name see separate table page 115 Press Return to Enter technical number or press Access to change the algorithm...

Страница 123: ... until after the restart In case of an automatic log off and one or more algorithms are changed the affected control unit s will restart Sensor values and setting alarm algorithm for the Analog multi detector 3316 The procedure is similar to the procedure for 3304 and 3308 respectively When using the smoke detector information will be shown before the heat detector information The algorithms can o...

Страница 124: ... have to be cleaned replaced soon The service signal has to be acknowledged see chapter Acknowledge SERVICE signal H8 S4 page 145 It is not possible to get a print out from menu H4 U6 Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1 yes U1 Scroll to menu U6 Sensors activa...

Страница 125: ...s U1 Scroll to menu U7 Event log Printout 1 yes U7 Press A for display presentation or Press 1 for print out Alternative A When A is pressed an event will be shown in the display e g FIRE ALARM zone 123 address 45 MM DD HH MM XX or FIRE ALARM zone 456 Many alarms in zone MM DD HH MM XX The most recent event will be shown i e use to scroll upwards in the list Press Return to menu U7 XX in the examp...

Страница 126: ...ntries have different conventions i e country specific functions etc The convention is set changed via Win512 menu Tools Settings Win512 Settings dialog box 103 It is not possible to get a print out from this menu Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1 yes U1 Sc...

Страница 127: ...quired Via a PC104 and Win512 access code for level 5 you can download backup site specific data SSD download of S W settings configurations C U system data create and download the user definable text messages shown in the alphanumeric display in the C U ext FBP and in the Display units Via a PC105 and TLON Manager you can do the TLON network programming configuration TLON Manager is used for prog...

Страница 128: ...y Comments Access According to chapter Access page 92 Perform monthly test ACCEPT H1 Scroll to menu H5 Service ACCEPT H5 A Access code _ If login was made with code for level 4 no code is needed Enter code for level 4 4 digits Access code The digits are replaced in the display NO ACCESS The access code was not correct Try again Calibration of supervised outputs ACCEPT A1 The access code was correc...

Страница 129: ...mally low default or normally high 24V but during the calibration the outputs will automatically be low i e a normally high output will be low during the calibration a few seconds Action Text in display Comments Access According to chapter Access code for service H5 see page 126 Calibration of supervised outputs ACCEPT A1 A Calibration in progress Please wait Calibration of supervised outputs ACCE...

Страница 130: ...orget to turn off this mode after the commissioning Action Text in display Comments Access According to chapter Access code for service H5 see page 126 Scroll to menu A2 Sensitive fault detection mode ACCEPT A2 A Sensitive fault detection mode 0 0 off 1 on Press A or 1 and A to accept ON is indicated by LED Fault tx activated L11 and the Fault output for routing equipment This mode is ON until tur...

Страница 131: ...s you see the text COM loop is currently communicating in A direction alternatively B direction in menu A3 When you log out or if you are automatically logged out after 60 min the communication will start in the A direction Action Text in display Comments Access According to chapter Access code for service H5 see page 126 Scroll to menu A3 Direction for communication on COM BS4 loop ACCEPT A3 A Se...

Страница 132: ...he control unit the following text message will be shown No SSD downloaded NOTE In the British Standard Marine Application convention it is possible to change the alarm algorithm for some type of analog detectors see chapter Algorithm setting via menu H4 U5 page 117 If one or more alarm algorithms are changed the following infor mation will be shown instead of the information shown above A Name xx...

Страница 133: ...00 mA is presented as 3800 mA Charging current 100 mA can not be correctly presented The displayed Charging value xxxx mA shall be multiplied by two when High current charging mode has been selected via jumper JP2 on the Charger board 1657 JP2 shunted High current charging mode Action Text in display Comments Access According to chapter Access code for service H5 see page 126 Scroll to menu A5 Dis...

Страница 134: ...n on COM BS4 loop ACCEPT A6 A Select type of loop 0 0 COM 1 BS4 ACCEPT Select type of loop Press A to accept A or 1 A Display current consumption on COM loop 0 CU 00 ACCEPT Write loop number board number 0 3 and control unit number Press A to accept Display current consumption on BS4 loop 0 board 0 CU 00 ACCEPT A Wait No reply from control unit If the control unit don t exist or don t answer this ...

