Programming Your Application
6-59
590+ Series DC Digital Converter
PRESET
The Preset block allows you to select one of
eight preset inputs, which in turn may be
connected to other blocks of inputs.
Preset
PRESET OP (%)
[572]
–
0.00 %
OUTPUT
[593]
–
0.0
FALSE
–
[560] SELECT 1
FALSE
–
[561] SELECT 2
FALSE
–
[562] SELECT 3
FALSE
–
[563] INVERT
100.0
–
[559] MAX SPEED
FALSE
–
[600] LIMIT
FALSE
–
[610] GRAY SCALE
0.0
–
[564] INPUT 0
0.0
–
[565] INPUT 1
0.0
–
[566] INPUT 2
0.0
–
[567] INPUT 3
0.0
–
[568] INPUT 4
0.0
–
[569] INPUT 5
0.0
–
[570] INPUT 6
0.0
–
[571] INPUT 7
MMI Menu Map
1
SETUP PARAMETERS
2
PRESET SPEEDS
SELECT 1
SELECT 2
SELECT 3
INVERT O/P
MAX SPEED
LIMIT
GRAY SCALE
INPUT 0
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
PRESET O/P
OUTPUT
Parameter
Tag
Range
PRESET OP (%)
572
x.xx %
Scales the selected preset input by MAX SPEED.
OUTPUT
593
x.x
Outputs the selected INPUT value.
SELECT 1
560
FALSE / TRUE
Select inputs 1
SELECT 2
561
FALSE / TRUE
Select inputs 2
SELECT 3
562
FALSE / TRUE
Select inputs 3
INVERT
563
FALSE / TRUE
Changes the sign of the output. If TRUE, the output is of the opposite sign to the selected
input.
MAX SPEED
559
0.1 to 3000.0
Scaler for PRESET OP (%).
LIMIT
600
FALSE / TRUE
Clamp output to MAX SPEED if TRUE.
GRAY SCALE
610
FALSE / TRUE
Selects Gray Scale encoding when TRUE, Binary encoding when FALSE. When gray scale
is selected, only one input changes between state preventing the mis-selection of
intermediate states.
INPUT 0 to INPUT 7
564, 565, 566, 567,
568, 569, 570, 571
-3000.0 to 3000.0
Pre-set input variables.