Technical Specifications
11-7
590+ Series DC Digital Converter
Power Supply Fuses
Power Board
Identification
Fuse Rating
SSD Part No.
Frame 1
AH466407 (terminal board)
FS1, 5x20mm glass slow-blow
(for auxiliary supply, contactor, fan supply)
3A
CH540033
Frame 2
AH470330
FS1, 5x20mm glass slow-blow
(for auxiliary supply, contactor, fan supply)
3A
CH540033
Frame 3
AH385851
FS1, 5x20mm glass slow-blow
(for auxiliary supply, contactor, fan supply)
3A
CH540033
Frame 4 & 5
AH466701
FS3 and FS4, 5x20mm glass slow-blow
(for auxiliary supply, contactor, fan supply)
3A
CH540033
Frame H
AH466001
FS1, 5x20mm glass slow-blow
(for auxiliary supply, contactor, fan supply)
3A
CH540033
Field Fuses
Identification
Fuse Rating
SSD Part No.
Frames 1, 2 & 3
10x38mm
10A
CS470407U010
Frame 4 & 5
10x38mm
30A
CS470407U030
External field fuses are required for Frame H units.
Earthing/Safety Details
Grounding
Permanent earthing is mandatory on all units because the earth leakage current exceeds 3.5mA
ac/10mA dc under normal operating conditions. Permanent earthing can be made in two ways:
1.
By using a copper conductor of at least 10mm² cross-sectional area.
2.
By using a second conductor, through separate terminals electrically parallel to the
protective conductor.
Note:
Each conductor itself must meet the local requirements for a protective earth
conductor.
Input Supply Details
(TN) and (IT)
Units with or without external filters are suitable for use on earth referenced (TN) supplies, but
units used with a filter are not recommended for non-earth referenced (IT) supplies..
Earth Leakage Current
>50mA (all models)