Страница 135: ...ions and the loop units All values are set to 0 after restart and or after re connection of COM loop menu H8 S3 Action Text in display Comments Access According to chapter Access code for service H5 see page 126 Scroll to menu A7 Display statistics for COM loop ACCEPT A7 A For which CU 00 and COM loop 0 shall statistics be displayed ACCEPT Write control unit and loop number Press A to accept A Wai...

Страница 136: ...s being polled Autronica interface board 1584 BY3 right pin 0 V BS4 board Autronica interface board 1584 Action Text in display Comments Access According to chapter Access code for service H5 see page 126 Scroll to menu A8 Select unit on COM BS4 loop to use for trigging ACCEPT A8 A Select type of loop 0 0 COM 1 BS4 ACCEPT Select type of loop Press A to accept A or 1 A CU 00 Loop 0 Address 000 ACCE...

Страница 137: ...can be activated for address setting NOTE The units have to be in operation and in quiescent condition i e the units have to have an address already Action Text in display Comments Access According to chapter Access code for service H5 see page 126 Scroll to menu A9 Activate address setting mode for DU ACCEPT A9 A Activate address setting mode for DU CU 00 1587 board 0 DU 00 ACCEPT Write control u...

Страница 138: ...Access According to chapter Access code for service H5 see page 126 Scroll to menu A10 Change access code for PC communication ACCEPT A10 A Access code _ New code Verify The digits are replaced in the display Incorrect access code NO change The code was not correct Try again Change access code for PC communication ACCEPT A10 The code was correct and is now changed to the new code Scroll or press R...

Страница 139: ...ify Enter the old code the new code and the new code again Access code New code Verify The digits are replaced in the display Incorrect access code NO change The code was not correct Try again Change access code for service ACCEPT A11 The code was correct and is now changed to the new code Scroll or press Return to H5 Scroll or press Return to log off NOTE After change of access code it is recomme...

Страница 140: ...xxxx Date MM DD Time HH MM See comments NOTE The date is in some conventions languages shown as DD MM This is a list in which you can scroll The first fault in the list is the most recent fault If a fault is corrected the text Serviced113 is shown To acknowledge the fault shown in the display press Fault acknowledge Fault acknowledge FAULT Xxxxxxxx Date MM DD Time HH MM Acknowledged The fault is n...

Страница 141: ...ccess see page 92 Scroll to menu H7 Perform ZONE TEST ACCEPT H7 A Zone to be set in TEST MODE Start test ACCEPT Write zone numbers e g 001 002 003 004 Zone to be set in TEST MODE 001 002 003 004 Start test ACCEPT Press A to start the test mode A Zones are set in test mode wait LED Test mode L9 will light up Zone in TEST MODE 001 002 003 004 End test ACCEPT Perform the tests The zone s will stay in...

Страница 142: ...ACCEPT H7 The LED Test mode is turned OFF If more zones are to be tested continue as above If not scroll or press Return to log off NOTE During the test the following information will be shown in all other c i e displays Zones in test mode 001 002 003 004 In DBI Danish convention only one zone NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will...

Страница 143: ... is required here Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H8 Maintenance ACCEPT H8 A Access code _ When required see above enter the access code for level 3 Enter the code 4 digits Access code The digits are replaced in the display NO ACCESS The access code was not correct Try again Disable or re enable outputs for routing equipment ACCEPT S1 T...

Страница 144: ...arms are required Disabled outputs are indicated by LEDs Disablements L8 and Fault Disablements Fire brigade tx L15 Disabled outputs are listed in menu H4 U1 Action Text in display Comments Access According to chapter Access code for maintenance see page 141 Disable or re enable outputs for routing equipment ACCEPT S1 A Routing equipment for FIRE 1 FAULT 1 1 enabled 0 disabled ACCEPT To move the c...

Страница 145: ...OM 1 BS4 2 DET8 3 Loop Unit ACCEPT Press 0 COM loop 1 BS4 loop 2 Expansion board 1580 3 Addr zone interface 2226 2335 2821 or 3361115 MIO Press A to accept A Depending on the chosen type 0 1 2 or 3 the following will be shown Disconnect COM Loop 0 CU 00 ACCEPT Write the required numbers Press A to accept Disconnect BS4 Loop 0 Board 0 CU 00 ACCEPT Disconnect DET8 input 0 Board 0 CU 00 ACCEPT Discon...

