14-6
Serial Communications
590+ Series DC Digital Converter
Error Codes
ERROR REPORT (EE)
The EI-BISYNCH Prime Set contains the EE mnemonic. This is also an output parameter in the
MAIN PORT (P1), AUX PORT (P2) and SYSTEM PORT (P3) function blocks, where the
parameter value can be read and reset. Refer to the COMMS Option Technical Manual for
further details.
The following values are returned if an enquiry (reading information from the Converter) is
performed on this Read/Write parameter.
Writing any value to this parameter will set the value to >00C0. Clearing the last error value
may be useful in seeing a repetitive error re-occurring.
Value
Description
>00C0
No error
>01C7
Invalid mnemonic
>02C2
Checksum (BCC) error
>03C2
Framing or overrun error
>04C8
Attempt to read from a write-only parameter
>05C8
Attempt to write to a read-only parameter
>07C7
Invalid message format
>07C8
Invalid data (encoding error)
>08C8
Data out of range