Страница 146: ...S4 2 DET8 3 Loop Unit ACCEPT Press 0 COM loop 1 BS4 loop 2 Expansion board 1580 3 Addr zone interface 2226 2335 3361 MIO Press A to accept A Depending on the chosen type 0 1 2 or 3 the following will be shown Re connect COM Loop 0 CU 00 ACCEPT Write the required numbers Press A to accept Re connect BS4 Loop 0 Board 0 CU 00 ACCEPT Re connect DET8 input 0 Board 0 CU 00 ACCEPT Re connect input techni...

Страница 147: ...ance see page 141 Scroll to menu S4 Acknowledge SERVICE signal ACCEPT S4 A Sensor xxxxxx needs service L NOTE The list order in this menu is as follows a Technical number order in the control unit this menu is opened b Technical number order in the rest of the system If there are no sensors to acknowledge menu S4 will be shown again L a list in which you can scroll If it is the correct sensor to a...

Страница 148: ...irst replace the sensor then clear the week average value as soon as possible Authorised service personnel only must do this Used incorrectly it can cause nuisance fire alarms The first week average sensor value after clearing will be calculated within one hour and after that each week Action Text in display Comments Access According to chapter Access code for maintenance see page 141 Scroll to me...

Страница 149: ...ible to de activate disable the AA function i e the AA function will be disabled for the alarm points zones programmed for Alert Annunciation in spite of the time channel is on or if they are programmed to be continuously enabled The AA function will stay de activated disabled until re activated re enabled again via this menu Action Text in display Comments Access According to chapter Access code ...

Страница 150: ...8 S7 or if a fire alarm is activated in the system Action Text in display Comments Access According to chapter Access code for maintenance see page 141 Scroll to menu S7 Test alarm devices ACCEPT S7 A Test alarm devices on CU 00 99 All ACCEPT Write a CU no or 99 for all CUs and press A to accept A Test of alarm devices in progress End test ACCEPT The test will continue for one hour if not stopped ...

Страница 151: ...enu S8 Safe shut down of control unit ACCEPT S8 A Shut down control unit 00 0 1 Yes 0 No ACCEPT Write the C U number 1 yes and A Please Wait Shown for 3 sec then one of the three alternatives In the CU that will be shut down when a front is available Ready for shut down break the power Automatic restart within nnn seconds Count down starts from nnn 300 seconds Disconnect the power supply mains and...

Страница 152: ...be automatically reset after one hour Action Text in display Comments Access According to chapter Access code for maintenance see page 141 Scroll to menu S9 Activate address in alarm mode ACCEPT S9 A Select zone 000 address 00 ACCEPT Write the zone and address Select zone 123 address 45 ACCEPT Press A to accept start the fire alarm A POINT 123 45 No 001 User definable text if programmed Normal fir...

Страница 153: ...are in menu H8 S9 and multiple reset is used or if you are logged out by pressing Return two times or automatically after 10 minutes Alternative a Reset Activate address in alarm mode ACCEPT S9 Scroll or press Return to menu H8 Scroll or press Return to log off Alternative b Reset Blank NOTE Multiple reset is default 119 By Single reset each point has to be reset individually 119 Alarm reset is se...

Страница 154: ... in the system Action Text in display Comments Access According to chapter Access code for maintenance see page 141 Scroll to menu S10 Synchronize the control units ACCEPT S10 A Shall synchronization be started 0 1 Yes 0 No ACCEPT Press 1 and A to start the synchronisation or press A to go directly to the field Synchronization completed or press Return to menu S10 1 A Synchronization in progress 0...

Страница 155: ...nstructions Fire alarm system EBL512 V2 7 x 153 A to start the synchronisation or press A to go directly to the field Synchronization completed Return Synchronize the control units ACCEPT S10 Scroll or press Return to menu H8 Scroll or press Return to log off ...

Страница 156: ...ify Enter the old code the new code and the new code again Access code New code Verify The digits are replaced in the display Incorrect access code NO change The code was not correct Try again Change access code for maintenance ACCEPT S11 The code was correct and is now changed to the new code Scroll or press Return to menu H8 Scroll or press Return to log off NOTE After change of access code it i...

Страница 157: ...ts inputs ACCEPT C1 A Depending on activated output and or input the following will be shown Output AAA PP activated at HH MM User definable text message if progr This is a list in which you can scroll AAA interlocking comb area PP interlocking comb point within the area Press Return to menu C1 Output AAA PP act HH MM input act HH MM User definable text message if progr Input AAA PP activated at H...

Страница 158: ...et has to be performed via menu H9 C3 Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H9 Interlocking outputs and inputs ACCEPT H9 A Activated interlocking outputs inputs ACCEPT C1 Scroll to menu C2 Activate interlocking output ACCEPT C2 A Activate interlocking output area 000 point 00 ACCEPT Write the area and point e g Activate interlocking output ar...

Страница 159: ...d via menu H9 C2 The output has to be reset via this menu Interlocking output activated via Web server II The output has to be reset via this menu Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H9 Interlocking outputs and inputs ACCEPT H9 A Activated interlocking outputs inputs ACCEPT C1 Scroll to menu C3 Reset interlocking output ACCEPT C3 A Reset in...

Страница 160: ...d in menu H4 U1 from which it is also possible to get a print out The LED Disablements L8 is also indicating one or more disabled interlocking outputs Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H9 Interlocking outputs and inputs ACCEPT H9 A Activated interlocking outputs inputs ACCEPT C1 Scroll to menu C4 Disable interlocking output ACCEPT C4 A Di...

Страница 161: ...00 00 will be re enabled at the same time Action Text in display Comments Access According to chapter Access see page 92 Scroll to menu H9 Interlocking outputs and inputs ACCEPT H9 A Activated interlocking outputs inputs ACCEPT C1 Scroll to menu C5 Re enable interlocking output ACCEPT C5 A Re enable interlocking output area 000 point 00 ACCEPT This is a list in which you can scroll If there are no...

Страница 162: ... Verify Enter the old code the new code and the new code again Access code New code Verify The digits are replaced in the display Incorrect access code NO change The code was not correct Try again Change access code for daily duties ACCEPT H10 The code was correct and is now changed to the new code Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutd...

Страница 163: ...n control unit Put back the fuse and acknowledge the fault Menu H6 Remove fuse F5 not F1 F4 on the connection board 1555 The following fault message is to be shown FAULT Supervised output 0 CU xx NOTE xx is depending on control unit Put back the fuse and acknowledge the fault When output units type 2262 2263 are installed Remove the battery fuse F3 on the rectifier p c b The following fault messag...

Страница 164: ...ows Read all instructions before changing the paper roll Open the control unit door Unlock the metal inner door by removing the screw placed on top to the left of the inner door Open the inner door Remove the old paper roll carefully cut the paper so that the paper within the printer remains there Take the new paper roll tape the new paper to the old paper and place the paper roll on the printer P...

Страница 165: ...and some unique data will be stored on the 1556 Main board After replacing a TLON connection board to another or replacing both a TLON connection board and a main board do Replace Update and Save in TLON Manager In TLON Manager version 2 0 Save will be automatically done after Update After replacing a main board to another not the TLON connection board do Update and Save in TLON Manager In TLON Ma...

Страница 166: ...l unit supervises the batteries and a fault will be generated if something goes wrong They are rechargeable sealed lead acid batteries and normally maintenance free The producer s instructions shall always be followed The ambient temperature affects the battery capacity self discharge and life span It should not be higher than normal room temperature approx 20 22 C For highest safety batteries use...

Страница 167: ...obacco smoking in connection with bad ventilation can cause a fire alarm Welding grinding cutting sawing drilling These kind of jobs cause smoke Carpet welding Welding of plastic carpets causes a smoke that can be almost invisible but it still influences the smoke detectors sensors Cooking fumes toasting candles It is not only normal smoke that influences smoke detectors sensors It is all kinds of...

Страница 168: ...nd thus cause unnecessary alarms Miscellaneous Choosing another type of detector can solve certain problems Bear also in mind that the coverage area can be different for different types of detectors It is however not always the best action to change detector type Here is a list of other actions programmed via Win512 which can be used Another alarm algorithm can be used Alarm delay for smoke detect...

Страница 169: ...ignal has been activated in the system contact your local dealer for replacement of the sensors detectors Metal objects must absolutely not be stuck into the sensor detector Static electricity might destroy the detector Defective faulty discarded and replaced sensors detectors shall be taken care of as radioactive waste They shall be packed in chock absorbing material to make a stable parcel PLEAS...

Страница 170: ...Panasonic Eco Solutions Nordic AB MEW01457 Rev Operating Instructions Fire alarm system EBL512 V2 7 x 168 40 Revision history ...

Страница 171: ...This page has deliberately been left blank ...

Страница 172: ...Panasonic Eco Solutions Nordic AB Jungmansgatan 12 SE 211 19 Malmö Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info pewnf eu panasonic com www panasonic fire security com ...